Professional Documents
Culture Documents
Chimney Breast Removals: Building Control Advice Sheet BC14
Chimney Breast Removals: Building Control Advice Sheet BC14
CHIMNEY BREAST
REMOVALS
Background
Since the 1960s coal and gas fires have become less fashionable and have been largely replaced by central heating. The
removal of disused chimney breasts can create additional floor space and larger living areas, especially in bedrooms.
The preferred option is to remove the stack fully. Alternatively, part of the stack may be retained. This guidance leaflet provides
advice on how to undertake this simple project. Advice Sheet BC11 shows how to get the necessary consent via a building
notice.
Is it Suitable?
Most chimneys in semi--detached or terraced houses are installed back to back on to the party walls between two properties.
These are generally suitable for removal. Some chimneys are installed within the party wall and cannot be removed safely
unless both neighbours are in agreement.
Fig. 1
The chimney may also provide buttressing to a gable wall (especially if you have already created a through lounge), and may
also be unsuitable for removal as it acts as a pier. Check Fig. 2 below to ensure that the gable wall has sufficient restraint.
675mm min.
190mm min.
Fig. 2
Support Method
Medway Council accepts two support methods:
6mm MS
checker
plate
75 x 75mm
mild steel
angle –
welded or
bolted
Side
together
pre-drilled
holes for
Rawlbolts
breast on 1st
1 floor 1
®
breast
G removed G Section
®
Plan
Other Work
The support in all cases must be protected against fire by encasement in plaster board. This protection may be provided by
the ceiling if the support is above it.
Whichever approach is used, the disused flues should be capped by an air brick. Redundant hearths should be removed, the
floors and roof repaired and the plasterboard/plaster patched and made good.