Aux Power - Fans - Pumps - 27.4.05
Aux Power - Fans - Pumps - 27.4.05
05
S.NO. PARAMETERS UNIT PA FAN FD FAN ID FAN BFP CEP
1 Volumetric flow m3/sec 60.4 93.8 227 590 410
cfm 127980.35 198750.94 480985.76 m3/hr m3/hr
2 Pressure Pa 10269 3203 3374 2052.39 292.56
inch wc 41.24 12.86 13.55 mwc (20.134MPamwc (2.87MPa)
3 Efficiency (calculated) - 0.6880 0.7893 0.7802 0.8 0.8
% 68.80 78.93 78.02 80 80
4 Shaft power KW 900 380 980 4124.35 408.55
bhp 1206.92 509.59 1314.20
5 No of operating fans/pumps for - 4 4 4 4 4
both units
6 Total Shaft Power for all working KW 3600 1520 3920 16497.41 1634.19
fans
Aux power consumption (present) KW
7 4000.00 1688.89 4355.56 18330.46 1815.77
with motor efficiency of 0.9
8 SEC proposal aux power KW 3800 3000 7200 16800 1500
9 REL committed aux power KW 5200 2400 6400 16000 1400
10 Motor rating KW 1800 800 2240 5300 630
NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 7 comes out to 37.707 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.
PANIPAT FANS DATA 100% TMCR
NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 7 comes out to 37.567 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.
Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of fan * 1000
NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 9 comes out to 36.658 MW against SEC proposal of
40.118 MW (excluding ESP hopper heater 336 KW). Refer enclosed sheets for details.
2 SEC should be requested to confirm the efficiencies of fans and pumps to match the figures arrived by us.
3 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW.
Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000
NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 8 comes out to
40.118 MW (excluding ESP hopper heater 336 KW).
2 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is
3 Other aux. power consumption (SEC's Latest Data) : SA fan (221 KW) + AH (49 KW) + Mills* (3304 KW) +
Chemical feed pump (30 KW) + Vacuum pump (220 KW) = 7044 KW
* to be confirmed by SEC.
4 PA / FD / ID fans data : Boiler Sch.B and BFP / CEP data : Sizing data sheets (Rev B)
5 Efficiency of BFP hydraulic coupling = 95%.
Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000
sheets (Rev B)
NOTE:
1 Total aux power consumption considering the SEC figures as arrived in point no 11 (Grand Total) comes out to 36.521 MW (including ESP hopper heater) against
SEC proposal of 40.118 MW (excluding ESP hopper heater).
2 Total aux power consumption committed by REL is 50.2 MW, out of which BTG portion considered is 38.322 MW (excluding ESP hopper heater).
3 Other aux. power consumption (SEC's Latest Data) : SA fan (221 KW) + AH (49 KW) + Mills (3304 KW) + ESP (3252 KW) + Coal Feeders (22 KW) +
Chemical feed pump (30 KW) + Vacuum pump (220 KW) = 7098 KW
* to be confirmed by SEC.
4 PA / FD / ID fans data : Boiler Sch.B and BFP / CEP data : Sizing data sheets
5 Efficiency of BFP hydraulic coupling and ID Fan considered = 95%.
Shaft power (KW) = Flow (m3/sec) * Pressure (Pa) / Eff of driven equipment * 1000
02/10/2021