DC12-100(12V100Ah)

Specification
Cells Per Unit 6
Voltage Per Unit 12
Capacity 100Ah@20hr-rate to 1.75V per cell @25℃
Weight Approx. 30.0 Kg (Tolerance±2%)
Internal Resistance Approx. 5 mΩ
Terminal F12(M8)/F5(M8)
Max. Discharge Current 1000A (5 sec)
DC (Deep Cycle) series batteries provide
Design Life 12 years (floating charge)
superior high integrity and reliability.It is
Maximum Charging Current 30.0 A specially designed for frequent cyclic charge
and discharge.By using strong grids,thick
C3 74.4AH
plate and specially active material are designed
C5 83.5AH
Reference Capacity for repeated deep-discharge applications.
C10 95.0AH
The DC series batteries offer 30% more cyclic
C20 100.0AH
life than the standby series.It is suitable for
13.6 V~13.8 V @ 25℃
Float Charging Voltage solar and wind renewable nergy storage,mobility
Temperature Compensation: -3mV/℃/Cell
and medical equipment,V,telecom,broadband
14.6 V~14.8 V @ 25℃ and cable TV,UPS systems etc.
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: 0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
ISO 9001 ISO 14001 OHSAS 18001
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charged batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional. MH 28539 G4M20206-0910-E-16

Dimensions
328 172
Φ16 Length 328±2mm (12.9 inches)
M8
Width 172±2mm (6.77 inches)
Height 215±2mm (8.46 inches)
5

Total Height 220±2mm (8.66 inches)


Terminal Value
220
215

39.5

M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
265
F12 Terminal Unit: mm

Constant Current Discharge Characteristics : A(25 ℃)

F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 225.4 173.7 100.7 59.3 35.5 26.5 20.9 17.6 12.0 10.2 5.20
1.65V 217.9 168.5 98.6 58.2 34.9 26.1 20.6 17.4 11.9 10.1 5.15
1.70V 208.1 161.7 95.8 56.7 34.1 25.5 20.3 17.1 11.7 10.0 5.09
1.75V 195.0 152.5 92.0 54.6 33.0 24.8 19.7 16.7 11.5 9.77 5.00
1.80V 177.4 140.2 86.8 51.9 31.5 23.8 19.0 16.2 11.1 9.50 4.88
1.85V 153.5 123.1 79.4 47.9 29.3 22.3 17.9 15.4 10.6 9.12 4.70

Constant Power Discharge Characteristics : WPC(25℃)

F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 403 320 193 117 70.8 53.2 42.3 35.8 24.7 21.1 10.8
1.65V 400 317 191 116 70.1 52.7 41.9 35.5 24.5 20.9 10.7
1.70V 386 306 187 113 68.7 51.7 41.2 35.0 24.2 20.7 10.6
1.75V 369 293 181 110 66.8 50.5 40.3 34.3 23.7 20.3 10.4
1.80V 341 273 173 105 64.1 48.6 39.0 33.3 23.1 19.8 10.2
1.85V 300 244 160 97.2 60.0 45.8 36.9 31.7 22.1 19.0 9.80
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
DC12-100(12V100Ah)
Discharge Characteristics Curve Charge Characteristic Curve for Cycle Use(IU)
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.60
Charge Volume
2.16

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 2.50

Charge Volume (%)


Charge Voltage
2.00

80 0.10 2.40
1.84
0.1C 0.05C
0.4C 0.2C 60 0.06 2.30
1.68 After 50% Discharge
0.55C
After 100% Discharge
3C 2C1C 40 0.04 2.20
1.52

1.36 20 0.02 2.10


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 2.00
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.70

100
2.60

Charge Voltage (v )
Cycle use
80
2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 50% 30%
DOD DOD DOD 2.40

40

2.30
20 Float charging
2.27~2.30VPC@25℃
2.20
0 -20 -10 0 10 20 30 40 50
300 600 900 1200 1500 1800 2100
Number of Cycles Temperature (℃)

Temperature Effects on Capacity Storage Characteristics


120 100

100 0℃
A
0 .0 5 C 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
3 .0 C A 20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
20 2.20

