Professional Documents
Culture Documents
EG407720 (A) B - A50 Manual
EG407720 (A) B - A50 Manual
Instruction Manual
PRISMIC A50 EXCITATION CONTROLLER
Editor: D.NAVRATIL
Checked: P. HLAVAC B Corrections to figure numbering and other C. N. Watts R. Thornton-Jones 03/03/09
minor corrections
Approved: P.HLAVÁČ A First release C. N. Watts R. Thornton-Jones 17/12/2008
Date: 17/12/2008 Index: Change description: Editor Approved Date:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 1
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
CONTENTS
1. INTRODUCTION TO MANUAL ...................................................................................................... 4
1.1. General .................................................................................................................................................4
1.2. How To Use The Manual ......................................................................................................................4
1.3. Copies ...................................................................................................................................................5
1.4. Feedback ..............................................................................................................................................5
1.5. Service & Spares ..................................................................................................................................5
1.6. Contact Address....................................................................................................................................5
1.7. Health & Safety At Work .......................................................................................................................5
1.8. Protection And Monitoring Devices .......................................................................................................6
2. EU DIRECTIVES............................................................................................................................. 7
3. INTRODUCTION............................................................................................................................. 8
3.1. Main Features .......................................................................................................................................8
3.2. Basic Specification................................................................................................................................9
3.2.1. Electrical ........................................................................................................................................................... 9
3.2.2. Communication................................................................................................................................................. 9
3.2.3. Mechanical........................................................................................................................................................ 9
3.2.4. Electromagnetic Compatibility......................................................................................................................... 10
3.2.5. Environmental conditions ................................................................................................................................ 10
3.2.6. Protection against electrical shock .................................................................................................................. 10
4. INTERFACES................................................................................................................................ 11
4.1. Type of connectors and terminals .......................................................................................................11
4.1.1. Connectors X1 to X5 ....................................................................................................................................... 11
4.1.2. Terminal board X6 .......................................................................................................................................... 12
4.1.3. Connector X7 .................................................................................................................................................. 12
4.1.4. Connectors X8 to X11 ..................................................................................................................................... 12
4.1.5. Protective earth............................................................................................................................................... 12
4.2. Connecting points ...............................................................................................................................13
4.2.1. X1:1 to 18 – DIGITAL INPUTS........................................................................................................................ 13
4.2.2. X2:1 to 5 – FEEDING...................................................................................................................................... 14
4.2.3. X2:6 – HIGH SPEED LOGICAL INPUT........................................................................................................... 14
4.2.4. X2:7 to 14 – LOGICAL INPUTS ...................................................................................................................... 14
4.2.5. X2:15 to 18 – DIGITAL OUTPUTS .................................................................................................................. 15
4.2.6. X3:1 to 18 – DIGITAL OUTPUTS.................................................................................................................... 15
4.2.7. X4:1 to 13 – VOLTAGE AND CURRENT SENSING INPUTS ......................................................................... 16
4.2.8. X4:14 TO 18 – UNIVERSAL ANALOG INPUT ................................................................................................ 17
4.2.9. X5:1 to 9 - CURRENT SENSING INPUTS ...................................................................................................... 17
4.2.10. X5:10 TO 12 UNIVERSAL ANALOG INPUT ................................................................................................... 18
4.2.11. X5:13 TO 18 ANALOGUE OUTPUTS ............................................................................................................. 19
4.2.12. X6:1 to 6 – RECTIFIER VOLTAGE SENSING INPUTS .................................................................................. 19
4.2.13. X7 - RECTIFIER CONTROL AND DIGITAL INPUTS ...................................................................................... 20
4.2.14. X8, X11 SERIAL COMMUNICATION PORTS................................................................................................. 22
4.2.15. X9 - CAN COMMUNICATION PORT ............................................................................................................. 23
4.2.16. X10 CAN COMMUNICATION PORT............................................................................................................... 23
4.2.17. X12, X13 CONNECTORS ............................................................................................................................... 23
4.3. Local Signalling...................................................................................................................................23
5. MAINTENANCE ............................................................................................................................ 25
6. COMMISSIONING ........................................................................................................................ 25
6.1. Pre-commissioning Checks.................................................................................................................25
6.2. Commissioning Checks.......................................................................................................................25
6.2.1. Initial State...................................................................................................................................................... 25
6.2.2. Tests with Generator Under Short-Circuit Run ................................................................................................ 26
6.2.3. Tests with Generator Under No-Load Run ...................................................................................................... 26
6.2.4. First Synchronizing ......................................................................................................................................... 26
6.2.5. Tests After Generator Synchronizing with the Network ................................................................................... 26
6.2.6. Complete Tests............................................................................................................................................... 26
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 2
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 3
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
1. INTRODUCTION TO MANUAL
1.1. General
The purpose of this manual is to provide information and advice on supplied equipment.
Information is given for guidance only and we do not accept any responsibility for the
manner in which the information is used, nor the consequences thereof.
The design and manufacture of equipment is subject to constant review and as a result
the information provided herein may vary from that manufactured.
Verbal or written modifications to the information contained herein have no legal status
unless confirmed in writing by the Engineering Director or his nominated deputy.
The manual, and any amendments, should be maintained for the lifetime of the
equipment.
All pages and topic headings are numbered for easy reference. Cross-reference(s) to
associated paragraphs and documentation is included where appropriate. When
referencing particular paragraphs in communications, it is important to specify the
Manual Number and the Issue Reference.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 4
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
1.3. Copies
Additional copies of the latest available version of manuals can be obtained from our
Service Department at the contact address given hereafter. A nominal charge may be
made for this service.
The information provided remains the copyright of Brush SEM s.r.o. , and is not to be
copied or disclosed to a third party without the written approval of the Sales Director at
the contact address given hereafter.
1.4. Feedback
We are constantly seeking to improve the quality and reliability of our products, and we
actively encourage user feedback.
Quotations for Service and Spares can be obtained from the Service Department at the
contact address given hereafter.
E-Mail: service.sales@bem.fki-et.com
spares.sales@bem.fki-et.com
The information hereunder is with respect to the duties of manufacturers, designers and
installers in providing health and safety information to Customers. The information
advises of reasonably foreseeable risks involved with the safe installation,
commissioning, operation, maintenance, dismantling, cleaning or repair of products
supplied by Brush. Every precaution should be taken to minimise risk. When acted
upon, the following precautions should considerably minimise the possibility of
hazardous incidents.
Delivery Checks: Check for damage sustained during transport. Damage to packing
cases must be investigated in the presence of an Insurance Surveyor.
Installation: Where installation is made by engineers other than Brush personnel, the
equipment should be installed by suitably qualified personnel in accordance with
relevant legislation, regulations and accepted rules of the industry. In particular, the
recommendations contained in the regulations with regard to the earthing (grounding)
must be rigorously followed.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 5
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Electrical Installation:
IMPROPER USE OF ELECTRICAL EQUIPMENT IS HAZARDOUS.
Before working on a unit, switch off and isolate it and all other equipment
within the confines of the same control panel. Check that all earth
connections are sound.
Adjustment and fault finding on live equipment must be by qualified and authorised
personnel only, and should be in accordance with the following rules:
Read the Instruction Manual.
Use insulated meter probes.
Use an insulated screwdriver for potentiometer adjustment where a knob is not
provided.
Wear non-conducting footwear.
Do not attempt to modify wiring.
