1) A single-phase unified power quality compensator (consisting of a DSTATCOM and a DVR 1 point
Week 2
using two VSCs with a common DC bus capacitor) is to be designed for a load of 230 V, 50 Hz, 25 A, 0.8
lagging power factor as a left-hand UPQC-Q, it used to provide reactive power compensation of the load
Week 3
for unity power factor at the AC mains with a constant regulated voltage of 230V at 50 Hz across the load.
Week 4 There is a voltage sag of -10% in the supply system with a base value of 230 V. Calculate the voltage rating
of the DVR (SSSC connected in distributed system )of the UPQC-Q,….
Week 5
49.32 V
Week 6
38.6 V
Week 7 44.3 V
UPQC 43.17 V
Introduction
and
No, the answer is incorrect.
Classification Score: 0
UPQC
Accepted Answers:
Classification - I 43.17 V
Operation and 2) In above question Q1, the total VA rating of the DVR of the UPQC-Q is …. 1 point
Control of
UPQC - II 1207.23 VA
Operation and 1079.25 VA
Control of
UPQC - III 984.25 VA
UPFC 921.4 VA
Quiz : No, the answer is incorrect.
Assignment 7
Score: 0
Solution for Accepted Answers:
Assignment - 7
1079.25 VA
Funded by
11.45 Powered
A by
2345.25 VA
1745.25 VA
4529.25 VA
5684.25 VA
5) A single-phase unified power quality compensator (consisting of a DSTATCOM and a DVR 1 point
using two VSCs with a common DC bus capacitor) is to be designed for a load of 230 V, 50 Hz, 25 A, 0.8
lagging power factor as a left-hand UPQC-P, used to provide reactive power compensation for unity power
factor at the AC mains with a constant regulated voltage of 230V at 50 Hz across the load. There is a
voltage swell of +10% in the supply system with a base value of 230 V. Calculate the voltage rating of the
DVR of the UPQC-P,….
28.05 V
26.12 V
29.95 V
24.58 V
6) In above question Q5, the total VA rating of the DVR of the UPQC-P is …. 1 point
1028 VA
701 VA
870 VA
685 VA
7) In above question Q5, The current rating of the DSTATCOM of the UPQC-P is …. 1 point
12.7 A
13.9 A
14.5 A
14.7 A
Score: 0
Accepted Answers:
13.9 A
4496 VA
4296 VA
3296 VA
3496 VA
9) A single-phase unified power quality compensator (consisting of a DSTATCOM and a DVR 1 point
using two VSCs with a common DC bus capacitor) is to be designed for a load of 230 V, 50 Hz, 25 A, 0.8
lagging power factor as a left-hand UPQC-Q used to t provide reactive power compensation of the load for
unity power factor at the AC mains with a constant regulated voltage of 230V at 50 Hz across the load.
There is a voltage swell of +10% in the supply system with a base value of 230 V. calculate the voltage
rating of the DVR of the UPQC-Q
32.13 V
34.12 V
35.64 V
36.58 V
10)In above question Q9, VA rating of the DVR of the UPQC-Q is, 1 point
891.15 VA
981.31 VA
1032.42 VA
1123.45 VA