INSTRUCTION SHEET

ERICO DYNASPHERE MKIV


®

Installation Instructions for 4.6m FRP Cantilevered Mast


Terminal Elevation: 3.6m Above Structure

ERICORE Downconductor
ERICO DYNASPHERE ERICORE Downconductor
(ERICO® Part # D/SMKIV-SS) Saddle
(ERICO Part # CONSAD/E2)
Saddle Mounting Screws
(ERICO Part # CONSADFX)
ERICORE Downconductor
with factory-fitted 3
upper termination -
2 Typical ERICORE Mount
-
Not to Scale

1.57 [39.9mm]
4.6m FRP Support Mast 2 Holes,0.43[ 10.9mm]
(ERICO Part # FRP4.6MBLACK)

Mast Support Bracket 3.54 [89.9mm]


(ERICO Part # ALOF1GS)
4.72 [119.9mm]

3 Typical Upper Termination End View


-
Not to Scale
1 Typical ALOF1GS Wall Bracket Base
3.3 FT [1M] -
Not to Scale

1
-
Detail "A" Lightning Event Counter
(ERICO Part # LECIV)
ERICORE Downconductor
Crow's Foot
ERICO® CADWELD®
Minimum 2/0 (50 mm ) Conductor
2 Connection or
(3 x 20 FT [6.1M] length) mechanical connection
2 Enclosed in GEM material Ground Inspection Well
-
Lightning Event Counter
Refer to installation manual
For complete for alternate locations
(ERICO Part # LECIV)
grounding system
refer to Detail "A"

Minimum 5/8" x 8' [16mm x 2.4M] long


Suggested three radial grounding system for each downconductor: ground rod in four locations

The grounding system shown in the detail is a suggested layout. Each radial consists of a trench
approximately 1.5FT [.45M] deep. The conductor is laid in the trench and is connected to ground
rods. The conductor in each trench is encased in GEM material. Ground rods must extend 10FT [3M]
below ground level.
Note: This is one of several alternative installation methods.
Refer to ERICO instruction print IP79157 for more details.
ERICO is not responsible for field installation of lightning protection systems. The installation
integrity of each system should be approved and stamped by a structural professional engineer.
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.