C250D5 Parameters Adjustment

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Genset Primary CT Current 975

Prime kVA rating (3 phase/ 50Hz) 228


Prime kVA rating (3 phase/ 60Hz) 281
Standby kVA rating (3 phase/ 50Hz) 250
Standby kVA rating (3 phase/ 60Hz) 313
Magnetic Pickup Enable Enable
Teeth Pulses Per Revolution 138
Excitation Source Shunt
Single/3 Phase Connection Three Phase
Genset Nominal Voltage 400
Genset Delta/Wye Connection Wye
Application Rating Select Standby
Alternate Frequency Switch 50 Hz
AVR Enable Enable
Electronic Governor Enable Enable
Fault Input #3 Fault Select Trim Shutdown
Configurable Input #3 Function Fault Input
Oil Pressure Sensor Type Sender
Oil Pressure Sender Type 2-Wire
Frequency to Speed Gain Select #1
Max Over Excitation Duty Cycle 56
LOP Shutdown Threshold 173
LOP Warning Threshold 193
HCT Shutdown Threshold 104
HCT Warning Threshold 100
Low Oil Pressure Idle Shutdown Threshold 83
Low Oil Pressure Idle warning Threshold 103
LOP shutdown Delay 10
LOP warning Delay 10
ECM Fault Code 1117 Enabled Disable
Nominal Battery Voltage 24V
Initial Crank Fueling Command 50
Initial Crank Fueling Period 2
Crank Fueling Ramp Rate 25
Maximum Crank Fueling 100
Crank Exit Fueling Command 50
Governor Enable Speed 1300
Governor Preload Offset 200
Governor Ramp Time 3
Dither Factor 15
Maximum Governor Duty Cycle 95
Minimum Governor Duty Cycle 10
Starter Disconnect Speed 450
Charging Alternator Functions Disable Enable
24V Charging Alternator Voltage for Starter
26
Disconnect
Governor Gain Adjust 100
Gov K2 Gain Adjust 100
Gov K3 Gain Adjust 100
Gov D Gain Adjust 100
GK1 (50Hz) 1300
GK2 (50Hz) 300
GK3 (50Hz) 28800
Governor Damping Effect (50Hz) 0.85
V/Hz Knee Frequency 1
V/Hz Rolloff Slop 5
Overspeed Shutdown Threshold 50Hz 1875