MCC Inspection and Test Forms
MCC Inspection and Test Forms
MCC Inspection and Test Forms
OTHER FINDINGS:
RECOMMENDATIONS:
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :
POWER METER TEST REPORT
I. TEST DATA
Auxillary Voltage Rating :
CT Ratio :
PT Ratio :
Test ID Current Injected Voltage Injected Measured PF Measured kW Measured kVAR Measured KVA
@ 1.0 PF 1A
@ 0.9 PF lag 1A
@ 0.8 PF lag 1A
@ 0.5 PF lag 1A
@ 0.9 PF lead 1A
@ 0.8 PF lead 1A
@ 0.5 PF lead 1A
Remarks :
Item 1.
Circuit No. : CT Ratio :
Ammeter Serial No. :
Item 2.
Circuit No. : CT Ratio :
Ammeter Serial No. :
Item 3.
Circuit No. : CT Ratio :
Ammeter Serial No. :
Item 4.
Circuit No. : CT Ratio :
Ammeter Serial No. :
Remarks :
Criteria : Resistance reading shall not deviate by more than 50% between each phase. Watt loss shall not exceed 1000 W.
Standard : NETA ATS 2009/ IEC 60694
Judgement :
TEST : Contact/Winding Resistance Test Set, Make: Teldar Instrument, Model: TRM-50, Serial No.: 18350493
EQUIPMENT : Insulation Resistance Test Set, Make: Fluke, Model: 1587, Serial No.: 42350117
:
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :
overcurrent RELAY TEST REPORT
I. TEST DATA
51P ( Inverse Time OCR) Operating Characteristics:
Current Rating :
51P Current Setting :
Time Dial/Multiplier :
Characteristic Curve :
Standard :
50P ( Instantaneous OCR)
Current Rating :
50P Current Setting :
Time Delay :
50 Result:
Instantaneous Current Test Setting (A)
Instantaneous Injected Current (A)
Tripping Time (s)
Remarks :
: Teldar Relay Tester; Model: IRT-340; Serial No.: J82I930871; Calibration Date: December 20, 2019
Test Equipment
:
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :
Voltage RELAY TEST REPORT
I. TEST DATA
59 ( Overvoltage Relay) Operating Characteristics:
Rating ( V) :
OV Setting Voltage (V) :
Time Delay :
27 ( Undervoltage Relay)
Rating ( V) :
UV Setting Voltage (V) :
Time Delay :
UV (27) Result:
Pick-up Voltage (V)
Drop-out Voltage (V)
UV Injected Voltage (V) @ 80 % Tap
150% Set Tripping Time (s)
UV Injected Voltage (V) @ 50 % Tap
200% Set Tripping Time (s)
Remarks :
TEST : Insulation Resistance Test Set, Make: Megger, Model: MIT520/2, Serial No.: Defaced
EQUIPMENT :
:
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :
current tranformer TEST REPORT
Criteria : Turns ratio percent error shall not exceed 0.5% for relaying and 0.3% for metering, polarity shall be OK, Winding resistance
reading between phases shall differ by less than or equal to 5%.
Standard : IEEE C57.13/ IEEE 62-1995 (R2005)
Judgement :
III. CT Insulation Test - Secondary Winding:
Test ID Voltage Inj. Resistance @ Resistance @ Remarks
(V) °C ( MΩ ) 20°C ( MΩ )
CT1
CT2
CT3
Criteria : Turns ratio percent error shall not exceed 0.5% for relaying and 0.3% for metering, polarity shall be OK, Winding resistance
reading between phases shall differ by less than or equal to 5%.
Standard : IEEE C57.13/ IEEE 62-1995 (R2005)
Judgement :
III. CT Insulation Test - Secondary Winding:
Test ID Voltage Inj. Resistance @ Resistance @ Remarks
(V) °C ( MΩ ) 20°C ( MΩ )
CT1
CT2
CT3
Test : Current Transformer Analyzer, Make: Teldar, Model: ICT-100, S/N: 4294967295
Equipment : Insulation Resistance Test Set, Make: Megger, Model: MIT520/2, Serial No.: Defaced
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :
POTENTIAL TRANSFORMER TEST REPORT
ITEM NO. 1
DATE TESTED : MANUFACTURER :
PROJECT : TEMPERATURE : WEATHER:
EQUIPMENT : HUMIDITY :
CIRCUIT NO. : REFERENCE :
VOLTAGE (Pri) : TEMPERATURE : WEATHER:
VOLTAGE (Sec) HUMIDITY :
LOCATION : REFERENCE :
I. PT Ratio, Polarity & Winding Test:
Test ID Serial Test PT Ratio Turns Ratio Turns Ratio % Error Polarity Winding Resistance (Ω)
No. Connection (Rated) ( Rated) ( Measured) Primary Secondary
PT1
PT2
PT3
Criteria : Turns ratio percent error shall not exceed 0.5% for relaying and 0.3% for metering, polarity shall be OK, Winding resistance
reading between phases shall differ by less than or equal to 5%.
Standard : IEEE C57.13/ IEEE 62-1995 (R2005)
Judgement :
II. PT Insulation Test:
Test ID Voltage Inj. Resistance @ °C ( MΩ ) Resistance @ 20°C ( MΩ ) Remarks
(V) P-S/P-G/S-G P-S/P-G/S-G
PT1
PT2
PT3
ITEM NO. 2
DATE TESTED : MANUFACTURER :
PROJECT : TEMPERATURE : WEATHER:
EQUIPMENT : HUMIDITY :
CIRCUIT NO. : REFERENCE :
VOLTAGE (Pri) : TEMPERATURE : WEATHER:
VOLTAGE (Sec) HUMIDITY :
LOCATION : REFERENCE :
I. PT Ratio, Polarity & Winding Test:
Test ID Serial Test PT Ratio Turns Ratio Turns Ratio % Error Polarity Winding Resistance (Ω)
No. Connection (Rated) ( Rated) ( Measured) Primary Secondary
PT1
PT2
PT3
Criteria : Turns ratio percent error shall not exceed 0.5% for relaying and 0.3% for metering, polarity shall be OK, Winding resistance
reading between phases shall differ by less than or equal to 5%.
Standard : IEEE C57.13/ IEEE 62-1995 (R2005)
Judgement :
II. PT Insulation Test:
Test ID Voltage Inj. Resistance @ °C ( MΩ ) Resistance @ 20°C ( MΩ ) Remarks
(V) P-S/P-G/S-G P-S/P-G/S-G
PT1
PT2
PT3
: Turns Ratio Test Set, Make: Teldar, Model: TTR-3000, S/N: 1661923 ; Winding Resistance Test Set, Make: Teldar, Model: TRM-50, S/N: 18350493
Test Equipment
: Insulation Resistance Test Set, Make: Megger, Model: MIT-520/2, S/N: Defaced
TESTED BY : WITNESSED BY :
COMPANY : COMPANY :
DESIGNATION : DESIGNATION :
SIGNATURE : SIGNATURE :