Model SF
a
Copyright and trademarks
All the information and drawings in this manual are the property of Biddle and may not be used (other than for the
actual operation of the device), photocopied, duplicated, translated and/or be brought to the attention of third
parties without Biddle’s prior written permission.
Biddle excludes liability for consequential loss at all times and under all circumstances.
Should you detect any errors or ambiguities in this guide then we would be pleased to hear from you: it helps us to
improve our documentation even further.
Biddle retains the right to change the specifications stated in this guide.
Biddle bv
P.O. Box 15
NL-9288 ZG Kootstertille
The Netherlands
e-mail: export@biddle.nl
internet: www.biddle.info
2
MANUAL
. . . Table of contents
1 Introduction 5
1.1 About this manual 5
1.1.1 General 5
1.2 How to use this manual 5
1.2.1 References in the manual 5
1.2.2 Symbols used on the unit and in the manual 6
1.2.3 Related documentation 6
1.3 About the unit 6
1.3.1 Applications 6
1.3.2 Working 7
1.3.3 Models and type references 7
1.3.4 Type plate 8
1.3.5 Components and accessories 8
1.4 Safety instructions 9
1.4.1 Operation 9
1.4.2 Installation, maintenance and service 9
2 Installation 10
2.1 Safety instructions 10
2.2 Delivery check 10
2.3 General working method 10
2.4 Mounting the unit 11
2.4.1 Positioning the unit 11
2.4.2 Suspending and securing the unit 12
2.5 Connecting the unit to the central heating system 13
2.5.1 Particulars 13
2.5.2 Units without water-side control 13
2.5.3 Units with water-side control 13
2.6 Connecting the unit to the power supply 15
2.6.1 Connecting water-heated models 15
2.6.2 Connecting electrically-heated models 15
2.7 Setting a unit as master (SFi , optional) 17
2.7.1 Working 17
2.7.2 Setting the unit 17
2.8 Connecting external controls (SFi , optional) 18
2.8.1 Input for external control 18
2.8.2 Output for fault signal indication 18
2.9 Installing the controller 19
2.9.1 Mounting and connecting the touchpad controller (SFi ) 19
2.9.2 Mounting and connecting the three-speed switch (SFs ) 20
2.10 Integrating the unit 21
2.10.1 Mounting the telescopic discharge grille 21
2.10.2 Mounting the integrated intake grille (option) 21
2.11 Applying the edge finishing 22
2.12 Switching On and checking operation 22
3 Operation 23
3.1 Three-speed switch (SFs ) 23
3.1.1 Setting the air curtain strength 23
3.2 Touchpad controller (SFi ) 23
3.2.1 Switching the air curtain On and Off 24
3.2.2 Setting the air curtain strength 24
3.2.3 Enabling or disabling heating 24
3.2.4 Enabling or disabling Automatic restart 25
4 Maintenance 26
4.1 Cleaning the unit 26
4.2 Scheduled maintenance 26
5 Faults 27
5.1 Safety instructions 27
5.2 Fault-finding by the user 27
5.3 Fault-finding by the installer 27
6 Service 32
6.1 Safety instructions 32
6.2 Access to the interior of the unit 32
6.3 PCB (SFi ) 33
6.3.1 Introduction 33
6.3.2 Removing the PCB (SFi W) 33
6.3.3 Removing the PCB (SFi E) 33
6.3.4 DIP switches on the PCB 34
6.4 Fuses (SFi ) 34
6.5 Resetting the high-limit thermostat (SFi E) 34
6.6 Composition of Biddle control cable 35
Declaration of conformity 36
4
MANUAL INTRODUCTION
1 . . Introduction
1.1 About this manual
1.1.1 General
So, read this manual carefully before starting to handle the unit
in any way.
If you are familiar with the device, you may use this manual as
a reference. Refer to the table of contents for looking up
information.
n Note:
Draws your attention to an important part of the text.
Read this part of the text carefully.
c Caution:
If you do not perform this procedure or action correctly,
you may damage the device.
Follow the instructions carefully.
w Warning:
If you do not perform this procedure or action cor-
rectly, you may cause damage and/or bodily injury.
Follow the instructions strictly.
d Danger:
This indicates actions which are not permitted.
Ignoring this warning may lead to serious damage
or accidents which may involve bodily injury.