Replace all protective covers, guards, etc. on completion.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 6
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
2. EU DIRECTIVES
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 7
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
3. INTRODUCTION
• Automatic control of generator terminal voltage, steady state regulation accuracy +-0.25%
o Reactive power compensation
o Generator rotor and stator current limitation with time delay proportional to the
square of current exceeding the admissible limit. The stator current limiter works in
both overexcited and underexcited areas.
o Underexcitation limiter
o Generator terminal voltage limiter, U/f ratio limiter with delay indirectly proportional to
U/f ratio exceeding the preset limit
o Dual input Power System Stabilizer
o Regulation of reactive power or power factor (the set value is set by remote control)
o Regulation of reactive power equal to zero (prior to disconnection of generator from
network)
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 8
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
• Easy interfacing to SCADA systems – I/O , serial link with standard protocol
• Windows HMI commissioning Software (Windows 95/98, NT, 2000, XP)
• Option: Automatic or Check Synchronization Function – control of machine set speed and
equalizing of generator voltage with that of the network prior to closing of the generator
circuit breaker
3.2.1. Electrical
3.2.2. Communication
3.2.3. Mechanical
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 9
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
• Indoor use
• Altitude: up to 2000 m
• Operating Temperature Range: -25°C to +55°
• Cooling: AN (Air Natural)
• Storage Ambient temperature: -40°C to +85°C
• Maximum relative humidity: up to 90% non condensing
• Pollution degree: 2
• Mains supply voltage fluctuation: 24V +20%, -15%
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 10
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
4. INTERFACES
X1 X3
X2
X8 –
X7 X11
X12,
X13 X6
X5
PGND
X4
4.1.1. Connectors X1 to X5
Figure 3: X1 to X5 plugs
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 11
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Plug features:
plug fixing: screw flange, vibration resistant
wire connection: spring-cage
number of positions: 18
2
Single conductor size: solid/stranded, 0.2 …2,5mm / AWG24-12
stripping length: 10mm
Multiple connection (two stranded conductor with the same cross section, with twin
2
ferule with plastic sleeve) 0.5-1mm / AWG 20 -18, length of sleeve 12mm
Terminal MKDSP10HV/2-12,7
• wire connection: screw
• number of positions: 6
• Stripping length: 10mm
• Single conductor size (stranded conductor , ferule with plastic
2
sleeve): 0.5 …10mm / AWG 20-8
• Multiple connection (two stranded conductor with the same cross
2
section, with twin ferule with plastic sleeve) 0.5-6mm / AWG 20-10
length 10mm
4.1.3. Connector X7
D- SUB 9M with fixing nuts 4-40UNC. Plugs D-SUB 9F with hoods and screw
locking are not included in delivery. Suitable types are for example connectors from
PHOENIX CONTACTS of SUBCON or SUBCON-PLUS types.
Left side bottom fixing must be connected to the protective ground. Two ways can
be used in accordance with applied mounting plate:
• For grounded conductive non painted mounting plate is used direct contact
between mounting plate and bottom fixing secured by tighten M5 fixing bolt.
This way is recommended).
• For other mounting plates must be used wire with minimum size 2,5mm
2
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 12
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
* Power supply with fuse or equivalent device with rated current 6A or less
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 13
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
G1, G2 are external power supplies with internal fuse or equivalent device with a
rated current of 10A
Input is electrically connected with supply voltage on terminals X2:1 to 5 and logical
inputs X2:7 to 14.
Connector X2 includes 8 of the digital inputs that are configured as sink (- common
inputs) (see Figure 6), as the common is uses the 0V on the connector terminal
X2:5
Inputs are electrically connected with the supply voltage on terminals X2:1 to 5 and
high speed input X2:6.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 14
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
* Power supply with fuse or equivalent device with rated current 6A or less
Connector X3 includes 16 of the digital inputs divided into two groups with common
potentials. Power supplies G4 and G5 can either be external power supplies* or the
+24V and 0V from the connector terminals X2:3 and 5 (see Figure 6: Digital inputs
supply)
* Power supply with fuse or equivalent device with rated current 6A or less
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 15
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Figure 10: Single phase current sensing (left), 5A/1A current range (right)
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 16
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
+-250mV DC
• Measuring range +-250mV
• Maximum continuous over voltage +-5VDC
• Input resistance 820Ω
PT100 thermometer
• Measuring range -25 to +50°C
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 17
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
+-250mV DC
• Measuring range +-250mV
• Maximum continuous over voltage +-5VDC
• Input resistance 820Ω
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 18
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 19
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The PRISMIC A50 Excitation Controller includes the capability for control of eight
switching elements (thyristors or IGBT modules). For each element there is a
control output +-24V/0,5A with integrated short circuit protection (a,b) and two logic
inputs 24V DC with a common 0V (c,d,e,f ) see Figure 17.
Circuits are fed from the 24V DC supply connected to terminals X2:1 to 5 see
4.2.2.
Number of X7 pins for individual in rectifiers with crowbar over-voltage protection (Figure 18)
B6C B2C
Figure 14 a b c d e f a b c d e f
V1 1 2 3 4 5 6 1 2 3 4 5 6
V2 31 32 33 34 35 36 19 20 21 22 23 24
V3 13 14 15 16 17 18 13 14 15 16 17 18
V4 7 8 9 10 11 12 7 8 9 10 11 12
V5 25 26 27 28 29 30 37 38 39 40 41 42
V6 19 20 21 22 23 24 43 44 45 46 47 48
V7 37 38 39 40 41 42 N/A N/A N/A N/A N/A N/A
V8 43 44 45 46 47 48 N/A N/A N/A N/A N/A N/A
Table 1: X7 pins
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 20
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 21
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Both the X8 and X10 ports contain configurable RS232 / RS422 / RS485 electrically
isolated transceivers (Tx, Rx signals only). RS232 is active when connected to pins
7 and 8. With pins 7 and 8 disconnected, RS422 is active with pins (1) 9, 4 and 2,3.
Pins 2 and 3 can be connected together to obtain RS485. 120R terminating
resistors for RS422 and RS485 end nodes need to be situated in the D-SUB
connector housings.
The X8 port is used as a service port for connection to a PC. The following cable is
recommended:
9F/9F Serial BRUSH SEM
communication PART.No:
cable, length 3m 6115 4299 0000
For a PC without a RS232 port the following adaptor can be used with the USB
port:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 22
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The X11 port can be used for communication with a SCADA or other system.
The CAN port is used for mutual interconnection of two redundant A50 controllers.
The port is not electrically isolated. Pin assignment:
2 CAN-L
7 CAN-H
The CAN port is used for auxiliary communication links, for example for connection
of local or remote operator consoles. The port is electrically isolated, testing voltage
500V, 50Hz/1min. Pin assignment:
2 CAN-L
7 CAN-H
3 GND
The PRISMIC A50 Excitation Controller is equipped with internal connector for a
plug in communication module (COM-C, Hilscher) with advanced SCADA
communication protocols (like PROFIBUS-DP). When the communication module
is installed, the plug blanking plate is replaced by the port connectors.
1 Digital inputs X1 X1:10 X1:9 X1:8 X1:7 X1:6 X1:5 X1:4 X1:3
aX07 aX06 aX05 aX04 aX03 aX02 aX01 aX00
2 Digital inputs X1 X1:18 X1:17 X1:16 X1:15 X1:14 X1:13 X1:12 X1:11
aX17 aX16 aX15 aX14 aX13 aX12 aX11 aX10
3 Digital inputs X2 X2:14 X2:13 X2:12 X2:11 X2:10 X2:9 X2:8 X2:7
bX23 bX22 bX21 bX20 aX23 aX22 aX21 aX20
4 Digital inputs X7 X7:24 X7:22 X7:18 X7:16 X7:12 X7:10 X7:6 X7:4
bX07 bX06 bX05 bX04 bX03 bX02 bX01 bX00
5 Digital inputs X7 X7:48 X7:46 X7:42 X7:40 X7:36 X7:34 X7:30 X7:28
bX17 bX16 bX15 bX14 bX13 bX12 bX11 bX10
6 Digital outputs X3 X3:9 X3:8 X3:7 X3:6 X3:5 X3:4 X3:3 X3:2
bY07 bY06 bY05 bY04 bY03 bY02 bY01 bY00
7 Digital outputs X3 X3:18 X3:17 X3:16 X3:15 X3:14 X3:13 X3:11 X3:10
bY17 bY16 bY15 bY14 bY13 bY12 bY11 bY10
8 Digital outputs X2 X2:18 X2:16
aY01 aY00
9 Reserve
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 23
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 24
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
5. MAINTENANCE
The A50 Excitation Controller is completely solid state, apart from configuration rotating switches,
and requires very little maintenance. It is recommended that the AVR is inspected approximately
every 12 months to check for excessive dust build-up, and that all connections are secure.
