Professional Documents
Culture Documents
Theory and Practice of Aeration in Wastewater Treatment
Theory and Practice of Aeration in Wastewater Treatment
1.
Introduction 167
2.
Steps Involved in the Oxygen-Transfer Process 170
3.
Oxygen-Transfer Rate Equation 170
4.
Determination of the Overall Oxygen-Transfer Coefficient Κγ^α by
Unsteady-State Aeration of Tap Water 172
5. Integration of the Differential Equation for Oxygen Transfer between
Limits 176
6. Unsteady-State Aeration of Activated Sludge Liquor 177
7. Steady-State Determination of Κγ^α for the Activated Sludge Liquor 178
8. Standard Oxygenation Capacity and Oxygenation Capacity under Actual
Operating Conditions 178
9. Transfer Efficiency of Aeration Units 183
10. Effect of Wastewater Characteristics on Oxygen Transfer 184
11. Laboratory Determination of Oxygen-Transfer Coefficient α 186
12. Classification of Aeration Equipment; Oxygen-Transfer Efficiency 187
13. Air Diffusion Units 187
14. Turbine Aeration Units 194
15. Surface Aeration Units 199
Problems 205
References 210
1. INTRODUCTION
This chapter is concerned with the transfer of oxygen from air to a wastewater
subjected to biological aerobic treatment. Knowledge of the rate of oxygen
transfer is essential for specification of aerators to be utilized in the process. The
subject matter in this chapter includes: (1) A brief review of the stationary film
theory applied to the case of oxygen transfer; (2) experimental procedures for
determination of oxygen transfer coefficients from bench-scale units; (3) a
discussion of the most c o m m o n types of aerators utilized in wastewater
treatment; and (4) procedures for specifying aerators for a given application and
arriving at a reasonable aerator layout for the treatment unit.
The simplest explanation for the mechanism of gas transfer is given by the
two-film theory. According to this theory, it is the presence of two films, one
liquid and one gas, at the gas-liquid interface which provides most of the
167
168 4. Theory and Practice of Aeration in Wastewater Treatment
resistance to the passage of gas molecules from the bulk of the gas phase to that
of the hquid phase.
F o r gases of high solubility in the hquid phase, e.g., absorption of SO2 by
water, the major resistance to absorption is that offered by the gas film. F o r
gases of low solubility in the hquid phase, e.g., absorption of oxygen by an
aqueous liquor, which is the case under study in this chapter, the controlling
resistance resides in the liquid film. For gases of intermediate solubilities, both
films may offer significant resistance.
Oxygen saturation values (Cs)76o for distilled water at standard atmospheric
pressure (760 m m Hg) are presented in Table 4.1 as function of temperature. For
a more complete table with 1 °C increments, which also takes into account the
presence of chlorides, consult Ref. [ 9 ] .
TABLE 4.1
Temperature Temperature O2
CQ CF) (mg/liter)
0 32.0 14.6
5 41.0 12.8
10 50.0 11.3
15 59.0 10.2
20 68.0 9.2
25 77.0 8.4
30 86.0 7.6
35 95.0 7.1
40 104.0 6.6
From Ref. [ 9 ] .
ß = Q J Q (4.1)
(4.3)
(Cs) 7 6 0 760 - P'
where Ρ is the barometric pressure (mm Hg) and P" is the vapor pressure of water
at the water temperature. Values of P^ are presented in Table 4.2.
TABLE 4.2
pv
Temperature Temperature
(X) (°F) (mm Hg)
0 32.0 4.579
5 41.0 6.543
10 50.0 9.209
15 59.0 12.788
20 68.0 17.535
25 77.0 23.756
30 86.0 31.824
35 95.0 42.175
40 104.0 55.324
* The error in neglecting the term in the numerator and denominator of Eq. (4.3) [or (4.4)] is
small, and thus these equations are frequently written as
= (C,)76o(P/760) (4.3a)
and
• ßiCsheoiPPeO) (4.4a)
1 70 4. Theory and Practice of Aeration in Wastewater Treatment
For a wastewater, from Eqs. (4.1) and (4.3) (see footnote on p. 169),
Equations (4.3) or (4.4) are only applicable at the water surface and are
utilized without further corrections for the case of surface aeration. F o r the case
of bubble aerators (e.g., diffusers and turbine aerators to be studied in Sections
13 and 14), it is necessary to introduce another pressure correction to account for
the hydrostatic head of liquid above the point of aeration. This matter is
discussed in Section 8.3.
Step L Saturation of the hquid interface between the two phases. Let Q (or
Csw) be the saturation concentration of oxygen for the cases when the hquid
phase is tap water or wastewater, respectively. This rate of oxygen transfer is
very rapid since the resistance of the gas film is negligible, and thus Step 1 is never
the controlhng one.
Step 2. Passage of oxygen molecules from the liquid interface to the bulk of
the liquid phase. Hence, C will denote the oxygen concentration in the bulk of
the liquid phase [ C < Q (or Q w ) ] . In the case of Step 2, the resistances involved
in this oxygen transfer are those offered by the hquid film and the resistance to
oxygen diffusion into the bulk of the hquid phase.
At very low mixing levels (low turbulence), the resistance to diffusion into the
bulk of the liquid phase is greater than the liquid film resistance. At moderate
turbulence levels the resistance to diffusion into the bulk of the liquid phase is
decreased and then the liquid film resistance will control the diffusion rate. At
higher turbulence levels the liquid film is broken u p and the rate of oxygen
transfer is controlled by the surface renewal rate, which is the frequency at which
hquid droplets with a concentration C replace the interface hquid in which the
oxygen concentration is Q (or Cs^).