The action may be carried out only by qualified
staff performing maintenance or repair works.
ICON DESCRIPTION
Warning: You are entering an area which contains ‘live’ components.
Warning: This surface or part can be hot. There is a risk of burns on con-
ç tact.
6
MANUAL INTRODUCTION
1.3.2 Working
The air curtain is designed such that there is no need for air
filters.
Biddle bv
Markowei 4
Code U 230 V 1N~ 50 Hz The type plate can be found on the top of the unit.
NL-9288 HA Kootstertille Nº 123456/1-1 04-53 Imax L1 6.18 A
Imax L2 -
M 66 kg Imax L3 - This manual refers to the following data on the type plate:
Medium LPHW Pmotor 1.42 kW
pmax 1400 kPa Pheating -
• Type: full type code of the unit.
• M: weight of the unit.
• pmax: maximum permissible operating pressure in the hot
water circuit (at 110 ºC).
• U, Imax, Pmotor and Pheating: maximum load on the electrical
system by the unit.
Components
Accessories
8
MANUAL INTRODUCTION
1.4.1 Operation
w Warning:
It is not allowed to install air filters in the air cur-
tain.
w Warning:
Do not put any objects in the in- and outlets.
w Warning:
Do not block the in- and outlets.
çw
Warning:
The upper surface of the unit becomes hot during
operation.
d Danger:
The unit may be opened by qualified technical staff
only.
w Warning:
Perform the following actions before opening the
unit:
The heat exchanger or, as the case may be, the heating ele-
ments can get very hot. Moreover, the fans may keep on
ç rotating for a while.
w Warning:
The fins of the heat exchanger are sharp.
2. . Installation
d Danger:
Installation works on the unit may be performed by
qualified technical staff only.
w Warning:
Before opening the unit, follow the safety instruc-
tions in section 1.4.
Working method
10
MANUAL INSTALLATION
General instructions
n Note:
Make sure you perform all installation operations that are
required for your unit.
n Note:
Protect the unit from damage and ingress of dust, cement,
etc. throughout the installation. You can, for instance, use
the packaging for protection.
w Warning:
The minimum mounting height (dimension h) is
1.8 m.
w Warning:
The top of the unit may get hot. Mount the unit at
ç a minimum of 25 mm from the ceiling (dimension x
on page 11).
n Note:
Mounting the unit at a height exceeding the maximum
height may affect the proper working of the unit.
b c d
12
MANUAL INSTALLATION
2.5.1 Particulars
1
1
c Caution:
The supply and return pipes of the central heating system
must be connected to the appropriate corresponding
connections 1 (G1"). The directions are indicated on the
unit using arrows.
c Caution:
When connecting the pipes, hold the connections 1 in
place using pliers.
c Caution:
Biddle recommends the inclusion of a valve and a relief
valve in both pipes, near the unit.
14
MANUAL INSTALLATION
1
3
3
n Note:
Biddle recommends a discharge temperature of 35°C.
c Caution:
Do NOT yet switch the mains supply on.
w Warning:
The unit must be earthed.
d Danger:
Do not perform the connection work unless you
are qualified to work with three-phase current.
Particulars
1 2 3 N
• An isolation switch (not supplied) must be fitted between
the unit and the power supply. This switch must:
contact clearance - be all-pole;
- have a minimum contact clearance of 3 mm;
- be positioned within 4 m from the right side of the unit.
R S T N w Warning:
The unit must NOT be switchable using the power
supply cable – use the touchpad controller for that.
w Warning:
The unit must be earthed.
w Warning:
Connect the unit in accordance with the applicable
local requirements.
w Warning:
Make sure that the power supply you are working
on is switched off.
5. Put back and screw down the inspection panel and grille.
2
c Caution:
Do NOT yet switch the mains supply on.
16
MANUAL INSTALLATION
2.7.1 Working
You may choose to set one unit as master. By this, the work-
ing of the units will be linked:
3. Set DIP switch no. 3 on the PCB into the ’ON’ position.
w Warning:
NEVER change the settings of the other DIP
switches.
n Note:
Do NOT remove the bridges from the other units.
18
MANUAL INSTALLATION
n Note:
Take the following into account, otherwise faults may
occur:
2. Hook the control panel on the screws using the key holes.
SFi
Multiple units operated from one control panel
1 2 12
• Only SFi -type units can be simultaneously operated using
one single control panel.