Excessive quantities of dust should be removed with a soft brush.
In common with generator protection systems it is good practice to annually check the calibration
and the correct operation of all the various functions of the A50. This will involve making tests that
were carried out during commissioning. If required a Service Engineer can be provided by Brush.
It should be noted that some of the functions, such as the limiters and special protections, may
never have needed to operate since the equipment was installed.
6. COMMISSIONING
Commissioning of the excitation system is a complex process that is not limited to the Excitation
Controller. The Excitation Controller is mounted into the excitation cubicle together with all
necessary equipment and is designed to fulfil the specific requirements of individual generators
and individual customers. The following provides a general overview of commissioning steps
commonly applied for excitation systems. These steps are usually performed together with the
setting and activation of individual electrical protection. For further detail, it is necessary to consult
the instruction manual for the particular excitation system and specific contract documents.
Initial state: finished building adaptation, assembly of cubicle and cabling (external
circuits for connecting the auxiliary supply voltages are prepared), room for excitation
equipment is clean, initial revision report is at disposal.
a) Visual inspection of switchboards
b) Check of protective grounding
c) Check of insulation state
d) Check of auxiliary supply voltages
e) Check of power supplies
f) Check of switchboard heating and lighting
g) Check of links-up to CTs / PTs
h) Check of sensors and actuating units of excitation set
i) Check of links-up to power plant control system and technology
j) Check of links-up to block protections ( emergency shut-down, tripping of field circuit
breaker)
k) Check of power links-up to Excitation transformer and to field winding
l) Check of thyristor rectifier function in manual control
Note: Tests according to 8.2.2-a),b),e); e) -a),f ) to i); 8.2.4 -b),d), 8.2.5 -c) to g) will be
carried out by a BRUSH authorised testing specialist. Mentioned specialist will cooperate
with others in remaining tests.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 25
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Note 1:
The A50 transducers are calibrated at the factory prior to despatch and will not normally
require adjustment.
Note 2:
Levels of active power for tests of underexcitation limiter and power system stabiliser: The tests are
performed after generator synchronising and during continuous increasing of the active power P from 0
to 100%. The first level is after synchronising, i.e. approx. P = 0. At this level only the underexcitation
limiter is checked (power system stabiliser is not activated). The next level is in the range from P=40 to
60% Pn (technological minimum). The last level is represented by rated active power.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 26
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
7.1. Introduction
7.3. Commissioning PC
The software runs under MS Windows (NT 4.0, 95/98, XP or Vista) and should
install automatically when the CD is inserted. If Autorun is disabled on your PC the
setup application can be run directly from the CD. Using the supplied serial
communication cable, connect the PC COM1 serial port to the serial port of the A50
unit.
On the Windows desktop, double click on the ‘AVR HMInt’ icon to run the software.
The HMI can be used to work with various BRUSH PRISMIC Excitation
Controllers/Cards including the A50. The HMI automatically detects the controller
that is connected.
The HMI software indicates healthy communication with the unit to be setup by
showing rotating ' / ' symbol in the bottom right corner of the HMI Window Status
Bar. If this symbol is stationary, there is no communication and the HMI cannot be
used to display relevant data.
Close the HMI application in the normal manner for any Windows application, i.e.
select ‘Exit’ from the ‘File’ menu or press [Alt] [F4].
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 27
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
There are several displays, each display shows values corresponding to some A50
feature or functional block.
7.9. Trending
The trend display is used to show the value of the selected variable over a
particular time span. The speed of communication is such that the trend display is
unsuitable for accurately displaying generator response, but can be useful for
displaying long term changes. This feature is accessible directly from the HMI main
menu.
7.10. Presets
Presets are accessible directly from the HMI main menu. Here you can set and
change various A50 parameters and constants. There are two lists of presets -
Maintenance presets and Operator presets. ‘Maintenance presets’ is an
exhaustive list of all the presets, whereas the ‘operator presets’ are split into
categories to group the presets accordingly making it easier to find them as
required. (Both lists contain the same presets). The method of changing a particular
preset value is the same in both cases.
Go to the menu - Presets, there are two lists of presets Operator Preset and
Maintenance Preset as described above.
For example choose Operator Preset - and choose one of the available presets.
The chosen preset dialog box appears.
Right Click on the line with the parameter, where a change should be made.
The Edit Preset dialog box appears. Set the change with the up and down buttons
and press the Transmit button. The change is done.
The Edit Preset dialog box disappears after approximately 60 seconds or it can be
closed manually.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 28
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
7.13. Maintenance
The maintenance display is accessible directly from the HMI main menu. The
contents of all holding registers and holding bits can be viewed from here. The
contents cannot be changed here, it only displays values.
7.14. Logging
7.14.1. General
HMI logging features are accessible directly from the main menu. Here are several
logging options.
Note: To see the actual measured value, you can use the standard HMI trending
feature. This chapter describes how to record measured data and events and save
them to the disk as a file.
• Save presets to file - when chosen, a save file dialog box appears. Enter
the path and new filename. All actual presets (operator and maintenance)
will be saved into this file filename.csv.
• Save all registers to file - when chosen, a save file dialog box appears.
Enter the path and new filename. The contents of all HR registers will be
saved into the desired file.
• Analog data logging - a more complex logging feature which allows the
user to gather a number of data items using automatic or manual
triggering. Sample rate of up to 100 per second is available. See section 8
for more detailed description of this feature.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 29
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The A50 is equipped with the Analog data logging (ADL) facility. This feature is
accessible from the windows HMI through the Logging menu item as shown in
figure 25.
The Analog Data Logging option allows up to four sets of recordings to be made.
Each set can contain up to eight recorded variables. Recorded data stored in the
A50 memory can be transferred to a file on the user's PC if required. Each sample
of the recorded data is 2 bytes wide and the total memory available for recordings is
32kB.
Recording options can be configured. Data already stored in the A50 memory is
lost when the logging configuration is changed.
Log
This is a drop down list that allows the user to select a particular recording from a
number of recordings that might have been stored in the A50 memory. The number
of recordings to be taken is configured through the 'Analog Logging Wizard'. This
drop down list automatically adjusts itself according to the entry made in the former.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 30
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Status
This indicates the current status of the data logger in obtaining the required
information. There are four stages that the logger goes through, these are:
• Priming – this is when the logger is configuring the A50 and collecting a buffer of
information to use once the trigger has been activated.
• Ready To Record – this appears once priming has finished. The logger is waiting
for user input or an automatic trigger to begin logging the data.
• Recording Complete – the logger has collected all the data and the chart is
displayed in the window.
Abort Recording
This button is enabled during the last 2 of the above statuses; it will cancel the
logger’s current task and display the data acquired up to that point.
Send Trigger
This is a manual trigger which activates the data recording. It is usually used if no
automatic trigger has been selected.
Show Grid
This toggles the grid on and off in the graph area of the window. See 'Save' below.
Load
Loads any previously saved data.