Consider the diagram in Fig. 4.1a for the transfer of oxygen across the hquid
film.
The rate of oxygen transfer is given by Fick's diffusion equation apphed
across the hquid film:
dM/dt = - DA dC/dXf (4.5)
3. Oxygen- Transfer Rate Equation 171
Distance, χ Distance, χ
(α) (b)
Fig. 4.1. Diagram for oxygen transfer through liquid film: (a) rigorous Pick's equation, (b) linear
approximation.
dM C-Q Q-C
= - DA - = DA— (4.6)
dt X( X{
Dividing both members by the volume of the liquid phase V:
A c ^
V dt V X, ^ ^
dC
O C = — = K^a{C, - C) (tap water, Q) (4.8)
at
dC
OC = — = K^a{C,^ - C) (wastewater, Q^) (4.9)
dt
The term dCjdt represents the pounds of oxygen transferred per hour per ft-^
and is designated as oxygenation capacity (OC) as indicated in Eqs. (4.8) and
(4.9).
In the determination of the oxygen-transfer coefficient, the overall coefficient
Ki^a is obtained without attempting t o separate the factors A^L and a. It is
admittedly impossible to measure the interfacial area A.
The difference (C^ — C) or (C^^ - C) between dissolved oxygen saturation
value at the hquid film interface and actual concentration of oxygen in the bulk
of the hquid phase is called oxygen deficit. It represents the driving force to
oxygen transfer. F o r a steady-state operation of a continuous aerobic reactor, C
is kept constant at all times, and thus the rate of oxygen-transfer is a constant
value. This steady-state value of C is hence denoted as CL . In the case of a batch
aeration, C approaches Cs (or Cs^) as aeration proceeds; eventuahy the driving
force becomes zero and oxygen ceases to be transferred to the hquid phase.
For continuous aerobic treatment processes designed for removal of carbo
naceous organic matter, the range for steady-state operating dissolved oxygen
level C L is between 0.5 and 1.5 mg/liter. When nitrification is to be achieved,
dissolved oxygen levels in excess of 2.0 mg/hter are utilized.
T h e S t o i c h i o m e t r i c r a t i o is
Na2S03/i02=^=7.9
4. Determination of the Overall Oxygen-Transfer Coefficient 173
This means that theoreticahy 7.9 ppm of N a 2 S 0 3 are required to remove 1 ppm
of D O . Based on the D O of the test tap water, the approximate N a 2 S 0 3
requirements are estimated (a 10-20% excess is used). Sufficient cobalt chloride
is added to provide a minimum Co^ concentration of 1.5 ppm. An alternative
deoxygenation procedure consists of removal of dissolved oxygen by purging
with nitrogen gas.
Step 2, After D O concentration becomes essentially zero, start aeration,
measuring the increasing concentrations of D O at selected time intervals. Since
D O concentration increases with time, this method is termed unsteady-state
aeration. A steady-state method, in which D O concentration is kept constant, is
discussed in Section 7. Dissolved oxygen measurements are preferably per
formed by instrumental methods. A properly cahbrated galvanic cell oxygen
analyzer and probe is the most rehable method. Experimental determination of
D O by this technique is described in Section 2.3.1 of Chapter 2. Chemical
analysis of dissolved oxygen (Winkler method) is also employed [ 9 ] . The
aeration device is located at the center of the test basin. When circular basins are
employed, baffles are placed at the quarter points of the basin, as indicated in
Fig. 4.2, in order to prevent vortexing.
When testing is performed in a circular tank for pilot or full scale tests,
sampling depths for the D O determinations are 1 ft from the surface and 1 ft
from the bottom, at the mid and end points of the radii trisecting the basin.
This yields a total of 12 samphng points, as illustrated by Fig. 4.3. Samples
Baffles
Baffles
End point
'-Ο" ^ /
hereH
—Bottom
, „ of tank
r-o"-j—
(a) (b)
Fig. 4.3. Location of sampling points (a) shown in cross section of tank (b).
174 4. Theory and Practice of Aeration in Wastewater Treatment
from various test locations are analyzed for D O and the results are averaged and
recorded for the particular sampling time.
Step 3. Results are tabulated as shown by sample data in Table 4.3.
TABLE 4.3
0 0.0 10.1
10 2.6 7.5
20 4.8 5.3
30 6.0 4.1
40 7.1 3.0
50 7.9 2.2
60 8.5 1.6
ID
9
θ
7
1 4
20 40 60
Time (min)
Eq. (4.8)
dCIdt = K^a{C, - C)
Example 4 . 1 . D a t a presented in columns (1) and (2) of Table 4.3 are obtained
by utilizing an 8-hp surface aerator in a 150,000-gal circular test tank under the
following conditions:
Test water is deoxygenated using sodium sulfite and a cobalt catalyst. Calculate:
Solution
Requirements
Theoretical 71.1 p p m
Excess 15.0 ppm
86.1 ppm of N a 2 S 0 3
or
K^a = 2.303 log[(C - C,)/(Q - €2)^2 - t,) (4.11)
From Eq. (4.11) the value of Ki^a is calculated from only two experimental
determinations of D O . However, it is preferable to utihze the semilog linear plot
method with several experimental points, since this permits statistical averaging
of errors.
Time, t
It has been stated in Section 4 that aeration devices are rated by determining
the overall oxygen-transfer coefficient Ki^a utilizing t a p water as the hquid
phase. Furthermore, the oxygenation capacity utilized in this rating is that under
the so-called standard conditions corresponding to a t a p water temperature of
2 0 ° C , standard atmospheric pressure of 760 m m Hg and zero dissolved oxygen
concentration. The reader will notice that the determination of Ki^a in Example
4.1, although performed with t a p water, was not at the standard conditions as
defined above. However, corrections which will be described in this section can
be apphed to refer that Ki^a value to the standard conditions.