• Up to 100 units can be connected to one single control
panel. The units must be interlinked using special control
cable from Biddle.
• The total length of the control cables is not to exceed
100m.
• If a unit has been set as master: the control panel may be
connected to any unit.
touchpad controller
n Note:
Use only control cables from Biddle. Standard modular
telephone cable is not suitable.
1 2 1 2
1. Interlink the units: Connect the control cable of the unit to
SFi SFi
which the controller is linked to socket 2, and that of the
next unit to socket 1.
1
4. Make a hole in the switch casing 6 and lead the feeder
cable through it. Mount the switch casing to the wall or
install a standard power socket.
c Caution:
Make sure that the switch indicates the correct speed on
the cover.
w Warning:
Never connect more than one unit to a three-speed
switch.
20
MANUAL INSTALLATION
c Caution:
For the unit to work properly, the cove or ceiling must
have enough openings through which the unit can take air
in.
- power supply;
- control cable(s) between controller and unit(s);
- external control components (if used).
2. Only SF W:
22
MANUAL OPERATION
3 . . Operation
This section describes the functions you should know for the
day-to-day use of the comfort air curtain.
Upon switching off the unit, the heat and air-flow settings are
1 3 5 retained. If heating is enabled, the unit will keep on running at
low speed for another minute.
Depending on the type of the unit, the heating of the air cur-
tain can be controlled automatically and manually. This only
applies for the types SFi E and for the types SFi W with corre-
sponding water-side control.
n Note:
With the types SFi W without water-side control or with
fixed discharge temperature and with the types SFi A,
heating is indicated on the controller but has no function.
24
MANUAL OPERATION
When the supply power is interrupted, you can have the unit
operate in either of the following ways:
4. . Maintenance
c Caution:
Make sure no water runs into the unit.
c Caution:
The fins of the heat exchanger are delicate parts.
w Warning:
The fins of the heat exchanger are sharp.
26
MANUAL FAULTS
5 . . Faults
5.1 Safety instructions
d Danger:
Work on the unit’s interior shall be performed by
qualified technical staff only.
w Warning:
Before opening the unit, follow the safety instruc-
tions in section 1.4.
c Caution:
First run through table 5-1 before considering the actions
in table 5-2.
d Danger:
The actions in table 5-2 may be performed by quali-
fied staff only
28
MANUAL FAULTS
30
MANUAL FAULTS
6. . Service
d Danger:
Service work on the unit may be performed by
qualified technical staff only.
w Warning:
Before opening the unit, follow the safety instruc-
tions in section 1.4.
w Warning:
Disconnect the power supply (pull plug from socket
or move isolation switch to Off).
2
2. Detach the inlet grille from the unit:
çw
Warning:
The heat exchanger or heating elements may be
hot.
c Caution:
The whole panel will come loose when you pull it for-
ward: take care it does not fall down.
4
32
MANUAL SERVICE
6.3.1 Introduction
The SFi E and the SFi W house the PCB at different locations.
n Note:
The PCB in your unit may look different from the PCB
illustrated opposite.
1
6.3.2 Removing the PCB (SFi W)
1
1. Switch the unit Off using the controller.
w Warning:
Disconnect the power supply (pull plug from socket
or move isolation switch to Off).
2
6.3.3 Removing the PCB (SFi E)
w Warning:
Disconnect the power supply (pull plug from socket
or move isolation switch to Off).
w Warning:
NEVER change the settings of the DIP switches,
unless instructed otherwise.
c Caution:
If you replace the PCB: set the DIP switches on the new PCB
in the same positions as the old PCB.
34
MANUAL SERVICE
The connectors are of the RJ-11 type but the connections are
‘straight’ at both ends of the cable, the core is connected to
the same pin.
PIN COLOUR
123456 1 (not used)
2 black
3 red
4 green
5 yellow
6 (not used)
Manufacturer: Biddle BV
Address: Markowei 4
9288 HA Kootstertille
THE NETHERLANDS
- EN 61000-6-2
- EN 50081-2
- EN 60335-2-30
I hereby declare that the equipment named above has been designed to comply with the relevant
sections of the above referenced specifications. The unit complies with all essentials requirements of
the directives.
ce declaration sf.doc