Illuminated Area: 6600 Sq.Ft Desired Footcandles: 40 No of Lamps per Fixture: 2 Nos Each Fixture Watts: 56 Watt Ballast Factor: 0.88 Rated mean Lumens per Lamp: 2650 Coefficient of Utilization: 0.6 Fixtures Burning hours per Year: 3200 Energy Rate (Rs.Per Kwh): रु 0.10
:Results:
Required Fixtures 95 Nos
Required Lamps 190 Nos Required Fixture Spacing 8.3 Feet Total Kw 5.3 Kw Watts per Sq.Ft 0.81 Energy Cost per Year रु 1,702.40 Jignesh.Parmar www.electricalnotes.wordpress.com
Calculate No of Fixtures / Lux for Indoor Lighting
Required Lux: (E) 200 Room Index Length:(L) 10 Meter Width: (w) 3 Meter Height: (h) 3 Meter Working Level: 0 Meter Fixture hanging Level : 0 Meter Actual Height: (Hm) 3 Meter Reflection Factors: Ceiling Reflection Factor: 0.7 Wall Reflection Factor: 0.5 Floor Reflection Factor: 0.2 Type of Luminaire / Fixtures: Type of Fixture: Type of Lamp: No of Lamps per Fixture: (n) 1 Nos Lamp Watt: 5 Watt Lamp Flux: 300 Lumen Room Index: (K) 0.944 Utilization Factor: (Uf) 0.48 Maintenance Factor: (Mf) 0.6 :Results: Required No of Fixtures: 69 Nos Required No of Fixtures along Length: 15 Nos Required No of Fixtures across Length: 5 Nos Actual No of Fixtures along Length: 15 Nos Actual No of Fixtures across Length: 5 Nos