The most general corrections to be applied will be to relate the Ki^a value for a
wastewater at temperature T, pressure conditions different from the standard,
and a steady-state dissolved oxygen concentration C = C L (where C L > 0) to the
Ki^a value for tap water at standard conditions. F o r this case, write Eq. (4.9) for
8. Oxygen Capacity 1 79
(OC)actual (^L^)w,r
(OQstandard (^L^)20°C Q
In Eq. (4.17) Cs is the standard dissolved oxygen concentration at saturation
for tap water ( Γ = 20°C, Ρ = 760 m m Hg). This value (Table 4.1) is 9.2 mg/liter.
Therefore Eq. (4.17) becomes
The corrections t o be studied next, fall into three categories which are
considered in Sections 8.1-8.3.
8.1. T e m p e r a t u r e Corrections
First, in the numerator of Eq. (4.18), Ki^a for the wastewater at temperature Τ
will be written as a function of the Ki^a for the same wastewater, but at Γ = 20°C.
It h a s been observed that Ki^a increases with temperature. Eckenfelder [ 3 ]
proposed the following empirical equation t o account for this temperature
effect.
For the wastewater,
(OC)standard (^C/i/Ostandard
= a2ox X 1.024' X —
9.2
(4.26)
^(Q.s)76o _ - CL
= a^ox X 1.024^-20 χ — (4.28)
8. Oxygen Capacity 1 81
For the case of bubble aerators [Eqs. (4.29), (4.30), and (4.33)], it is necessary
to take into account the pressure correction due to the hydrostatic head of liquid
above the point of aeration. Oldshue [5] has proposed in this case to utihze for
the term Cs in Eq. (4.25), the oxygen saturation concentration for tap water at
aeration tank mid-depth. This term will be hence denoted as Cs,m. Equation
(4.25) will then be written as
Notice that i^Cs,^ represents the oxygen saturation concentration for the
wastewater at aeration tank mid-depth. Furthermore, Oldshue [5] proposed the
foUowing equation for Cs,m ·
-(PJ14.7) + (0,/21)"
Γ =c = C,s[(Pb/29.4) + (0,/42)] (4.30)
Terms Cs,^ and Cs,s have been previously defined. In case the barometric
pressure is different from 760 m m Hg, the value of Cs,s can be estimated from Eq.
(4.27), where (Cs,s)76o is the value of the saturation oxygen concentration read
from Table 4.1 at the operating temperature. The other terms in Eq. (4.30) are as
fohows.
Pb- Air pressure (psia) at the depth of air release. Since the standard
atmospheric pressure (14.7 psia) corresponds to a column of water 33.92
ft high, then
= ^atm + (<^/33.92) X 14.7 + [fricfional losses in piping system (psi)]
(4.31)
where Patm is the local atmospheric pressure (psia) and d is the depth of air
release (tank depth) in feet.
Ol- percentage of oxygen in exit gas leaving the liquid surface. This value
might be estimated from gas analysis made in covered aeration tanks in
bench-scale units. In case such data is not available, it may be assumed
that between 6% and 10% of the oxygen is absorbed. Since the air
contains initially 21% of oxygen,
0 , = 21(1 - x ) ( % ) (4.32)
where χ is the fraction of oxygen absorbed
0.06 <x< 0.10
There are modifications of conventional activated sludge process, such as
the U N O X process (Chapter 6, Section 4.5), which utilize pure oxygen
instead of air, and this can be taken into account in the choice of the value
for Of. Since Eq. (4.28) is only approximate, the term O JAI is frequently
estimated as 0.5, taking = 21%, without correcting for absorbed
oxygen. In this case, Eq. (4.30) becomes
Cs,. ^ Cs,s[(/'b/29.4) + 0.5] (4.33)
1 82 4. Theory and Practice of Aeration in Wastewater Treatment
1. Value of {Ki^a)2o°C'
Solution
StepL The value 1.85 h " ^ (Step 4, Example 4.1) was that f o r / = 15°C.From
Eq. (4.20)
( ^ L « ) 2 o c = (^Lfl)r X θ^""-^ = (1.85)(1.024)^^-^^ = 2.083 h " ^
Step 2. lb 02/h at standard conditions. F r o m Eq. (4.16)
lb 02/h = (^Lö)2oxC X V
1 . Ib02 lb water
lb02/h = 2.083 - X 9.2 X 10"^ — χ 150,000 gal χ 8.34
h lb water gal
= 24 lb 02/h
Example 4 . 3 . A diffused air system is employed in aeration of an activated
sludge tank. The diffusers are located 14 ft below the liquid surface. The
frictional loss in the piping system is estimated at 2 psi. T h e design is to be based
on an average barometric pressure of 740 m m Hg and a system temperature of
77°F (25°C). The manufacturer's specifications indicate that each diffuser unit is
capable of transferring 1.7 lb 02/h when operating under an air flow of 12
S C F M * , for aeration of t a p water at 20°C, 760 m m Hg pressure, and zero
concentration of D O (i.e., under standard conditions). Estimate the lb 0 2 / h
transferred per diffuser unit at actual operating conditions. Assume that 7% of
the oxygen bubbling through the water is absorbed. The values of a2ox and β
from bench-scale tests are 0.9 and 0.92, respectively. Base design upon an
operating steady-state value C L of 2.5 mg/liter.
Solution
Step I. Compute the value Cs,s for t a p water at the liquid surface at 25°C and
Ρ = 740 mm Hg from Eq. (4.27). (Cs,s)76o = 8.4 mg/liter from Table 4.1 a n d
= 23.756 m m Hg from Table 4.2.