Save
Saves the displayed data as a ‘*.tnd’ file.
Save Config
Saves the current configuration information as *.adld. This can be used for future
testing.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 31
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Export
Allows the data to be exported with a ‘csv’ extension for viewing using other
products such as MS Excel.
Plot Settings
Allows the colour of the individual plots to be changed (See Figure 26). Select the
plot you wish to alter in the ‘select variable’ drop down menu, then edit the colour in
the ‘Plot Colour’ subsection of the window. It is also possible to alter the plot scaling
in the ‘Plot Scaling’ subsection of the window; the default setting is auto.
Note: After sending new recording configuration to the A50, all previously stored data
records will be lost.
Before proceeding, ensure that the A50 is connected and is communicating with the
HMI.
This feature is a simple way to use the analog data logger. All of the data loggers
features are available through here.
The analog logging wizard comprises of 5 steps.
When the analog logging wizard is selected the first of five steps, shown in Figure
27, is loaded.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 32
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
In this step the user is given the choice of either creating a new logging
configuration or to use a previously stored configuration.
If ‘Create a new logging configuration’ is selected and the ‘Next >’ button is clicked,
step 2 is loaded.
The analogue logging wizard step 2 allows the user to select variables to be
recorded. Any combination can be selected as required. Also an automatic trigger
can be selected in this window. This is shown in Figure 28.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 33
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
When the automatic trigger selected here goes from False to True, it activates data
recording. Data recording stops when the ‘sample count after’, specified in step 4,
is reached. The total recording comprises of a number of samples before and a
number of samples after the trigger as specified by ‘Before points’ and ‘After points’
respectively.
This step allows the user to select one of the two modes of the analog data logging
as shown in Figure 29. Either a single mode or a multiple mode is possible. The
single mode is designed for testing purposes only and does not allow partitioning of
the buffer for multiple logs. When a trigger is applied the logging stops. To record
another log, the buffer has to be reset using the button provided and a new trigger
has to be sent.
In cyclic mode, the logging buffer is subdivided to allow two, three or four data logs.
It allows manual and automatic triggering. Breaker status changing from closed to
open is available as an automatic trigger in firmware. Data is stored cyclically, i.e.
first log 1 is triggered, then log 2 and then log 3 and then log 4. After this log 1 is
overwritten and then log 2 and then so on. At any given time the four most recently
triggered logs are available.
In this step the sample time, number of buffers, total capture time and amount of
data to be captured before and after trigger point are set. Figure 30 shows the
window where Step 4 is configured. Below is a description of the various sections
contained within the window.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 34
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
This section of the step 4 window allows the user to set the ‘Sample Time’ which is
the rate at which data points are logged in A50 memory. A slider bar is provided to
change the ‘Sample Time’, or a value can be entered directly. Also, number of
buffers can be set. This dictates how many sub-sections the A50 data-logging
memory is to be divided. The minimum setting is one and the maximum is four (in
single mode only 1 can be selected here, in cyclic mode a setting between 2 and 4
is allowed). The recording contained in each sub-section can be downloaded and
viewed on the HMI.
There are also two information windows here which display the following:
1) Maximum no. of samples that can be stored - This term is self explanatory. It
displays the maximum number of samples per data logging buffer that can be
stored.
2) No of samples that will be recorded - this location displays the actual number of
samples that will be stored depending on the logging configuration that is set.
This sub section allows the user to select the ‘Total Capture Time’ and to set the
ratio of the amount of data to be captured before and after the trigger is issued.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 35
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The total capture time is set in the window of the same name. There are four
buttons ‘<<’, ‘<’, ‘>’ and ‘>>’ that can be used to set the capture time or it is also
possible to directly enter a value by pressing the ‘…’ button.
A movable slider bar is provided to set the ratio of the number of data to be
captured before trigger point to the number of data to be captured after the trigger
point. Also three buttons ‘25%’, ‘50%’ and ‘75%’ are provided to set the ratio to
these pre-set values.
Also present in this section are four displays ‘before points’, ‘after points’, ‘before
time’ and ‘after time’. As their names suggest these display either the length of time
or the number of data points that will be stored before and after the trigger.
Here the plot settings can be adjusted to manually set the data logger plot. When
this is done and the 'Send' button is pressed, a window appears which confirms that
the configuration has been sent (see Figure 32:).
This step allows the user to save the configuration for later use. If this option is
selected, the user is allowed to select a filename and a path where the file is to be
stored. Once this has been done, the file can be used later by selecting ‘choose
previously saved configuration’ in step 1 (section 8.2.1). Pushing the 'Close...'
button completes the analog data logging configuration. The logger then primes
itself according to the configuration, and sits waiting for a trigger.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 36
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 37
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
In normal “on-load” operation the generator terminal voltage regulation loop has the
characteristics of a Proportional and Integral (PI) regulator. In no-load running of
the generator and during operation of supervisory regulation (automatic
synchroniser, reactive power regulation, power factor regulation), the transfer
function has only the proportional characteristic.
The purpose of the above mentioned facilities is to secure stable operation of the
generator within limits given by the capability diagram of the generator and
respecting a certain time-limited overload.
When the generator breaker is closed and the regulator is operating in normal PI
control mode, the control loop operates on the difference between the reference
voltage setting and actual value of generator terminal voltage corrected by the
reactive power compensation and output signals of all limiters (see section 9.5) and
power system stabiliser processed in the PI regulator with the transfer function:
KA
KA +
s ⋅ TA
The output voltage limiter is located on the output of the PI (or P) voltage regulator.
There are two levels of the limitation adjusting according to the kind of failure which
initialised this limitation.
In the case of the excitation systems with exciter (ac, dc or brushless exciter) the
regulator is equipped with an internal loop of exciter excitation current, this loop has
a proportional regulation characteristic.
The AVR is also equipped with a derivative stabilizing feedback taken from the field
current, which is used especially in cases of brushless systems (feedback taken
from the exciter field current).
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 38
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
z120=0 … exciter
z120=1 … static
VT VR max
PI block
-
KA VR
VREF +
∑ KA +
+ sT A
- +
- + ∑ KB
Limiters VR min
Stab. FB block - Internal loop of
VST (PSS output) Field Current
sTF
KF Ife /If
1 + sTF
Load
Compensator
Q
K LC
* Regulation modes transfer coefficient C066 is used for smooth transfer between
modes of regulation (E.g. transfer from the voltage regulation to reactive power
regulation) or between regulators (i.e. between channels if available). In these
cases it is necessary to recalculate the setpoint of the currently controlled quantity
corresponding to the particular generator operating point to the setpoint of the
quantity which will be controlled after the transfer and at the same time maintaining
the generator operating point unchanged. The value of the constant C066 is given
by variable r37 that can be read by the HMI or Excel debugger.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 39
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The actual generator terminal voltage value (program variable Vt) reaches, at the
nominal voltage, the value Vt=100 [%]. The actual generator terminal voltage is
corrected by a signal proportional to reactive power (program variable Q). This
correction signal expressed in % is called reactive power compensation (or QCC or
load compensation). Positive compensation increases generator terminal voltage
when reactive power is rising, negative compensation decreases it.
UT
G
3~
Ek [%]
G – Synchronous generator
UT – Unit transformer
Ek – Unit transformer short-circuit voltage
10% positive
100 Reactive power
Compensation compensation
-5 % final load
Final Characteristic characteristic
80 Voltage drop EK=-15%
Voltage drop of
Unit Transformer
60
Vt [ % ]
40
20
0 20 40 60 80 100
0
Q[%]
Figure 34: Reactive power compensation example
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 40
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
Desig. Param. Value Max Min Table C30 H Reg.
