Professional Documents
Culture Documents
California RMP ARB Leak Check Report Form
California RMP ARB Leak Check Report Form
Inputinformationat www.arb.ca.gov/rmpͲr3
*Thisworksheetisforcompanyuseonly.DONOTRETURNTOARB.*
CompanyName: TechnicianName:
FacilityName: TechnicianCertificateType:
TechnicianCertificateNumber:
SystemID(asreportedinR3):
LeakDetection AmountRefrigerant AmountRefrigerant PurposeofAddedor
DateofService TypeofService LeakDetected
Method Added(lbs) Removed(lbs) RemovedCharge
LeakInspection Bubbletest InitialCharge
LeakRepair Yes Leakdetectiondevice Leakrepair
RoutineService No Electronic/Ultrasonic ToppingOff
Other_________________ Other_________________ Other_________________
Ifaleakwasdetected,fillouttheinformationbelow.
Descriptionofleakrepair:
Continueonbackifnecessary.
Leakinspectionsmustbeconductedatleastonceevery90daysperRule95385(b)forany
refrigerationsystemwithanoperatingchargeof200ormorepoundsbutlessthan2000pounds,and
atleastannuallyforanysystemwithanoperationchargebetween50and200poundsperRule
95385(c),unlessthesystemismonitoredbyanAutomaticLeakDetectiondevice(ALD).Additional
requirementsapplytoallhighͲGWPHVAC/Rsystemsincludingleakrepairwithin14days.Complete
RMPRuleisavailableathttp://arb.ca.gov/rmp