740 - 23.756
Cs s = 8.4 = 8.17 mg/ Iter
760 - 23.756 ^'
* SCFM stands for standard cubic feet per minute measured at 760 mm Hg pressure and a
temperature of 0°C.
9. Transfer Efficiency of Aeration Units 183
Step 2. C o m p u t e the value Cs,^ at mid-depth from Eq. (4.30). The required
value of [Eq. (4.31)] is
740 14
= _ X 14.7 + X 14.7 + 2.0 = 14.3 + 6.1 + 2.0 = 22.4 psia
= (0.9)(i.024)—
= 0.74
TE = l b 0 2 transferred/(hp χ h) (4.34)
* Equation (4.35) is written, as indicated by the cos PF term, for the case of a three-phase motor,
which is by far the most common type in industrial power distribution systems.
1 84 4. Theory and Practice of Aeration in Wastewater Treatment
^ ^ = α . . , χ · . 0 2 4 - « χ ^ ^ ,4.36)
and also Eq. (4.28) does apply. For bubble aerators, from Eq. (4.29),
—— = c X 1.024^ χ — (4.37)
I A ^Jstand
where C^,. is given by Eqs. (4.30) or (4.33).
Example 4.4. For the aerator in Examples 4.1 and 4.2, report aerator standard
efficiency in terms of nameplate hp and blade hp. The following data are
available in addition to those for Examples 4.1 and 4.2:
Drawn voltage: 225 V (average)
Amperage: 20 A (average)
c o s P F (measured): 0.85
Motor efficiency (estimated): 90%
Gear efficiency (estimated): 90%
coefficient {Ki^a) of the wastewater to that of the tap water is given by Eq.
(4.23).
There are many variables which affect the magnitude of a. These include ( 1 )
temperature of the mixed liquor; (2) nature of the dissolved organic and mineral
constituents; (3) level of agitation of aeration basin, usually expressed in terms
of hp per 1 0 0 0 gal of basin volume; ( 4 ) characteristics of the aeration equipment;
and (5) liquid depth and geometry of aeration basin.
The temperature effect is attributable to temperature dependence of the liquid
film coefficient Ä^L- Figure 4 . 9 illustrates typical temperature effect on values
of a.
Since the nature of dissolved organic and mineral constituents affects a, its
value is expected to increase during the course of biological oxidation, because
dissolved organic materials affecting the transfer rate are removed in the
biological process. A typical situation is shown in Fig. 4 . 7 . As the final efñuent
approaches purity of tap water, the value of α approaches unity asymptotically.
Effect of mixing intensity in aeration basin (usually expressed in terms of
h p / 1 0 0 0 gal) is illustrated by Fig. 4 . 8 , which is a typical curve for a wastewater
containing surface-active agents. M a n y wastewaters of domestic and industrial
origin contain surface-active agents such as fatty acids and alcohols. These
compounds have a polar group (carboxyl and hydroxyl for the case of acids and
alcohols, respectively) and a nonpolar hydrocarbon chain. The polar groups are
hydrophilic, whereas the hydrocarbon chains are hydrophobic. It is assumed
1.0 -
0.8 -
0.6
Low » Moderate High
0 . 4 Lturbulence 1 turbulence turbulence
0.2
H P / 1 0 0 0 gal
that these surface-active agents concentrate at the interface hquid film, with their
polar hydrophilic groups dipping into the liquid film and their hydrophobic
hydrocarbon chains extending into the gas phase. This concentration of
molecules into the hquid film retards the process of oxygen diffusion described in
Section 2 (Step 2) of this chapter. As a result of this decreased oxygen transfer
for the wastewater as compared to the transfer for tap water, the ratios α [refer to
Eq. (4.23)] tend to be depressed to values of α < 1.0. Referring to Fig. 4.8, one
notices that this depression is less accentuated for the region of low turbulence.
This is explained by the fact that as described in Section 2 (Step 2) at very low
turbulence levels the resistance to oxygen diffusion into the bulk of the liquid
phase is greater than the liquid film resistance. At moderate turbulence levels
owing to the decrease of the resistance to diffusion into the bulk of the hquid, the
liquid film resistance becomes the controlhng factor to oxygen transfer. It is then
that the presence of the surface-active agents concentrated at the liquid film and
hindering the process of molecular diffusion becomes a critical factor. For this
reason the α values are depressed to a minimum in this region of moderate
turbulence as shown in Fig. 4.8. At high turbulence levels as described in Section
2, the liquid film is broken u p and the surface renewal rate becomes the
controlhng factor in oxygen transfer. Under such conditions the α values will
approach or even exceed unity as shown in Fig. 4.8.
An interesting illustration of the effect of characteristics of aeration equip
ment on the value of α is bubble aeration (air diffusion or turbine units) in the
presence of surface-active agents. Presence of these agents decreases bubble size,
and thus increases interfacial area per unit volume. Under these conditions the
Ki^a value of the wastewater usually increases, because increase in a exceeds
decrease of A^L caused by the surface barrier. This increase in Κγ^α of the
wastewater results in a corresponding increase of α [Eq. (4.23)].
0 0.05 0.15 0.25 0.35 Fig. 4.9. Plot of α versus power level at two
Power level (HP/1000 gal) different temperatures [ 3 ] .