Vt setpoint slew rate
C080 2000 1 40081
[0.1%/s]
Vt setpoint lower limit| - no 40082
C081 100 1
load [%]
Vt setpoint upper limit| - no 40083
C082 150 80
load [%]
Vt setpoint lower limit| - on 40084
C083 100 80
load [%]
Vt setpoint upper limit| - on 40085
C084 110 90
load [%]
Vt setpoint - Field flashing 40086
C085 100 20
[%]
Vt setpoint slew rate| - Field 40087
C086 10000 500
flashing [0.01%/s]
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 41
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
q - axis
Uc j xq It
Ut
It d - axis
0
Figure 35: Derivation of Generator Voltages & Current
The regulator is equipped with two types of power system stabilisers for increasing
stability and damping of rotor oscillations during generator transition states.
The first type of built-in PSS is PSS3B type according the IEEE 412.5 standard with
the additional field current branch. As input quantities to the PSS, the following are
used:
• Frequency of generator terminal voltage fE (or compensated frequency fC)
• Generator active power P
• Generator field current If
„1” - if P>Pmax
„0“ - if P<Pmin
Input filter Phase Gain
P 1 sT2
K S1
1 + sT1 1 + sT2
If 1 sT6
1 + sT5 1 + sT6 KS3
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 42
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
The second type of built-in PSS is a PSS2A type according the IEEE 412.5
standard. As input quantities to the PSS, the following are used compensated
frequency fC and the generator active power P.
This advanced dual input PSS type utilizes the calculation of integral of accelerating
power method.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 43
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
fC V1 V3 V4
sTw1 sTw2 1 1 + sT8
N
∑ 1 ∑
1 + sTw1 1 + sTw2 1 + sT6 M
(1 + sT9 )
+ +
+ _
K S3
P sTw3 sTw4 Ks 2 V2
1
1 + sTw3 1 + sTw4 1 + sT7
V6 V V8
STM
1 VST
V5 1 + sT3 1 + sT10
1 + sT1 KS4
K S1 1 Π
1 + sT2 1 + sT4 1 + sT5
-VSTM V7
P < 0.8*C188
/f-fnom. / < 2%
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 44
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Where:
fC compensated frequency, frequency of internal generator
voltage
KS1, KS2, KS3, KS4 stabiliser gain
M, N grade of torsional filter
P active electric power
T1, T3, T10 phase lead time constant
T2, T4, T5 phase lag time constant
T6,T7 low pass filter time constant
T8,T9 torsional filter time constants
Tw1,Tw2,Tw3,Tw4 washout time constant
V1,V2,V3,V4,V5,V6 power system stabiliser internal variables (accessible for
tests)
VST power system stabiliser output
VSTM,-VSTM power system stabiliser output limit
Adjustable parameters:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 45
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Integral parts of the PSS2A are diagnostics and control logic modules.
The diagnostic block includes sensor diagnostics and PSS output diagnostics.
When a failure is detected, the PSS status output is changed and the PSS input
into the AVR is disconnected.
• Minimum active power Pmin(C188) – specifies the level of active generator
power for automatic PSS switch ON, below this level the PSS is OFF.
• PSS output diagnostic – evaluates the output from the PSS2A stabilizer.
When the ERROR LEVEL (C190) of the PSS output is overridden for a
time higher than the DELAY (C189) of the PSS output diagnostic, failure is
detected and output of the PSS to the AVR is disconnected.
• Time Ramps for soft switch ON / OFF – to provide soft switch ON/OFF, the
PSS output signal is multiplied by the signal from ramp function, that
increase from 0 to 1 during ton(C191) in the case of PSS switch ON
respectively from 1 to 0 during toff(C192) in the case of PSS switch OFF,
see Fig. 37.
dω 1
= (Pm − Pe ) = 1 Pa
dt 2H 2H
Equation 1
where:
Pm [pu] - mechanical power
Pe [pu] - electrical power
Pa [pu] - accelerating power
H [MWs/MVA] - constant of inertia
ω [rad/s] - angular speed of rotor
p m (s ) p e (s ) s 2 Hω (s )
= +
1 + s2H 1 + s2H 1 + s2H
Equation 2
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 46
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
ω s2H
1 + s2H
+
Pm
∑
Pe + 1 + s2H
1
1 + s2 H
The actual signal of mechanical power obtained in this way can contain
disturbances caused by low frequency torsional oscillation. In order to eliminate
them, the mechanical power signal is passed through a ramp-tracking filter that
dampens oscillations on frequencies higher than approximately 4Hz. The
corresponding block diagram is shown in Figure 39.
ω s2H
1 + s2H
+ N
1 + sT8 Pm
∑
(1 + sT9 ) 1 + s2H
M
Pe 1 +
1 + s2 H
Pe
After subtracting the signal in accordance with Equation 1 and Equation 2
1+ s 2 H
Pa
we obtain accelerating power , that is suitable to dampen oscillations (See
1+ s 2 H
Figure 40).
ω s2H
1 + s2H
+ N +
1 + sT8 Pa
∑ M
∑
Pe 1 + (1 + sT9 ) -
1+ s 2 H
1 + s2 H
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 47
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
In a practical power system stabiliser derivations of power and speed are used
instead of actual power and speed. This is to damp oscillations but not to influence
control. Deviations are realized by inserting of the washout filters with the transfer
sTw
function
1 + sTw that eliminate the dc components in both input signals. Phase
shift of the output signal proportional to the accelerating power must be
compensated for phase lag through generator, excitation and power system by two
or three stages lead - lag filters with transfer function (1+sTi) / (1+sTj). The final
structure of the power system stabiliser conforming to IEEE Std. 421.5-1992 is
shown in Figure 37.
9.5. Limiters
AVR
summing
junction
P, Q, If, lim. ref. UEL
block +
Σ
V/f, lim. ref. to AVR PI
V/Hz
- block
limiter
It, lim. ref.
SCL
-
block
Vt, lim. ref.
Vt
-
limiter
Note: All of the limiters exhibit hysteresis with a ‘dead band’ of 2%. This means,
for example, that if the limit alarm is switched on by a signal reaching 105%, it
will remain on until the signal drops below 103%.
The limiter is carried out as integral regulator with time delay dependent on the
current increase over the set limit Ifm on condition If < IfM according to the relation:
Tz If 2
Tf = ∫ − 1 dt
0
Ifm
where:
Ifm maximum continuous value of field current (limiter delayed action)
IfM maximum actual value of field current (limiter immediate action)
If actual value of field current
Tz time of the limiter intervention delay (depends on actual rotor current values)
Tf limiter constant which expresses the time of the limiter intervention delay
when value of field current If=141% Ifm was reached
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 48
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
If the rotor current limit Ifm is exceeded, the delay circuit starts timing and after the
time delay TZ given by the current overloading height, the limiter decreases current
to the set value Ifm.
If the rotor current rises above the level of IfM (IfM > Ifm), the limiter decreases
current to the set value IfM without any delay, at the same time the delay circuit
starts to work and after the delay time passes the rotor current is further decreased
to the limit Ifm.
Delay block
Tz 2
If
Tf = ∫ −1 dt
0
Ifm
„1” - if delay>= Tz or
If >I fM
„0“ - if delay < Tz
and If < I fM Integrator
0.5 p.u.
0
If + 1
∑
1 sTRCL inverted
- polarity to
AVR
0 summing
If REF
junction
if (If >= IfM & delay < TZ) then If REF = IfM
if (If >= Ifm & delay > TZ) then If REF = Ifm
The rotor current limiter has the possibility of applying temperature correction of the
continuous rotor current limit level Ifm. Temperature correcting coefficient C140
[0.01%/ºC] is specified in the FCONST.txt file. The function of temperature
correction is selected by setting z215 in USER.plc file.
