FM200 Hydraulic Calculations of Server Room
FM200 Hydraulic Calculations of Server Room
00 (NAF S 227)
UL: EX6264
Consolidated Report
Customer Information
Company Name:
Address:
Phone:
Contact:
Title:
Project Data
Project Name:
Designer:
Number:
Account:
Location:
Description:
Enclosure Report
Page: 1 of 11
Consolidated Report
Minimum: 7,00 % Total Volume: 75,00 m ³
Min. Agent Required: 41,24 kg
Adjusted Agent Required: 41,47 kg
Page: 2 of 11
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40TF 15 mm 5,70 m 3 0 0 0
40TF 25 mm 5,80 m 3 0 1 0
Other
Objects Name Quantity Part Number
FLEX HOSE 25 mm MODULAR - 45 Bend 1 SH30502140
Page: 3 of 11
Consolidated Report
Enclosure Number: 1
Enclosure Name: ROOM
Minimum Design Concentration: 7,00%
Adjusted Design Concentration: 7,04%
Predicted Concentration: 7,01%
Maximum Expected Agent Concentration: 7,01% (At 20,0 C)
Enclosure Number: 2
Enclosure Name: RAISED FLOOR
Minimum Design Concentration: 7,00%
Adjusted Design Concentration: 7,04%
Predicted Concentration: 7,27%
Maximum Expected Agent Concentration: 7,27% (At 20,0 C)
Page: 4 of 11
Consolidated Report