13. Air Diffusion Units 1 87
Small bubbles, having a high surface area per unit volume, provide good
oxygen-liquid contact, leading to relatively high values of the oxygen-transfer
efficiency. Diameter of the bubbles released from these diffusers are 2.0 to 2.5
mm, the oxygen-transfer efficiency depending on bubble size, (ε from 5 to 15%
are common.) Standard porous diffuser units are designed to deliver 4-15 S C F M
of air per unit. ( S C F M stands for standard cubic feet per minute, referred to a
pressure of 760 mm Hg and a temperature of 0°C.) Diffusers with micropores of
the order of 3 μm in diameter are now available, with transfer efficiencies ε in the
range of 20-25%.
(compressed
air)
Fig. 4.10. Sketch of a fine bubble air diffusion system consisting of a series of porous ceramic
diffusers.
Perforated tube
Air bubbles wrapped witti α
Dacron sock-
Clomp
area for oxygen transfer is considerably less. Bubble sizes are u p to 25-mm
diameter. They have the advantage, however, of not requiring air filters, of
generally requiring less maintenance and lower power expenditure for the air
compressors. Sketches of two typical large bubble air diffuser units are shown in
Fig. 4.11. A large variety of designs for fine and large bubble diffusers is
commercially available [ 1 ] .
Performance data for air diffusion units are available as graphs for the lb of
O2 transferred/h per aeration unit versus the air flow per unit. A sample of
typical data for a Saran-wrapped tube (small bubble) is shown in Fig. 4.12.
3.0
- WIDE BAND
^ 1.5
c
—
y^i^NARROW
BAND
O
-h
0.3
02 1 1 1 1 1 1 11 . 1
2 5 10 20 30
Gs [air flow/unit (SCFM)]
Fig. 4.12. Oxygen-transfer data from Saran tubes in water [ 2 ] . (Reprinted with permission.
Copyright by the University of Texas Press.) · , 9-in. spacing narrow band; O , 9-in. spacing wide
band; Δ , 24-in. spacing narrow band; O , 5-in. spacing wide band.
Air diffusion units are not recommended when the oxygen uptake rate
( O U R ) , a parameter which was defined in Section 6 of this Chapter, exceeds 1
mg/(hter)(min). F o r values of O U R in the range from 1 . 0 - 1 . 4 mg/(hter)(min)
surface aerators are indicated. F o r higher values of O U R , turbine aerators are
preferable.
Eckenfelder [ 1 ] recommends the following empirical equation for correlating
performance of air diffusion units and tabulates values of characteristic
constants for several types of diffusers:
N=CG['-\H'^IWP){C,^ - C L ) Χ 1 . 0 2 4 ^ - ^ ^ χ α 20°C (4.39)
State 2 {P2J2)-
Isoenthalp (Hg)
Isoenthalp
the compressor inlet ( P i , Tj). Then fohow a vertical line (constant entropy for
the reversible adiabatic compression) until reaching the required discharge
pressure P2. This locates state 2 {P2, T2) corresponding to the condition of the
compressed air at the compressor discharge. From the first law of thermody
namics written for a continuous flow process, neglecting changes of potential
and kinetic energy between states 1 and 2 and taking into account that the
compressor is assumed to be adiabatic it follows that
W, = -AH= -(H2-H,) (4.46)
where is the shaft work for the compressor per pound of compressed air and
AH is the difference between the enthalpies Η2 and Hi (Btu/lb) for the air in
states 2 and 1, respectively. The values of H^ and Η2 are read from the diagram
(corresponding to the isoenthalps passing through points in the diagram
representing states 1 and 2). The final temperature T2 can also be read.
Equation (4.46) yields the compressor shaft work in Btu/lb. If is the pounds
of air per minute being compressed [Eq. (4.44)], the theoretical horsepower is
given by
lb Btu ft lb 1
hp = m. X W.— X 778: X
mm lb Btu 33,000 ft Ib/min/hp
= 0m36m,W, (4.47)
into account not only that the actual compressor is not a reversible adiabatic
ideal compressor, but also that there are losses in the electric motor and in the
transmission of work. In effect the overall efficiency EQ is
= X (4.49)
where £Ί stands for the thermodynamic efficiency (deviation of the actual
compressor from the reversible adiabatic one) and is the efficiency term,
allowing for the losses in electric motor and transmission of work.
An alternative procedure for estimating the compressor horsepower is based
upon the assumption that for the pressure and temperature ranges involved in
the compression, the behavior of air is adequately described by the ideal gas law.
In this case the shaft work is given by the well-known equation for the
reversible adiabatic compression of an ideal gas [8]:
> \(y-i)/y"
Btu/lb (4.50)
where R = 1.987 Btu/lb mole °R, y is the adiabatic constant (ratio of heat
capacities at constant pressure to constant volume, i.e., y = Cp/C^) and (jg) is the
number of lb moles in one pound of air, where the average molecular weight of
air is taken as 29. Take y = 1.4 for air. Equations (4.47) to (4.49) are then utilized
for the computation of the horsepower.
The value of the required pressure P2 can be estimated from Eq. (4.31), where
P2 = P^. The temperature T2 at the compressor exit may be estimated from the
relationship for adiabatic compression of an ideal gas [8]:
T2 = Τ,{Ρ2ΐΡιψ~'^" (4.51)
where the Τ are absolute temperatures (°R or °K).
Example 4.5. For the diffused air system in Example 4.3, design calculations
for the activated sludge unit (to be discussed in Chapter 5, Section 7.2.6)
indicated that 1450 Ib/h of oxygen are required.
Estimate:
1. Temperature of air at discharge conditions. Assume that inlet air is at the
average barometric pressure of 740 m m Hg and 60°F.
2. The number of diffuser units required.
3. Oxygen transfer efficiency ε.
4. The actual horsepower requirements, assuming an overall efficiency of
70% for the compressor unit.