Adjustable parameters:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 49
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Tz
It 2
Tt = ∫ − 1 dt
0
Itm
where:
Itm maximum continuous value of stator current (delayed limiter action)
ItM maximum actual value of stator current (immediate limiter action)
It actual value of stator current
Tz time of the limiter intervention delay (depends on actual stator current
values)
Tt limiter constant which expresses the time of the limiter intervention delay
when value of stator current It = 141% Itm was reached
Itn nominal terminal current
If the stator current limit Itm is exceeded, the delay circuit starts timing and after the
time delay TZ given by the current overloading height, the limiter decreases the
current to the set value Itm.
If the stator current rises above the level of ItM (ItM > Itm), the limiter decreases the
current to the set value ItM without any delay, at the same time the delay circuit
starts to work and after the delay time passes the rotor current is further decreased
to the limit Itm.
Stator current limiter’s action is different in the lagging and leading areas of
capability diagram. The excitation is reduced in the lagging area and excitation is
increased in leading area. If the value of active current exceeds the stator current
limit, the limiter keeps the operating point of the generator at unity power factor
(minimum achievable value of stator current, when excitation regulator is in
operation).
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 50
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Delay block
Tz
It 2
Tt = ∫ −1dt
Itm
0
„1” - if delay>= Tz
or It >I tM
„0“ - if delay < Tz
and It < ItM
0.5 p.u.
0
It + +
1 1
∑ Q>0
1 sTSCL
- -
inverted
It REF - 0.5 p.u. *(-1) polarity to
0 AVR
if (It >= ItM & delay < TZ) then It REF = ItM Integrator polarity summing
if (It >= Itm & delay > TZ) then It REF = Itm inversion junction
Adjusted parameters:
Desig. Param. Value Max Min Table C43 H Reg.
Itm Continuous stator current 40143
C142 15000 10000
limit [0.01%]
ItM Max. terminal current - no 40144
C143 30000 10000
delay [0.01%]
Tt Delay at 141% limit exceed 40145
C144 500 1
[s]
C145 10000 1 Inverse timing coefficient 40146
TSCL C146 5000 1 Integral time constant [ms] 40147
Temp. correction at -20º C 40148
C147 2000 1000
[0.001]
Temp. correction at 60ºC 40149
C148 1000 500
[0.001]
Temp. at Rating point 40150
C149 599 -199
[0.1 ºC]
Temp. At Breaking Point 40151
C150 599 -199
[0.1 ºC]
The stator current limiter has the possibility of applying temperature correction of
continuous stator current limit level Itm. The maximum continuous stator current limit
at +15ºC is set by parameter C142. For other temperatures it is possible to use a
correction temperature-time curve, see figure below. This curve is defined by four
points, (C147, C148, C149, C150). Calculation of the actual stator current limit as
adjusted by the correcting coefficient rDF is given below:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 51
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
rDF
C147
1300
1200
1100
1000
900
C148
800
700
C150 C149
-20 0 20 +60 [ºC]
Correction of the continuous stator current limit level Itm as a function of terminal
voltage is possible in order to maintain the apparent power Sn of the generator
when voltage is changing. Maximum continuous stator current limit Itm is corrected
indirectly to changes of the generator terminal voltage.
The voltage range of where the correction is applied is +/- 5% of the rated terminal
voltage. The voltage correction of stator current limiter is enabled by setting z213 in
USER.plc file.
P0
Q Q0 Q1 0
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 52
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Preset values P0 , Q0 , Q1 are used to draw a vertical line through Q1 and a sloping
line between P0 and Q0. The intersection of these two lines define UE limit. These
points are set in relative units of apparent power. Stabilising feedback from the
generator (exciter) field current is used when active power is greater than the
preset Pmax and this stabilizing signal is switched off if active power is less than the
preset Pmin.
„1” - if P>Pmax
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 53
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Note: If the Generator is being used in the pumping mode, then the second limit
UEL2 is used and this is set using presets C119, C120 and C121.
The V/Hz limiter is implemented as an integral regulator. Its action is delayed. The
delay depends on the actual value V/Hz at a given time as compared to the overflux
limit setting (V/Hz)m as shown in the following relationship:
Tz
V / Hz
TV / Hz = 10 ⋅ ∫ − 1dt
0
(V / Hz ) m
where:
When the limit (V/Hz )m is exceeded and when time delay TZ is spent the V/Hz
limiter operates. It decreases excitation to bring the actual V/Hz ratio within the
allowed limit.
Delay block
Tz
V / Hz
TV / Hz =10∫ −1dt
0
(V / Hz)m
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 54
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Integrator
0.5 p.u.
VT + 1
∑
sTTVL inverted
- polarity to
AVR
Vtm 0 summing
junction
Adjustable parameters:
The term superior regulation is used when the action of a certain module is to
adjust the voltage reference as opposed to going into the summing junction of the
AVR.
The voltage equaliser is created by the differential circuit which evaluates the
deviation between the generator terminal voltage and the network voltage. This
deviation then affects the change of the generator terminal voltage reference
setting. The trend of the generator reference setting change depends on the height
of the equaliser control deviation, when the absolute value of the deviation is bigger
than 5 %, VREF setting changes with constant trend otherwise depends on the
integral of equaliser control deviation.
„1” - if |∆V|> 5 %
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 55
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
The VAr and PF control loop are superior to the basic voltage control loop. During
PF and VAr control the voltage control loop is in P regulation and the VAr/PF
control loop is operating as an integral controller. VAr or PF deviation affects the
voltage reference setting through the action of the VAr/PF controller – see Figure
51. The operating range of Vref (r00) is limited by C083 (lower limit) and C084
(upper limit).An adjustment to these limits is made to account for the fact that the
voltage control loop is in P control mode and not in PI mode when PF/VAr control is
active. Reaching the lower Vref limit is indicated by setting flag z117 and reaching
the upper limit is indicated by setting flag z114. In the event that the limits of the
capability diagram are exceeded then Vref adjustments in the relevant direction are
disabled (and flag z10D is set) and Vref is adjusted to bring the operating point in a
safe area within the capability diagram limits – see Figure 50 below. The safe
operating area for PF/VAr controller is defined by variable r143 which is set to 3%
from the actual limits.
r143
r143
-Q 0 +Q
In this mode of regulation the deviation between the required and the actual value
of reactive power is evaluated and a correction of the generator terminal voltage
reference setting is made (also taking consideration of the limiters). It is used
particularly during operational shut-down of the generator, when regulation to Q=0
is selected.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 56
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Limiters
activity
Integrator
+
+ ∆QM
Q - VAr/PF 1
∑ corrector sT VREF setting
+ increment /
- ∆QM - decrement
QREF
The power factor regulator works similarly to the VAr regulator. In this case a
reactive power reference is derived from the power factor reference setting
adjusted by the operator.
Limiters
activity
Integrator
+
+ ∆QM
Q - VAr/PF 1
∑ corrector sT VREF setting
+ increment /
- ∆QM -
decrement
QREF
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 57
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
There are two options available for field current control; field current regulation
mode and manual restrictive mode. The user logic can be set to determine which
mode of operation is used when manual mode (current control mode If or Ife) is
selected. This is implemented by the setting of flag z214, which is activated by a
digital input (see 9.7.2 Manual Restrictive Mode)
The field current regulator is P type. When operating in field current (If) control
mode, the regulation loop has its own reference setting of the field current (IfeRef),
which is controlled by the "RAISE" and "LOWER" commands.
When switching to field current control mode a bumpless transfer occurs whereby
IfeRef takes the value of the actual exciter field current (Ife) at the time of the transfer.
+VR max
If - VR
∑ KB
+
- VR min
If REF
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 58
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
Note: Field current proportional gain KB = C060 – see section 9.1 table C22
This feature is only fully functional if “Manual Restrictive Mode” is NOT ENABLED
(see section 9.7.2 for description of ‘Manual Restrictive Mode’).
