Professional Documents
Culture Documents
24 Electrical Power
24 Electrical Power
A330
TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2
ELECTRICAL POWER
This document must be used for training purposes only
ELECTRICAL POWER
Electrical Power System Presentation (1) . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL
Electrical System General Description (3) . . . . . . . . . . . . . . . . . . . . . 42
AC GENERATION
Main AC Generation D/O (3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Auxiliary AC Generation D/O (3) . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Emergency AC Generation D/O (3) . . . . . . . . . . . . . . . . . . . . . . . . . 100
Contactors Management D/O (3) . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
LOAD DISTRIBUTION
Load Management D/O (3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
G4R06501 - G37T0DG
CLASSIC A330 ----> ENHANCED A330 - T1+T2 TABLE OF CONTENTS Dec 21, 2006
24 - ELECTRICAL POWER Page 1
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 2
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
GENERAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 3
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 4
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 5
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 6
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 7
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 8
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
AC GENERATION - EMERGENCY
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 9
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 10
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 11
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 12
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 13
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 14
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 15
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 16
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 17
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 18
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 19
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 20
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 21
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 22
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 23
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 24
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 25
A330 TECHNICAL TRAINING MANUAL
LOAD MANAGEMENT
The ECMUs have protective functions, which become active in case of
a power source overload, they carry out a preprogrammed shedding of
some loads (galleys, service sub-busbars...). For A340-500 and A340-600,
due to a high number of galleys, an ELMU is installed and achieves this
shedding task.
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 26
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 27
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 28
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 29
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 30
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 31
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 32
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 33
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 34
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 35
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
COMPONENT LOCATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 36
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 37
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 38
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
MAINTENANCE/TEST FACILITIES
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 39
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 40
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24P2000000001
SAFETY PRECAUTIONS
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL POWER SYSTEM PRESENTATION (1) Dec 21, 2006
24 - ELECTRICAL POWER Page 41
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 42
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
ELECTRICAL GENERATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 43
A330 TECHNICAL TRAINING MANUAL
AC ESSENTIAL SUPPLY
In normal configuration, the AC ESS BUS is supplied from AC BUS
1. If AC BUS 1 fails, there is an automatic switching of the supply to
AC BUS 2. The AC ESS BUS switching can also be performed
manually in the flight deck. Other sources of supply for the AC ESS
BUS are the EMER GEN, or the STAT INV.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 44
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 45
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 46
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 47
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 48
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 49
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 50
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 51
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 52
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
NORMAL CONFIGURATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 53
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 54
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
NBPT FUNCTION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 55
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 56
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
SUPPLY PRIORITY
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 57
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 58
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
EMERGENCY CONFIGURATION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 59
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 60
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DC000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 61
A330 TECHNICAL TRAINING MANUAL
CONTROL AND MANAGEMENT - GENERATOR CONTROL UNIT (GCU) ... CIRCUIT BREAKER MONITORING UNIT (CBMU)
CLASSIC A330 ----> ENHANCED A330 - T1+T2 ELECTRICAL SYSTEM GENERAL DESCRIPTION (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 63
A330 TECHNICAL TRAINING MANUAL
(PMG), an exciter generator with rotating diodes and a main GEN. FEEDER LINE
The CSD of the IDG converts the variable input speed (4900 to 9120
A 3 phase generator feeder cable and neutral connects the generator
RPM), provided by the engine gearbox, into a constant output speed
terminal block to a terminal block located on the upper engine structure
(24000 RPM).
(disconnection for engine change). The neutral line is grounded to the
GENERATOR CONTROL UNIT engine structure.
Each IDG is controlled and monitored by its own GCU. All the GCUs Another terminal block, located in the pylon, splits each phase into
are fully identical and interchangeable. two feeder cables (parallel feeders), sent through the wing leading
The GCU performs the following main functions: edges and the cargo compartment to rack 710 VU in the avionics
- control, monitoring and protection of the IDG (GEN and CSD),- compartment. The parallel feeders are connected to the GLC after
regulation of the GEN voltage,
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 64
A330 TECHNICAL TRAINING MANUAL
having passed through a 6-hole Current Transformer (CT) used for
protection monitoring.
The feeder lines and the GEN are monitored and protected for
differential current conditions and open cable conditions.
ECMU
The GLC is under control of the related GCU and ECMU. If all
parameters are correct, the GLC connects the generator to its own
busbar.
The ECMUs receive relative IDG information via the GCUs.
Each ECMU monitors the status of its own side contactors (ECMU
1 for LH side and ECMU 2 for RH side) and ensures the opening or
closing of the contactors according to the priority logic and the NBPT
operation (on ground only).