Solution
Step 7. Estimate T2 from Eq. (4.51), where
P^ = P^ = 22.4 psia [Example 4.3, Step 2]
Pi=l^^ 14.7 = 14.3 psia
Γι = 60 + 460 = 520°R
y = 1.4
.'.T2 = 520(22.4/14.3)^^·^-^·^^/^·^ = 59rR (13ΓΕ)
194 4. Theory and Practice of Aeration in Wastewater Treatment
1.26
• -^ = 7 1 ^ ^ 100 = 9.4%
13.46
1.4 1 22 4 \ < ΐ · ^ - ΐ · 0 ) / ΐ · 4 ^
W, = (1.987)(520) 1 - = - 17.06 Btu/lb
' 1.4 - 1.0 29^ ^ 14.3
The minus sign simply indicates that work is done on the air (compression).
(b) Calculate (lb air/min) from Eq. (4.44):
lb air
m a = (0.081 X 12) χ 1151 units = 1119 lb air/min
(min)(unit)
(0.0236)(1119)(17.06)
Brake hp = = 644 hp
0.7
14.1. Description of U n i t
A sketch of a typical turbine aeration unit is shown in Fig. 4.14. These units
entrain atmospheric oxygen by surface aeration and disperse compressed air by
a shearing action employing a rotating turbine or agitator. Air bubbles
discharged from a pipe or sparger below the agitator are broken down by the
shearing action of the high-speed rotating blades of the agitator. For systems of
low oxygen utilization rate, oxygen is supphed by the flow of air self-induced
from a negative head produced by the rotator (suction effect). F o r systems of
higher utilization rate a blower or compressor is needed.
14. Turbine Aeration Units 195
An interesting feature of turbine units is the flexibihty, owing to the fact that
the degree of mixing is controUed by the power input to the turbine and is
therefore independent of the air flow, controlled by the compressor capacity. In
the cases of either diffuser units or surface aerators the degree of mixing and the
air supply cannot be independently varied.
where term Ki^a has units of h " ^ and V is the volume of the aerator tank in ft^. If
(Csw - CL) in Eq. ( 4 . 5 3 ) is given in mg/liter, its value is multiphed by factor
6 . 2 3 X 1 0 ~ ^ to obtain in Ib/h, as shown in Section 1 3 , 3 .
4.8 ^ 5.3
2.0 ^ /7 ^ 2.5
100 r-i— — 1 —
o 80
g
\ 60
• -
^ 40
-
5 20
-
1
20 40 60 80 100
G./Ap
Fig. 4.15. Effect of air rate on turbine horsepower hp^, actual hp; hpr,u, ungassed hp [Eqs. (4.54),
(4.55)]; Gs, air flow, S C F M ; A,, area of circle described by the rotation of the impeller = ^πΟ^.
14. Turbine Aeration Units 197
P¿ = hp,/hpe (4.57)
Pd=HP,/HP,
Fig. 4.16. Correlation for power split for turbine aeration units.
For fundamental information required see items 1 - 5 for air diffusion units
(Section 1 3 . 4 ) . Obtain performance data for the turbine aeration units available
from manufacturer's information or expressed in terms of values for the
constants in Eq. ( 4 . 5 2 ) . The following design procedure is then utihzed.
Step 1. Select a tank depth H, usually between 1 5 and 2 0 ft. In some cases
deeper hquid depths are employed.
Step 2. Cross-sectional area is then A = V/H.
198 4. Theory and Practice of Aeration in Wastewater Treatment
Step 3. Select a ratio r = D/T, where D is diameter of the turbine and Γ the
"diameter" of the tank. F o r tanks of circular cross section, the meaning of ratio
D/T is straightforward. For tanks with rectangular or square cross sections,
select a value for Τ based on geometry of the system. Selection of Τ for a
rectangular tank with two turbine aerators is illustrated by Fig. 4.17 ( Γ equals
the diameter of influence of the aeration unit, which is the diameter of a circle
within which complete mixing conditions prevail). In the final layout an overlap
of the circles corresponding to the diameters of influence is provided in order to
reduce or eliminate dead zones in prehminary layout (Fig. 4.17) where total
mixing does not occur. Typical Ζ)/Γ ratios are 0.1 to 0.2.
Step 4. F o r tanks of circular cross section, calculate the tank diameter Γ, i.e.,
Τ = (4Α/πΥ'^, where A is the cross-sectional area (Step 2). For tanks of
rectangular cross section select a tank width Τ approximately twice the tank
depth. Therefore turbine diameter is D = Τ χ r.
Step 5. Select the desired model of turbine unit with an air flow rate Cs, per
unit (SCFM/aeration unit). Typical values of are between 200 and 1500
SCFM.
Step 6. From Fig. 4.16 (manufacturer's data) determine optimum power split
P*.
Step 7. Value C^^ [to be used in Eq. (4.52)] is computed at tank mid-depth.
Refer to Section 13.4, Step 5.
Step 8. Oxygenation capacity per aeration unit [ i V = l b 0 2 transferred/h
unit] is estimated from manufacturer's data or computed from Eq. (4.52).
Step 9. F r o m oxygen requirements (lb 0 2 / h ) calculated in Chapter 5, Section
7.2.6 and value of TV calculated in Step 8, determine the number of aeration units
needed to transfer required a m o u n t of oxygen [Eq. (4.42)]:
There should be one turbine unit for every 900-2500 ft^. By varying air rate per
unit, i.e., Cs, one adjusts calculations so that spacing falls within this range.
Fig. 4.17. Ratio r = D/T (or a rectangular Fig. 4.18. Cross-sectional diagram of a
tank with two turbine aerators (prehminary surface aerator.
layout).