If the generator is loaded and voltage sensing failure occurs (e.g. loss of terminal
voltage feedback, z055 = 1) then the AVR transfers regulation from the “terminal
voltage regulation under load” mode (j01 = 5) to the “field current (If or Ife)
regulation under load” mode (j01 = 14). In this case, active power P and reactive
power Q are not known.
The operating point of the generator in terms of the capability diagram is then
derived from the field current (If or Ife). The operating point of the generator is
limited by controlling the field current reference value – see Figure 54.
The maximum field current reference r20 (If_ref) or r40 (Ife_ref) is limited to the
rated field current (through variable r28 or r48 – curve 2-2 in Figure 54) – the value
of rated field current has no specific preset (no Cxx type variable) it is assumed as
simply 1 p.u.
The minimum field current reference is limited to the field current value IF1 (preset
C041) required to achieve cosφ = 1 when Pn and Vtn = 1 (through variable r27 or
r47 – curve 1-1 in Figure 54).
The minimum attainable value of the field current reference is chosen to provide
some clearance from the UEL. Under these conditions, after sensing failure, the
operating point of the generator is transferred from point X to point Y – see Figure
54.
Under special circumstances the curve 1-1 could be shifted more to the
underexcitation area by decreasing of the preset IF1 (C041) but this is not
recommended for normal practice.
If the operating point of the generator is situated inside of the area determined by
curves 1 and 2, then transfer to the field current regulation loop is smooth.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 59
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
2
1
X Y
B A
1 2
Manual Restrictive Mode (MRM) is an optional field current regulation mode for use
when the unit is on the network. This mode is available in addition to the
functionality described in 9.7.1. If the MRM is enabled, the minimum field current
reference (curve 1-1 in Figure 54) as described above in 9.7.1 is no longer present.
However, the maximum field current reference (curve 2-2 in Figure 54) is still
present (see Figure 55) and will still limit the operating point accordingly. This mode
is also intended to prevent the generator from being underexcited during the field
current regulation mode when the generator is on the network.
The selection of manual control with MRM is activated by a digital input which sets
flag z214 and transfers the regulation to the state st01=14 (field current regulation
on the network). A set point C123 is used to denote (exciter) field current desired
when P = 0 pu. A second set point C124 is used to denote (exciter) field current
desired when P = 1 pu. A linear interpolation of (exciter) field current Ife=f(P) based
on these two set points is then carried out to give a line (MRM line – see Figure 55).
The working point of the generator (if more leading than MRM setting of UEL) is
moved to a safe area (to the right of the MRM line).
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 60
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
Desig. Param. Value Max Min H Reg.
MRM integral time constant 40123
C122 100 1
[sec]
f_MRM_0 - Field Current at 40124
C123 5000 100
P=0, 100 = 1 % Ifen
If_MRM_Pn - Field Current 40125
C124 10000 1000
at P=1 p.u. , 100 = 1 % Ifen
C124 ∼ P=1
P
P=Sn=1
2
Pn
Ifemax=85A
-Q 2 +Q
C123 ∼ P=0, Ifemin=8,5A
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 61
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Adjustable parameters:
Note: Values for manual control are in reference to regulator output – for maximum
control rectifier output +32000 (control angle 0°, set number 320), for inverter run -
32000 (control angle 180°, set number -320).
The monitor is only used in twin A50 systems. The ‘Monitor’ always runs in the
standby AVR. The monitor is designed to operate when the generator operating
point deviates outside of the AVR limiters (see Figure 56). The monitor setpoints
need to be outside the envelope of the limiters. Only when the limiters fail to control
the generator to the required limits does the monitor activate. The monitor initiates
a smooth transfer from the main AVR to the standby AVR when this occurs.
Returning operation back to the main AVR is possible through the use of the
“monitor reset” function – flag z12F, after fault clearing. To identify the cause of the
fault the relevant flags (z133, z135, z137, z13A, z13C) remain active until the
monitor is reset.
Conditions to enable the Monitor (z13E=1) and Monitor Reset are defined in the
USER.plc file.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 62
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
OEM
C239
UEM
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 63
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
This function evaluates loss of terminal voltage feedback and short circuit condition.
This diagnostic is disabled if Dual VT Loss of Sensing Detection is enabled. See
Fout! Verwijzingsbron niet gevonden..
Activation of the diagnostics is selected by the value of C067 in FCONST.txt as
follows:
This feature can detect if an incident is feedback failure or a short circuit. In case of
a short circuit the control needs to continue in the same AVR but it should operate
with the ceiling voltage.
The next excitation set behaviour depends on the selection of time constants C058,
C059 as follows:
C058 < C059 - after a period specified in C058 expires, the AVR transfers control
to field current regulation (Rif / Rife) and after the period specified in C059 expires
control is transferred to the terminal voltage regulation loop (Rut) in the standby
AVR (see Figure 57 below).
failure
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 64
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
C058 > C059 - after a period specified in C059 expires, control is transferred to the
standby AVR terminal voltage regulator (RUt) (see Figure 58 below)
C058
failure
If this feature is enabled then the standard loss of sensing feature is disabled (see
section 9.7.1).
This feature is enabled in the user logic by setting the flag z1E8. If this flag is set to
0, normal or no diagnostic is active. According to the FCONST and user logic
setting if a sensing failure is evaluated and transfer to field current regulation
needed – the regulation will be transferred to manual control with MRM (see section
9.7.2) or normal manual regulation mode (see sections 9.7 and 9.7.1).
This special diagnostic evaluates only voltage measurement (no current
measurement is taken into account) but in a more sophisticated way. This
diagnostic can be used in a twin channel system and requires use of the network
voltage sensing input and the equaliser voltage sensing inputs. It requires a cross
connection of the voltage measurement signals between the two channels in the
following way:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 65
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
The 3 phase voltage sensing wires (coming to A-X4:1, A-X4:2, A-X4:3) should be
split and fused in channel A, let’s name these fused branches UA, VA, WA and
connected to the channel B voltage sensing inputs as follows:
UA connected to B-X4:10, VA connected to B-X4:11 and B-X4:12, WA connected
to B-X4:13.
The 3 phase voltage sensing wires (coming to B-X4:1, B-X4:2, B-X4:3) should be
split and fused in channel B, let’s name these fused branches UB, VB, WB and
connected to the channel A voltage sensing inputs as follows:
UB connected to A-X4:10, VB connected to A-X4:11 and A-X4:12, WB connected
to A-X4:13.
Let’s name the 3 phase voltage sensing in the active channel VT1 (control VT) and
the additional sensing (coming from the stand-by or following channel) into the
active channel VT2 (checking VT).
All terminal voltage, network voltage and voltage for equalizer voltage
sensing inputs in both channels should be correctly calibrated (set proper
scaling factors ) otherwise there will be measurement misalignment resulting
in incorrect functioning!
Sensing Failure will raise Action Flag B03_sens_RI after a delay specified in
preset C058 (usually 50 ms). This causes control to transfer to Ife mode in the
same channel. Then Action Flag B03_sens_R2 is raised after a delay specified in
preset C059 (usually 100ms), which causes control to transfer to the standby
channel if possible.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 66
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Delays in C058 of 50ms and C059 of 100ms are preferred as this sets Ife control in
the same channel 50ms after detection of Voltage Sensing Error followed by
transfer to standby channel in voltage control mode a further 50ms later. Transfer
to standby channel is subject to the standby being available and it being in a better
condition than the main channel.
It is possible to alter the behaviour of the AVR by setting times C058 and C059
differently.
