Professional Documents
Culture Documents
Calculation of Stabilizing Resistor in High Impedance Differential Protection - Electrical Concepts
Calculation of Stabilizing Resistor in High Impedance Differential Protection - Electrical Concepts
Calculation of Stabilizing Resistor in High Impedance Differential Protection - Electrical Concepts
Menu
Before going into the calculation part of Stabilizing Resistor, I will first explain the purpose of
Stabilizing Resistor in High Impedance Differential Protection.
Stabilizing Resistor in High Impedance Differential Protection is used to prevent the operation of
Relay in case of through fault. Through fault is a fault outside the zone of protection. Lets us
assume that High Impedance Differential protection is used to protect a Bus bar as shown in
figure.
It shall be noted here that, in High Impedance Differential Protection, all the CTs are connected
in parallel and then the four wires i.e. R, Y, B and N are connected with the Relay as shown in
figure above. If there is any fault in the bus, the according to Kirchhoff’s current law, the
summation of current will not be zero and a net current will flow through the Relay coil to
operate it. In normal condition, the summation of current will be zero and hence no current will
flow through the Relay coil and hence the Relay will be stable. Mathematically under normal
condition,
I1+ I2 + I3 = 0
As Relay sees only summation of current hence we normally employ an overcurrent element in
High Impedance Differential Protection. This is the main difference between a high impedance
and low impedance differential protection.
Let us consider a through fault i.e. fault outside the zone of protection. To be more specific, let a
fault take place after the CT of any feeder. If all the CT’s maintain the same nominal ratio for all
external faults the assumed scheme is perfectly valid since no current can flow in the relay coil.
However, when the instantaneous overcurrent relay is set low enough to give useful sensitivity
to internal faults the Relay may in practice operate falsely on external faults due to a reduction
of the nominal ratio of the fault CT resulting from fault CT core saturation. This reduction of the
fault CT nominal ratio results in a “false” differential relay current that may operate the
instantaneous overcurrent relay. The wort condition will be when a CT gets completely
saturated. Thus we need to make Relay insensitive for through fault. To do this we use
Stabilizing Resistor.
How Stabilizing Resistor makes Relay Insensitive to through Fault?
Well, the main cause for the flow of current through the Relay coil in High Impedance Differential
Protection is the Voltage across the terminals of CT. We consider the worst case here when a
CT gets completely saturated for through fault. When a CT gets completely saturated, it will no
longer will be a source of current rather it will behave purely as a Resistor having a value equal
to the CT secondary winding. Thus the fault current will not go toward the relay rather it will go
circulate through the saturated CT secondary only as current always chooses a path having
least resistance. Let the fault current be IF and the resistance of CT secondary be RCT. Therefore
the voltage developed across the saturated CT will be,
Or,
Rstb= Vs / Is
Or
Rstb= Vs = IF(RCT + 2RL) / Iswhen looping of CT is done at Panel or near Relay end.
Thus during through fault, for the worst condition of CT saturation, the current through the Relay
coil will not be enough to cross setting value of Is and thus will not operate.
Hope you enjoyed this post. Please write your views and comments. Thank you!
Power System Protection
High Impedance Differential Protection, Stabilizing Resistor
Concept of Subtransient, Transient & Steady State
Rated Normal, Short Circuit Making & Breaking, Short Time Current Rating & Operating
Duty Cycle of Circuit Breaker
9 thoughts on “Calculation of Stabilizing Resistor in High Impedance
Differential Protection”
Sumit
March 6, 2018 at 6:41 pm
Same logic and calculations are applicable for REF also? Please advise.
Reply
Aditya Kumar
March 6, 2018 at 6:42 pm
Reply
Sara
March 19, 2018 at 12:21 am
I was stuck in a old PVD manual for the last 2 hours and your article made it much
easier to understand. Thank you! May I ask what's your background?
Reply
Aditya Kumar
March 19, 2018 at 12:22 am
I am an electrical engineer.
Reply
F13
March 19, 2018 at 12:23 am
As what I read IF(RCT + 2RL) is the voltage developed across the CT for the
maximum through fault current.Hence Vs should be greater than this value but
less than the half of the the knee point to ensure the quick operation of the relay
.For the second condition ,how it will happen since the protection is already
instantaneous ?
Reply
Unknown
March 19, 2018 at 12:24 am
yes
Reply
Suhag Patel
October 19, 2018 at 9:33 pm
Nice clarification.
Reply
Rathinavel P
April 24, 2020 at 5:15 pm
Nicely explained.
Reply
admin
April 26, 2020 at 1:24 am
Leave a Comment
Name *
Email *
Website
Post Comment
Topics
Power System
Power System Protection
Electrical Machines
DC Machine
Measurement and Instrumentation
AC Circuit
Digital Electronics
Electrical Drives
Power Electronics
EM Theory
Recent Posts
Subscribe to our mailing list and get interesting stuff and updates to your email
inbox.
SUBSCRIBE NOW