15. Surface Aeration Units 1 99
15.1. Description of U n i t
Surface aeration units are based solely on entrainment of oxygen from
atmospheric air. Unlike air diffusion and turbine aerators, there is no stream of
air involved in this system.
Improved design of surface aerators has resulted in improvement of oxygen-
transfer capacity and a rapid increase of their use in the past few years. They are
widely used in activated sludge plants and aerated lagoons.
The principle of operation of surface aerators is illustrated by the sketch in
Fig. 4.18. Liquid is drawn from underneath the unit and sprayed upward and
outward by a propeller inside a vertical tube.
Most conventional surface aerators are fixed to piers mounted across the
aerating tanks. Floating units are also available, the whole unit being supported
on a reinforced fiberglass float filled with plastic foam to make it unsinkable.
Oxygen transfer in surface aerators occurs according to two mechanisms: (1)
transfer at the turbulent liquid surface, and (2) transfer to droplets sprayed by
the blades of the unit. Considerable heat dissipation occurs due the evaporation
of the water droplets in the spray. The resulting temperature d r o p may cause
freezing, which may become a problem in the operation of surface aerators,
mainly during the winter months. F o r this reason, in regions where cold weather
prevails for a large fraction of the year, the utihzation of bubble aerators
(diffusers or turbine-type) is usually preferable to that of surface aerators.
Unit horsepower
30 40 50 55 60
0 0.1 0.2
Pv ( H P / 1 0 0 0 gal)
between diameter of influence and unit horsepower, which is also plotted in Fig.
4.19, is discussed in this section. Ordinate (TE)stand equals the lb of O2
transferred to tap water at standard conditions (20°C and 1 atm, with initial zero
dissolved oxygen) per (hp χ h). The correction to obtain oxygen transfer
( T E ) a c t u a i for a wastewater under operating conditions is obtained from Eq.
(4.36) as
( Q w = ßC.^s) (4.59)
where Q s is corrected for deviations from standard barometric pressure by Eq.
(4.27).
The linear correlation plotted in Fig. 4.19 is expressed by the relationship* [ 1 ]
* For the specific surface aerator unit corresponding to Fig. 4.19, this relationship is
( T E U „ d a r d = 3.4P, + 2.1
15. Surface Aeration Units 201
conditions per unit [lb 0 2 / ( h p χ h ) ] ; is the h p per 1000 gal of basin hquid; S
is a constant characteristic of the aeration device (in Fig. 4.19, .S corresponds to
slope of the straight line); and (TE), is the oxygen transferred to tap water at
standard conditions per (hp χ h) at zero turbulence. In Fig. 4.19, (TE),
corresponds to the ordinate of the straight line at the origin. For a given aerator,
(TE), corresponds to oxygen transfer per (hp χ h) at standard conditions in a
basin of infinite volume. In such cases, all oxygen transfer is accomplished by the
spray mechanism alone since turbulence is negligible. The subscript s in (TE),
stands for ''spray."
Performance of surface aerators is related to the following factors: (1)
submergence of impeller and (2) diameter and speed of rotor. Values for transfer
efficiency [ l b 0 2 transferred/(hp χ h)] are 2-4 for most surface aerators,
although values as high as 7 are reported. Transfer efficiency remains essentially
constant at an optimum submergence regardless of size of the unit.
Some typical ranges for power levels P^ in terms of hp/1000 gal of basin
volume are the following:
For fundamental information required see items 1-5 for air diffusion units
(Section 13.4). Next obtain characteristics for the aerator. This includes (1)
correlation of (TE),tand versus P^ and (2) correlation between unit horsepower
and diameter of influence for sohds in suspension (ft). For the specific design
illustrated by Example 4.5, these two correlations are presented in Fig. 4.19.
Depths of aerator basins for surface aerators are usually lower than for
diffusion or turbine aeration, ranging from 8 to 12 ft.
The design steps are as follows:
Step 1. Take Eq. (4.59) and calculate the term between brackets for summer
and winter conditions to determine which is the controlhng one. Remark that
jSC,,, = C,,,. Note that [C,J,u^„,er < [Csw]winter [thus (C,^ - C L ) [S larger for
the winter condifions], whereas Trümmer > ^winter»thus term 1.024^ is larger
for summer conditions. Let the results of this calculation be
Step 2. Since power level (abscissa of Fig. 4.19) is not known, a trial and error
solution is necessary for determination of (TE)stand based on the correlation of
(TE)stand versus power level.
where the oxygen requirement has been previously calculated from biological
reactor requirements (item 2 on Fundamental information required. Section
13.4).
(5) Recalculate power level:
Example 4.6. Surface aerators are to be specified for the activated sludge plant
designed in Chapter 5 [Section 7.14, Example 5.2, Step 9 ] . Oxygen requirements
and volume of the biological reactor are calculated by the procedure described in
Chapter 5, yielding the following results:
Solution
Step 1. Calculate the term between brackets in Eq. (4.59) for summer and
winter conditions:
Summer:
α,οχ Χ 1 . 0 2 4 —
Ρ-Ρ"
C,,,[Eq. (4.27)]: C , , = ( Q , J^eo _
where
(C.s)76o = 8.4 mg/liter [Table 4 . 1 , for Γ = 25°C]
Ρ = 755 mm Hg
755 - 23.756
• • ^ - - ^ • S 6 0 - 23.756 = ^ · ^ ^ '^^/'"^-·
and
Winter:
1 0 2 4 ^ - 2 0 = 1.024·^-^° = 0.847
.755
755 - 11.231
C s . [ E q . (4.27)]: C, = 1 0 ' 7. 660 -- —11.231
- — = 10.53
and
Cs,w = (0.97)(10.53) = 10.21
204 4. Theory and Practice of Aeration in Wastewater Treatment
Then
10.21 - 2.0
^winter = 0.87 X 0.847 X — = 0.658
h28'-0'^56'-0"—~28'-Öii
28'-'
-ét --
56'-0"
l68'-0" -I φ é - - -
56'-0"
PROBLEMS
0 0.00
12 2.65
24 4.50
36 5.80
48 6.70
60 7.33
Calculate:
Wastewater (0°C)
0 0.0
5 1.9
10 3.4
15 4.7
20 5.8
25 6.8
0 0.0
5 2.3
10 4.2
15 5.7
20 6.9
25 7.9
III. The following smoothed data were obtained utilizing the unsteady-state
aeration technique for a petrochemical wastewater at 15°C [3] and at four
different power levels.