If sensing failure occurs during soft start then excitation will switch to the standby
channel if it is healthy, otherwise Ife control is selected on the same channel and
(exciter) field current reference will continue to ramp up until (exciter) field current
reaches the adjustable preset IF0 (C040). IF0 is set to the level required to achieve
full speed no load excitation. The operator can then investigate the cause of VT
Failure and take appropriate action. The excitation will not revert to auto without
operator intervention.
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 67
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
9.11. Synchronization
The computations of the main synchroniser are carried out in processor ST1. ST1
is accessed via X08 connector. The parameters for the main synchroniser can be
found in FCONST.txt file under X08.
The computations for the check synchroniser are, however, carried out in processor
ST2. ST2 is accessed through port X11. The parameters for check synchroniser
can be found in FCONST.txt file under X11.
The following parameters are common (in table “comm.”) for all synchronising
points:
- C212 - maximal permissible slip limit
- C213 - maximal permissible difference between net and generator voltage
- C215 - pulse length factor for speed setting commands
- C211 - pulse length factor for terminal voltage setting commands
Adjustable parameters:
main synchroniser, X08 connector
x = 1 to 4 - number of
paralleling
points
C036 43 0 y = 0 – Synchronizing
disabled
= 1 - Synchronizing
downwards
= 2 - Synchronizing
upwards
= 3 – Synchronizing
in both cases 2+3
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 68
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Synchr.
Param. Value Max Min Table C50 H Reg.
point
SP1 Network voltage sensor 40155
C154 1500 700
scaling factor [0.001]
Generator terminal voltage 40159
SP1 C158 1500 700 sensor scaling factor
[0.001]
Synchr.
Param. Value Max Min Table C70 H Reg.
point
comm. Length of voltage control 40212
C211 1000 0
pulse [ms]
comm. Maximal allowed slip value 40213
C212 400 0
[0.01%]
comm. Maximal terminal and net 40214
C213 400 0
volts difference [0.01%]
SP1 closure time coefficient of 40215
C214 1000 0
CB [ms]
comm. Length of speed control 40216
C215 1000 0
pulse [ms]
SP1 Terminal and line volts 40217
C216 +180 -180
phase shift correction [º]
Generator terminal voltage 40218
C217 1500 700
SP2 sensor scaling factor [0.001]
SP2 Network voltage sensor 40219
C218 1500 700
scaling factor [0.001]
SP2 closure time coefficient of 40220
C219 1000 0
CB [ms]
SP2 Terminal and line volts 40221
C220 +180 -180
phase shift correction [º]
Synchr.
Param. Value Max Min Table C71 H Reg.
point
Generator terminal voltage 40222
C221 1500 700
SP3 sensor scaling factor [0.001]
SP3 Network voltage sensor 40223
C222 1500 700
scaling factor [0.001]
SP3 closure time coefficient of 40224
C223 1000 0
CB [ms]
SP3 Terminal and line volts 40225
C224 +180 -180
phase shift correction [º]
Generator terminal voltage 40226
SP4 C225 1500 700 sensor scaling factor
[0.001]
SP4 Network voltage sensor 40227
C226 1500 700
scaling factor [0.001]
SP4 closure time coefficient of 40228
C227 1000 0
CB [ms]
SP4 Terminal and line volts 40229
C228 +180 -180
phase shift correction [º]
Adjustable parameters:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 69
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Synchr.
Param. Value Max Min H Reg.
point
Generator terminal voltage
C020 1500 700
SP1 sensor scaling factor [0.001]
SP1 Network voltage sensor
C021 1500 700
scaling factor [0.001]
SP1 Terminal and line volts
C022 +180 -180
phase shift correction [º]
SP1 closure time coefficient of
C023 1000 0
CB [ms]
Generator terminal voltage
SP2 C025 1500 700 sensor scaling factor
[0.001]
SP2 Network voltage sensor
C026 1500 700
scaling factor [0.001]
SP2 Terminal and line volts
C027 +180 -180
phase shift correction [º]
SP2 closure time coefficient of
C028 1000 0
CB [ms]
Generator terminal voltage
C030 1500 700
SP3 sensor scaling factor [0.001]
SP3 Network voltage sensor
C031 1500 700
scaling factor [0.001]
SP3 Terminal and line volts
C032 +180 -180
phase shift correction [º]
SP3 closure time coefficient of
C033 1000 0
CB [ms]
Generator terminal voltage
C035 1500 700
SP4 sensor scaling factor [0.001]
SP4 Network voltage sensor
C036 1500 700
scaling factor [0.001]
SP4 Terminal and line volts
C037 +180 -180
phase shift correction [º]
SP4 closure time coefficient of
C038 1000 0
CB [ms]
This function is used where several generators are being operated in parallel and it
is required to adjust the operating set point Vref of all the AVR’s simultaneously.
The input is a varied signal from 30% to 100% of 110V AC. This signal is
connected to X4:12,13 of the AVR PRISMIC A50 and it will adjust the generator
voltage by +/- 10%. Zero adjustment occurring at the level C242 [0.01%] of input
voltage (in our case 65% of 110V AC / C242=6500) and the gain C242[0.01%]
should be calculated like this – C241 = 10000*Vref biasing range[%] / input varied
signal range[%] - (in our case C241=10000*20 / 70 = 2857).
Adjustable parameters:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 70
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Prismic A50 software includes a rotating rectifier fault diagnostic module. This
module is optional and can be activated in the case of brushless excitation
systems. This module evaluates the contents of third harmonic frequency in exciter
field current. Specific ripple containing third harmonic (150 Hz – 50 Hz systems,
180 Hz – 60 Hz systems) is typical in case of rotating rectifier failure.
Adjustable parameters:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 71
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 72
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
X08 connector:
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 73
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 74
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 75
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 76
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 77
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 78
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 79
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.
ELP4R1_Y
X11 connector:
Note: These parameters should be set only through FCONST file.
Synchr.
Param. Value Max Min H Reg.
point
Generator terminal voltage
C020 1500 700
SP1 sensor scaling factor [0.001]
Network voltage sensor
SP1 C021 1500 700
scaling factor [0.001]
Terminal and line volts
SP1 C022 +180 -180
phase shift correction [º]
closure time coefficient of
SP1 C023 1000 0
CB [ms]
Generator terminal voltage
C025 1500 700 sensor scaling factor
SP2
[0.001]
Network voltage sensor
SP2 C026 1500 700
scaling factor [0.001]
Terminal and line volts
SP2 C027 +180 -180
phase shift correction [º]
closure time coefficient of
SP2 C028 1000 0
CB [ms]
Generator terminal voltage
C030 1500 700
SP3 sensor scaling factor [0.001]
Network voltage sensor
SP3 C031 1500 700
scaling factor [0.001]
Terminal and line volts
SP3 C032 +180 -180
phase shift correction [º]
closure time coefficient of
SP3 C033 1000 0
CB [ms]
Generator terminal voltage
C035 1500 700
SP4 sensor scaling factor [0.001]
Network voltage sensor
SP4 C036 1500 700
scaling factor [0.001]
Terminal and line volts
SP4 C037 +180 -180
phase shift correction [º]
closure time coefficient of
SP4 C038 1000 0
CB [ms]
Higher level
Title: INSTRUCTION MANUAL BRUSH SEM s.r.o.
assignment:
PRISMIC A50
EXCITATION CONTROLLER Sheets / Sheet
(ODE PROJECT)
EG407720(A)/B 80 / 80
ALL RIGHTS TO THIS DOCUMENT BELONG EXCLUSIVELY TO BRUSH SEM s.r.o.. THIS DOCUMENT MUST NOT BE COPIED,
DUPLICATED OR OTHERWISE COMMUNICATED TO A THIRD PARTY WITHOUT PERMISSION OF THIS COMPANY.