G4R06501 - G37T0DG - FM24D1000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 65
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 66
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 67
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 68
A330 TECHNICAL TRAINING MANUAL
IDG OIL PRESSURE Eight minutes after engine shutdown, the GCU initiates an oil level
The oil pressure is monitored by a Low Oil Pressure (LOP) switch interrogation sequence. Then the sequence is generated every six
located in the IDG charge oil circuit. minutes. In the case of oil low level detection, the GCU sends a status
The LOP switch provides a signal to the GCU when IDG charge oil message to the ECAM.
pressure is less than 140 PSI (9.65 bars). A visual check of the oil level sight glass is required. Oil servicing is
In LOP condition, that is not caused by under-speed, the IDG P/B performed according to the oil level determined by the oil level sight
FAULT legend comes on amber and an ECAM warning IDG 1(2) glass level indication colors (red, yellow, green).
OIL LO PR is triggered.
The IDG scavenge oil filter is fitted with a Differential Pressure
Indicator (DPI), which indicates a clogged filter condition. The switch
is located across the scavenge filter and associated to a pop-out
indicator located on the IDG filter housing.
In the case of a clogged filter, the DPI sends a signal to the GCU,
which, in turn, sends a status message to the ECAM.
A visual check of the pop-out is required.
If the DPI is popped out, both filters (inlet and outlet) and oil must be
removed, inspected and replaced according to Aircraft Maintenance
Manual (AMM) procedures.
The DPI device is automatically inhibited during cold oil running
conditions (under-speed), due to high oil viscosity.
IDG OIL LEVEL
The GCU includes a Remote Oil Level Sensor (ROLS) function that
enables to know the IDG oil level status. Four minutes after engine
G4R06501 - G37T0DG - FM24D1000000003
NOTE: In case of low oil level detection, the GCU generates a LOW
OIL LEVEL message to the Central Maintenance Computer
(CMC) via the GPCU.
A message is displayed on ground on the status page of the
ECAM system display to inform the crew.
The ROLS sensor is located in the IDG.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 69
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
INTEGRATED DRIVE GENERATOR OPERATION - IDG CONTROL P/B ... IDG OIL LEVEL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 70
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 71
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 72
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
IDG OIL COOLING SYSTEM AND DISCONNECTION MECHANISM - SPEED CONTROL LOOP & IDG DISCONNECTION MECHANISM
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 73
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
IDG OIL COOLING SYSTEM AND DISCONNECTION MECHANISM - SPEED CONTROL LOOP & IDG DISCONNECTION MECHANISM
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 74
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 75
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 76
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 77
A330 TECHNICAL TRAINING MANUAL
and regulation control module, where it is converted into DC voltage The differential protection is based on the comparison of each phase
and applied to the exciter field. of the line 6 hole CTs and the GEN CTs in the IDG.
The voltage frequency regulation module senses the average of the If the difference of current is above 50 +/- 10 A for at least 60
three phases at the POR and compares it against a reference voltage. milliseconds, the PRR and GCR are tripped.
If a difference exists, the voltage regulator adjusts the exciter field The differential protection circuit reset is done via the GEN P/B and
current as needed to keep a constant voltage at the POR. this protection can be reset twice.
UNDER-SPEED After 2 reset attempts, the GCU must be powered down (cold start)
to reset the protection latch-in software.
Pin programming activates the underspeed set point. The Engine
Interface and Vibration Monitoring Unit (EIVMU) provides ENG
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 78
A330 TECHNICAL TRAINING MANUAL
OVERLOAD AND OVERCURRENT
The IDG (GEN) CTs provide current sensing information to the GCU.
In case of overload or over-current, the corresponding GCU protection
circuits are triggered.
If the overload is still present 10 seconds after this initialization, the
GCU only sends a signal to ECMUs to shed the corresponding galley.
No tripping occurs.
The automatic shedding is performed by ECMUs, and no ECAM
warning is triggered.
If the automatic shedding is not performed, the ECAM is triggered
and the FAULT legend on the GALLEY P/B comes on.
The crew has to press the GALLEY P/B to manually shed the galley
load to reduce the generator load.
If an over-current is detected, after the inverted protection time delay,
the Bus Tie Contactor (BTC) is locked in OPEN position.
If the fault persists, the GEN is de-energized (via the GCR) and the
GLC is opened (via the PRR).
INADVERTENT PARALLEL TRIP
The power supply logic to each AC main bus bar is established through
the ECMU control system.
Furthermore, the NBPT allows two AC sources to be connected
momentarily during the transfer phase.
After transfer completion, a special protection in the ECMU and GCU
G4R06501 - G37T0DG - FM24D1000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 79
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D1000000003
MAIN AC ELECTRICAL SYSTEM OPERATION - CONTROL AND PROTECTION ... FIRE PROTECTION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 80
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 MAIN AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 81
A330 TECHNICAL TRAINING MANUAL
APU GENERATOR source (A and B) to monitor the quality of the power supply.