Power level no. 1 Power level no. 2 Power level no. 3 Power level no. 4.
(0.05 hp/1000 gal) (0.15 hp/1000 gal) (0.25 hp/1000 gal) (0.35 hp/1000 gal)
The same tests were then repeated utilizing tap water, also at 15°C. The data
are as follows:
Problems 207
Power level no. 1 Power level no. 2 Power level no. 3 Power level no. 4
(0.05 hp/1000 gal) (0.15 hp/1000 gal) (0.25 hp/1000 gal) (0.35 hp/1000 gal)
0 0.0
5 2.4
10 4.4
15 5.9
20 7.2
25 8.2
During this experiment the tank was covered and the effluent gas was
analyzed with the following result:
Volume (%)
CO2 2.3
16.9
N2 80.8
0 0.0
5 1.5
10 2.8
15 4.1
20 5.2
25 6.1
Volume (%)
CO2 2.7
O2 18.8
N2 78.5
where D is the impeller diameter (ft) and η is the revolutions/sec of the rotor.
1. Compute Ki^a ( h " ^ ) . Turbine is 40-in. diameter, rotating at 15 ft/sec
peripheral speed and air flow is 300 S C F M (measured at 760 m m Hg and 0°C).
Problems 209
2. Calculate the pounds of oxygen transferred per hour to the wastewater for
a continuous operation at a steady-state oxygen concentration in the hquor of
2.0 mg/liter. Wastewater temperature is 20°C and C^w = 8.45 mg/liter.
3. Calculate the turbine horsepower corrected from Fig. 4.15.
4. Calculate the brake horsepower for the compressor. F o r this calculation
base estimates of discharge pressure on an atmospheric pressure of 14.7 psia,
allow a 4-psi air pressure d r o p through piping and the required hydrostatic head.
Take inlet air at 60° F, y = 1.4, and an overall compressor efficiency of 65% with
respect to the ideal reversible adiabatic compressor. What is the ratio P^ of
power supplied to the rotor to compressor power?
5. Estimate oxygen-transfer efficiency, Eq. (4.38).
hp=/[^,K,^_r,.S,(TE)J
VII. 1. Write an equation for the ratio C'J{C^)η^o, equivalent to Eq. (4.3) for
aeration of tap water with a surface aerator, for the case of oxygenation with
pure oxygen (Chapter 6, Section 4.5) where
Like for the case of Eq. (4.3) assume applicability of Henry's law.
2. With the equation estabhshed in Part 1, calculate the dissolved oxygen
saturation concentration for tap water, oxygenated with pure oxygen, with a
surface type aerator in a covered biological reactor. The pressure of the gas
phase is 795 mm Hg and the tap water temperature is 15°C.
For a wastewater which is to be oxygenated under these same conditions,
estimate the saturation concentration of dissolved oxygen, taking β = 0.96.
3. F o r this surface aerator, the value of (TE)standard is 2.2 lb 0 2 / ( h p χ h). This
value corresponds to oxygen transfer to tap water at Ρ = 760 m m Hg, t = 20°C
and an initial dissolved oxygen concentration C = 0.
21 o 4. Theory and Practice of Aeration in Wastewater Treatment
Estimate the value of (TE)actuai [lb02/(hp χ h)] for the case of oxygenation
of the wastewater in Part 2 with the covered reactor ( P = 795 m m Hg, / = 15°C),
in a continuous process when the steady-state dissolved oxygen concentration is
CL = 6.5 mg/liter. Take « 2 0 c = 0.8.
REFERENCES
1. Eckenfelder, W. W., Jr., "Water Quality Engineering for Practicing Engineers." Barnes & Noble,
New York, 1970.
2. Eckenfelder, W. W., Jr., and Ford, D. L., in "Advances in Water Quality Improvement" (E. F.
Gloyna and W. W. Eckenfelder, Jr., eds.), p. 226. Univ. of Texas Press, Austin, 1968.
3. Eckenfelder, W. W., Jr., and Ford, D . L., "Water Pollution Control." Pemberton Press, Austin
and New York, 1970.
4. Eckenfelder, W. W., Jr., and O'Connor, D . J., "Biological Waste Treatment." Pergamon,
Oxford, 1961.
5. Oldshue, J., "Biological Treatment of Sewage and Industrial Wastes." Van Nostrand-Reinhold,
Princeton, New Jersey, 1956.
6. Perry, R. H., and Chilton, C. H., "Chemical Engineer's Handbook," 5th ed. McGraw-Hill, New
York, 1973.
7. Quirk, T. P., unpubHshed report (1962) (mentioned in Eckenfelder [1]).
8. Smith, J. M., and Van Ness, H. C , "Introduction to Chemical Engineering Thermodynamics,"
3rd ed. McGraw-Hill, New York, 1975.
9. "Standard Methods for the Examination of Water and Wastewater," 15th ed. Yearbook Publ.,
Chicago, IlHnois, 1981.