2.15
Battery Voltage (V)
Lift Expectancy (y ears)

16
2.10

2.05
12

2.00

8
1.95

1.90
4
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

SHENZHEN RITAR POWER CO.,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, No.81, Xuefu Road, Nanshan District, Shenzhen,
Guangdong, China 518057
URL: www.ritarpower.com Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: sales@ritarpower.com Version 17B-0
YINGDE AOKLY POWER CO., LTD 
6GFM100G (12V/100Ah) 

GENERAL FEATURES 

● Longer cycle life: special paste formula, over dimensioned nega ve plate,
op mized manufacturing process, addi ves for deep discharge.
● Special separators boost up the ba ery internal performance.
● Using oxygen recombina on technology, maintenance-free and li le water losing.
● ABS material: enhanced strength of the ba ery container. (Flame-retardant ABS is
op onal).
● Designed to have a lifespan of 15 years for float charging at 25°C

APPLICATIONS 

● Electric tools ● Electric toys
● Vehicle in place of walking ● Railway and marine systems
● Lawn mowers ● Fire alarms
● Golf trolleys and golf cart ● Solar and wind power system
● Power system of special network or ● Electric wheelchairs
local area network ● Medical equipment

SPECIFICATIONS 

Nominal Vol tage  12V


Model Rated Capacity
100Ah
(10Hr rate)
Length Width Hei ght Total  Hei ght
Dimensions
329mm  172mm  214mm 243mm 
Weight Approx. 31.3kgs (+/-3%)
 10 Hour (10A,10.8V)  5 Hour (17A,10.8V)  3 Hour (25A,10.5V)  1 Hour (55A,9.6V)
Capacity @25℃ (77℉)
100Ah  85Ah 75Ah 55Ah
Internal Resistance Fully charged at 25℃, approx. 4.2mΩ
Max. Discharge current 1000A (5 Sec.)
Capacity Affected by Temp. 40℃ (104℉) 25℃ (77℉) 0℃ (32℉) -15℃ (5℉)
(20Hr) 112% 100% 80% 68%
Self Discharge Rate After 3 months  Storage After 6 months  Storage After 12 months  Storage
@25℃ (77℉) 91% 82% 64%
Cycle Us e Fl oat Charging
Charge Method 14.1-14.4V (Initial current less than 30A)
13.5-13.8V@25℃(77℉)
@25℃(77℉)

DIMENSIONS & TERMINALS 

P1/2
YINGDE AOKLY POWER CO., LTD 
6GFM100G (12V/100Ah) 

PERFORMANCE CHARACTERISTICS 

DISCHARGE CHARACTERISTICS  CHARIGING CHARACTERISTICS (STANDBY) 

TEMP. EFFECTS IN RELATION TO BATTERY CAPACITY  EFFECT OF TEMP. ON LONG TERM FLOAT DESIGNED LIFE 

SELF DISCHARGE CHARACTERISTICS  CYCLE LIFE IN RELATION TO THE DEPTH OF DISCHARGE 

A. No supplementary charge required. (Carry out supplementary charge before use if 100% capacity is required.)
B. Supplementary charge required before use. Optional charging way as below:
1. Charged for above 3 days at limited current 0.25CA and constant voltage 2.25V/cell.
2. Charged for above 20hours at limited current 0.25CA and constant voltage 2.45V/cell.
3. Charged for 8~10hours at limited current 0.05CA .
C. Supplementary charge may often fail to recover the capacity. The battery should never be left standing till this
is reached.

P2/2
RT1270(12V7Ah)
Specification
Cells Per Unit 6
Voltage Per Unit 12
Nominal Capacity 7Ah@20hour-rate to 1.75V per cell @25℃
Weight Approx. 2.04 Kg (Tolerance±4.0%)
Internal Resistance Approx. 30 mΩ
Terminal F1/F2
Max. Discharge Current 70A (5 sec)
Short Circuit Current 350A RT series is a general purpose battery with
6~8 years design life in float service. It meets
Design Life 6~8 years (Float charging)
with IEC, JIS, BS and YDT standards. With
Recommended Maximum Charging 2.1 A advanced AGM valve regulated technology
Current and high purity raw material, the RT series
C3 5.43AH battery maintains high consistency for better
C5 6.13AH performance and reliable standby service
Reference Capacity C10 6.58AH life. It is suitable for UPS/EPS, Telecom,
C20 7.04AH power grid, medical equipment, emergency
Standby Use Voltage
13.7 V~13.9 V @ 25℃ light and security system applications.
Temperature Compensation: -3mV/℃/Cell
14.6 V~14.8 V @ 25℃
Cycle Use Voltage
Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: 0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charge batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional.

