This document contains a checklist for the equipment of Forced Draught Fan A. The checklist includes items to check the status and safety of various components, including motor temperatures, vibration switches, cooling water flows, start permissives, and damper positions. It aims to verify that the fan and related systems are in safe operating condition before startup.
This document contains a checklist for the equipment of Forced Draught Fan A. The checklist includes items to check the status and safety of various components, including motor temperatures, vibration switches, cooling water flows, start permissives, and damper positions. It aims to verify that the fan and related systems are in safe operating condition before startup.
This document contains a checklist for the equipment of Forced Draught Fan A. The checklist includes items to check the status and safety of various components, including motor temperatures, vibration switches, cooling water flows, start permissives, and damper positions. It aims to verify that the fan and related systems are in safe operating condition before startup.
S.N Statu Remar Signatur o Check List Description s k e Safety Interlocks 1 FD fan * motor winding R temp >130 DegC. 2 FD fan * motor winding Y temp >130 DegC. 3 FD fan * motor winding B temp >130 DegC. 4 FD Fan * motor DE bearing temperature >110 DegC. 5 FD Fan * motor NDE bearing temperature >110 DegC. 6 FD fan A Vibration switch A is Not Operated. 7 FD fan A Vibration switch B is Not Operated. Process Interlocks 1 In board bearing cooling water flow is normal. 2 Out board bearing cooling water flow is normal. 3 Air Heater is in running. 4 Seal air flow is adequate. 5 Steam Drum level is Normal. Start Permissive 1 FD fan * Remote Selected 2 FD fan * Start Push button pressed. 3 No natural draught purge in progress. 4 All burners are in a satisfactory shutdown condition. No flame indication from main burner or igniter flame 5 monitor. 6 All main fuel valves closed. 7 All burner air dampers are in open condition. 8 Air heater all air and gas dampers are in open. 9 FD fan * Inlet guide vane is in Close position. 10 FD fan * Inlet guide vane control loop in manual mode. 11 FD fan * Discharge Damper is in close position. 12 Other FD fan * Discharge Damper in close position. 13 FD fan * Switch gear available is Ok. 14 FD fan * Elec DIST is not disturbed. 15 FD fan* safety interlocks is not operated. (as per serial No E) 16 FD fan* process interlocks is Ok. (as per serial No F)