AUX POWER CONSUMPTION BASED ON INPUTS FURNISHED BY SEC/SWEPDI VIDE MAIL DATED 22.4.

05
S.NO. PARAMETERS UNIT PA FAN FD FAN ID FAN BFP CEP
1 Volumetric flow m3/sec 60.4 93.8 227 590 410
cfm 127980.35 198750.94 480985.76 m3/hr m3/hr
2 Pressure Pa 10269 3203 3374 2052.39 292.56
inch wc 41.24 12.86 13.55 mwc (20.134MPamwc (2.87MPa)
3 Efficiency (calculated) - 0.6880 0.7893 0.7802 0.8 0.8
% 68.80 78.93 78.02 80 80
4 Shaft power KW 900 380 980 4124.35 408.55
bhp 1206.92 509.59 1314.20
5 No of operating fans/pumps for - 4 4 4 4 4
both units
6 Total Shaft Power for all working KW 3600 1520 3920 16497.41 1634.19
fans
Aux power consumption (present) KW
7 4000.00 1688.89 4355.56 18330.46 1815.77
with motor efficiency of 0.9
8 SEC proposal aux power KW 3800 3000 7200 16800 1500
9 REL committed aux power KW 5200 2400 6400 16000 1400
10 Motor rating KW 1800 800 2240 5300 630

NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 7 comes out to 37.707 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.
PANIPAT FANS DATA 100% TMCR

Sl. No. Description Unit PA Fan FD Fan ID Fan


1 Voumetric flow m3/sec 44.8 81.8
2 Pressure Pa 7514.46 3129.39
3 Fan efficiency % 80.6 87.3
4 Power consumption KW 407 290
5 Motor rating (recommend KW 1500 775
6 Motor rating (selected) KW 1550 790
7 Fan speed RPM 1490 1490
AUX POWER CONSUMPTION BASED ON INPUTS FURNISHED BY SEC/SWEPDI VIDE MAIL DATED 22.4.05 (100% TMCR)
S.NO. PARAMETERS UNIT PA FAN FD FAN ID FAN BFP CEP
1 Air volumetric flow m3/sec 60.4 93.8 227 0.16388 0.11388
2 Pressure Pa 10269 3203 3374 20134000 2870000
3 Efficiency (Assumed) % 80 80
4 Efficiency (calculated) % 68.92 79.06 78.15
5 Shaft power KW 900 380 980
6 Shaft power (calculated) KW 4124.45 408.54
7 No of operating fans/pumps for both No. 4 4 4 4 4
units
8 Total Shaft Power for all working fans KW 3600 1520 3920 16497.80 1634.18
Aux power consumption (present) KW
9 4000.00 1688.89 4355.56 18330.89 1815.75
with motor efficiency of 90%
10 (Assumed)
SEC proposal aux power KW 3800 3000 7200 16800 1500
11 REL committed aux power KW 5200 2400 6400 16000 1400
12 Motor rating KW 1800 800 2240 5300 630

NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 7 comes out to 37.567 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.

Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of fan * 1000

Motor Input (KW) = Shaft power (KW) / Eff of motor


AUX POWER CONSUMPTION BASED ON INPUTS FURNISHED BY SEC/SWEPDI VIDE MOM & MAIL DATED 01.07.05 (100% TMCR)
S.NO. PARAMETERS UNIT PA FAN FD FAN ID FAN BFP Booster pump CEP
1 Volumetric flow m3/sec 57.3 88 227 0.16388 0.16388 0.11388
2 Pressure Pa 10050 3179 3221 19108421 1025579 2880000
3 Efficiency (Assumed) % 82.48 80.31 80
4 Efficiency (calculated) % 58.49 85.29 85.02
5 Shaft power KW 984.5 328 860
6 Shaft power (calculated) KW 3796.66 209.28 409.97
7 No of operating fans/pumps for both No. 4 4 4 4 4 4
units
8 Total Shaft Power for all working fans KW 3938 1312 3440 15186.65 837.12 1639.87
Aux power consumption (present)
9 with motor efficiency of 90% KW 4375.56 1457.78 3822.22 17804.19 1822.08
(Assumed)
10 SEC proposal aux power KW 3800 3000 7200 16800 1500
11 REL committed aux power KW 5200 2400 6400 16000 1400
12 Motor rating KW 1800 800 2240 5600 630

NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 9 comes out to 36.658 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.

Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000

Motor Input (KW) = Shaft power (KW) / Eff of motor


AUX POWER CONSUMPTION BASED ON INPUTS FURNISHED BY SEC/SWEPDI VIDE MOM & MAIL D
S.NO. PARAMETERS UNIT PA FAN FD FAN
1 Volumetric flow m3/sec 61.4 83.4
2 Pressure Pa 10745 3133
3 Fan / Pump Efficiency % 52.80 86.14
4 Shaft power KW 1250.4 306
5 No of operating fans/pumps for both No. 4 4
units
6 Total Shaft Power for all working fans KW 5001.6 1224
7 Motor Efficiency % 95.6 91.9
8 Aux power consumption (present) KW 5232 1332
9 SEC proposal aux power KW 3800 3000
10 REL committed aux power KW 5200 2400
11 Motor rating KW 2500 800

NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 8 comes out to
40.118 MW (excluding ESP hopper heater 336 KW).
2 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is
3 Other aux. power consumption (SEC's Latest Data) : SA fan (221 KW) + AH (49 KW) + Mills* (3304 KW) +
Chemical feed pump (30 KW) + Vacuum pump (220 KW) = 7044 KW
* to be confirmed by SEC.
4 PA / FD / ID fans data : Boiler Sch.B and BFP / CEP data : Sizing data sheets (Rev B)
5 Efficiency of BFP hydraulic coupling = 95%.

Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000

Motor Input (KW) = Shaft power (KW) / Eff of motor


SEC/SWEPDI VIDE MOM & MAIL DATED 01.07.05 (100% TMCR)
ID FAN BFP Booster pump CEP
226 0.16388 0.16388 0.11388
3246.8 19108421 1025579 2880000
89.30 82.48 80.31 80
863.7 3718.92 187.89 481.00
4 4 4 4

3454.8 15658.61 751.56 1924.00


95.1 96.0 92.0
3633 17094 2091 Total: 29382
7200 16800 1500
Misc: 7044
6400 16000 1400
2240 5600 630 Grand Total: 36426

point no 8 comes out to 36.426 MW against SEC proposal of

hich BTG portion considered is 38.322 MW (including ESP hopper heater).


+ AH (49 KW) + Mills* (3304 KW) + ESP (3188 KW) + Coal Feeders* (32 KW) +

sheets (Rev B)

Eff of driven equipment * 1000


AUX POWER CONSUMPTION BASED ON INPUTS FURNISHED BY SEC/SWEPDI VIDE MOM & MAIL DATED 01.07.05 (100% TMCR)
S.NO. PARAMETERS UNIT PA FAN FD FAN ID FAN BFP Booster pump CEP
1 Volumetric flow m3/sec 61.4 83.4 226 0.16388 0.16388 0.11388
2 Pressure Pa 10745 3133 3246.8 19108421 1025579 2880000
3 Fan / Pump Efficiency % 52.80 86.14 89.30 82.48 80.31 80
4 Shaft power KW 1252.3 306 863.5 3718.92 187.89 481.00
5 No of operating fans/pumps for both No. 4 4 4 4 4 4
units
6 Total Shaft Power for all working fans KW 5009.2 1224 3635.79 15658.61 751.56 1924.00
7 Motor Efficiency % 95.4 90.0 94.5 97.0 94.0
8 Aux power consumption (present) KW 5251 1360 3847 16918 2047 Total: 29423
9 SEC proposal aux power KW 3800 3000 7200 16800 1500
Misc: 7098
10 REL committed aux power KW 5200 2400 6400 16000 1400
11 Motor rating KW 2500 800 2240 5600 630 Grand Total: 36521

NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 11 (Grand Total) comes out to 36.521 MW (including ESP hopper heater) against
SEC proposal of 40.118 MW (excluding ESP hopper heater).
2 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW (excluding ESP hopper heater).
3 Other aux. power consumption (SEC's Latest Data) : SA fan (221 KW) + AH (49 KW) + Mills (3304 KW) + ESP (3252 KW) + Coal Feeders (22 KW) +
Chemical feed pump (30 KW) + Vacuum pump (220 KW) = 7098 KW
* to be confirmed by SEC.
4 PA / FD / ID fans data : Boiler Sch.B and BFP / CEP data : Sizing data sheets
5 Efficiency of BFP hydraulic coupling and ID Fan considered = 95%.

Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000

Motor Input (KW) = Shaft power (KW) / Eff of motor