Dimensions
151 65 Length 151±1.5mm (5.94 inches)
6.35
66 Width 65±1.5mm (2.56 inches)
Height 94±1.5mm (3.70 inches)
3.4
7.8

Total Height 100±1.5mm (3.94 inches)


Terminal Value
100
94

6~7 N*m
43

0.8 M5
M6 8~10 N*m
M8 10~12 N*m
F2 Terminal
Unit: mm

Constant Current Discharge Characteristics : A (25℃)


F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 27.75 18.10 13.35 7.728 4.465 2.634 1.915 1.525 1.287 0.860 0.701 0.364
1.65V 26.75 17.56 13.00 7.558 4.382 2.596 1.890 1.506 1.273 0.852 0.694 0.362
1.70V 25.45 16.85 12.54 7.334 4.273 2.545 1.856 1.481 1.253 0.840 0.685 0.358
1.75V 23.77 15.94 11.94 7.040 4.129 2.477 1.811 1.447 1.226 0.825 0.673 0.352
1.80V 21.66 14.77 11.17 6.659 3.941 2.388 1.752 1.403 1.192 0.804 0.658 0.346
1.85V 19.06 13.30 10.20 6.173 3.698 2.272 1.674 1.345 1.146 0.777 0.637 0.336
Constant Power Discharge Characteristics : WPC (25℃)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 47.77 31.23 23.69 14.25 8.47 5.07 3.71 2.97 2.52 1.71 1.40 0.73
1.65V 47.27 31.10 23.56 14.14 8.40 5.03 3.69 2.95 2.50 1.69 1.39 0.72
1.70V 45.46 30.18 22.92 13.80 8.22 4.95 3.63 2.91 2.47 1.67 1.37 0.72
1.75V 43.24 29.06 22.15 13.38 7.99 4.84 3.56 2.85 2.43 1.64 1.35 0.71
1.80V 40.08 27.39 21.01 12.79 7.66 4.69 3.45 2.78 2.36 1.61 1.32 0.69
1.85V 35.90 25.12 19.45 11.97 7.24 4.48 3.32 2.67 2.28 1.56 1.28 0.68
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
RT1270(12V7Ah)
Discharge Characteristics Curve Charge Characteristic Curve For Standby Use
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.40
2.16 Charge Volume

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 Charge Voltage 2.30

Charge Volume (%)


2.00

80 0.10 2.20
1.84
0.1C 0.05C
1.68
0.25C 0.17C 60 0.06 2.10
0.55C After 50% Discharge
3C 2C 1C After 100% Discharge
1.52 40 0.04 2.00

1.36 20 0.02 1.90


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.80
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature
2.70
120

100 2.60

Charge Voltage (v )
Cycle use
80 2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 50% 30%
DOD DOD DOD 2.40
40

2.30
20
Float charging
2.28~2.32VPC@25℃
0 2.20
200 400 600 800 1000 1200 1400
-20 -10 0 10 20 30 40 50

Number of Cycles Temperature (℃)

Temperature Effects On Capacity Storage Characteristics


120 100

100 0℃
A
0 .0 5 C 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
3 .0 C A 20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect Of Temperature On Long Term Life Life Characteristics Of Standby Use


Testing conditions: float charging Temperature: 25℃(77℉)
10
120
Lift Expectancy (y ears)

8 100

80
6
Capacity(%)

60
4
40

2
20

0 0
0 10 20 30 40 50 0 1.5 3.0 4.5 6.0 7.5 9.0
Temperature(℃) Life expectancy (years)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

SHENZHEN RITAR POWER CO.,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, No.81, Xuefu Road, Nanshan District, Shenzhen,
Guangdong, China 518057
URL: www.ritarpower.com Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: sales@ritarpower.com Version 17A-0