CKP/QC/ARCH/01/001
Description
Architectural Work Inspection Form
GENERAL: FLOORS
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
1. FLOORS 1. Ponding not deeper than 3mm
a. Screed finish
2. Cracks not wider than 0.3mm
4. Tiles should not but tightly with each other; joint size
2-4mm or otherwise stated by Architect
Description
Architectural Work Inspection Form
GENERAL: FLOORS
Name : Location :
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
c. Timber strips 1. No cracks and warpage
Date : Date :
Description
Architectural Work Inspection Form
CEILING (BY VISUAL INSPECTION)
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
3. CEILING 1. Overall surface should be even, gaps between light
(BY VISUAL fittings and ceiling should not be seen
INSPECTION)
2. Formwork joints are grounded smooth
a. Skim coats
3. No spalling, leaks or stains
2. No stains
Date : Date :
Description
Architectural Work Inspection Form
DOORS AND WINDOWS
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
4. Doors & Windows 1. Alignment / level with walls
3. No rainwater leakage
Description
Architectural Work Inspection Form
DOORS AND WINDOWS
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
9. Door and frame corners maintained at right anglers
Date : Date :
Description
Architectural Work Inspection Form
PLUMBING AND SANITARY FITTINGS
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
5. PLUMBING AND 1. No damage or chokage
SANITARY
FITTINGS 2. Must be securely fixed
a. Gully and Floor 3. Trap's top to be lower than the surrounding floor level
Trap
3. No leakage at joints
2. No leakage at joints
Date : Date :
Description
Architectural Work Inspection Form
ROOF
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
6. ROOF Flat (Panel)
1. Ponding less than 3mm
a. Construction
2. No cracks or chips
Pitched
1. No sign of damage to roofing materials
2. No leaking
3. No rust or stains
Date : Date :
Description
Architectural Work Inspection Form
COMPONENTS
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
7. COMPONENTS 1. Mortar dropping should not be observed
b. Other components 1. For permanent fixtures which are not covered in the
standards, the fundamentals such evenness,
straightness vertically and consistency will still be the
basis for assessment
Date : Date :
Description
Architectural Work Inspection Form
EXTERNAL
Name : Location :
Drawing Ref. :
Date :
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
EXTERNAL 1. Corners of wall maintained at right angels
Alignment
3. Straightness of corners
Tiled finish 1. Tile joints aligned and between 2-4mm wide unless
specified
4. No efflorescene
Acceptability
ITEMS ITEMS TO BE CHECKED Contractor JKR Remark
Yes No Yes No
Architectural Coating 1. Substrate - see plaster finish
Date : Date :