The APU generator can supply all or part of the normal network, APU GEN AND EXTERNAL POWER CONTROL P/BSW's
depending on the priority logic of the network supply. The APU GENerator P/BSW and the two EXT PWR (A and B)
The APU generator is a two pole high speed (24000 RPM) brushless P/BSWs are located on the overhead ELECtrical panel and have 2
spray oil cooled generator. Speed regulation is made by the APU stable operating positions.
(there is no Constant Speed Drive (CSD)); therefore, it operates in When selected ON (EXT PWR A, Not "OFF" for APU GEN and
the same manner but it is not interchangeable with the Integrated Drive AUTO for EXT PWR B), they enable the GAPCU to control, monitor
Generators (IDGs). and connect the APU GEN and the external power sources to the
aircraft network.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 82
A330 TECHNICAL TRAINING MANUAL
A manual deselection of the APU GEN switch de-energizes and
disconnects the APU GEN and resets the APU GEN control part in
the GAPCU.
A manual deselection of the EXT PWR switch disconnects the GPU
from the A/C network.
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 83
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
DESCRIPTION - GAPCU ... APU GEN AND EXTERNAL POWER CONTROL P/BSW'S
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 84
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 85
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 86
A330 TECHNICAL TRAINING MANUAL
If the APU GEN is in overload condition, the GAPCU informs the - communication and interface.
ECMU which sheds the GALLEY and indicates the information in The diagram shows the connection for External Power A.
the cockpit. MONITORING:
APU GEN CONTROL BOARD The GAPCU permanently monitors the quality of the delivered ground
FUNCTIONS: power.
At least one faulty parameter automatically disconnects the ground
The GAPCU also controls, monitors and protects the APU generator
power from the transfer line (EPRR and EPC open).
supply to the network.
The interlock system is also activated (Interlock Monitoring Relay
It ensures the following main functions:
(IMR) open) and the GPU is electrically disconnected from the aircraft.
- control of the field excitation through the Generator Control Relay
The IMR enables a holding supply to be connected to the GPU line
(GCR),
contactor.
- voltage regulation,
It is not possible to connect a faulty power source to the network.
- control of the AGLC through the PRR in conjunction with the
ECMU1, INTERLOCK:
- control and protection of the APU generator and the network. The conditions for the IMR to be closed are:
APU ECB ensures the speed regulation. At 95 % RPM, the ECB - the 28 VDC control voltage from the GPU is within accepted limits
provides an APU ready signal to the control part of the GAPCU. (<42 VDC and <13 VAC),
AGLC CONTROL AND MONITORING: - the delivered power quality, sensed at a Point Of Regulation (POR),
The AGLC connects the APU GEN to the Transfer Circuit. It is is accepted by the Control and Protection Module.
controlled and monitored by the GAPCU and the ECMU 1. The The closed IMR connects 28 VDC via pin F to the GPU.
position of the AGLC is monitored by the FAULT legend on the APU This interlock voltage acts as a holding supply for the GPU output
GEN P/BSW. contactor.
If the control voltage is not within the limits, the IMR opens to
EXT PWR CONTROL BOARD
electrically disconnect the GPU and sends a signal to the valid external
G4R06501 - G37T0DG - FM24D2000000002
FUNCTIONS: power interlock module to open the EPRR (EPC will open).
The GAPCU controls and monitors EXT PWR contactors and relays. The closed IMR status is also sent to the valid EXT PWR (Valid EP)
When EXT PWR A and/or B are connected, the GAPCU performs interlock circuit which will close the EPRR, provided the quality of
the following functions: the power voltage is accepted by the control and protection module.
- monitoring, For EXT PWR A, the green legend AVAIL illuminates.
- interlock function, For EXT PWR B, the green legend AVAIL illuminates.
- EPC control, EXTERNAL POWER CONTACTOR CONTROL:
- protection function,
The closed EPRR provides 28 VDC to the solenoid of the EPC.
- FRU function for NBPT,
As soon as the EXT PWR P/BSW is pressed, the ECMUs are notified
- BITE function,
that an external power is ready to be involved in an NBPT.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 87
A330 TECHNICAL TRAINING MANUAL
For EXT PWR A, the blue legend ON illuminates. If the overload condition persists for an additional 2 seconds, after
For EXT PWR B, the blue legend AUTO illuminates. the load shedding action by the ECMUs (galley switch FAULT legend
PROTECTION: on), the ECAM warnings are triggered and the message EXT PWR
A (or B) OVERLOAD appears.
The GAPCU has to be powered to allow APU or EXT PWR sources All galley loads must be shed by setting the galley P/B to OFF. The
to be connected to the aircraft electrical network. message GALLEY OFF appears.
In case of a total GAPCU power supply failure, the BATTERY BUS If after galley shedding an overload is still detected, the overcurrent
will ensure the necessary supply to the GAPCU. protection will be triggered after an inverse time delay: the IMR and
The GAPCU has a BACK UP module which contains software, in EPRR are tripped.
the case the GAPCU main operating software fails. The BACK UP
module operates on the EXT PWR A side (board) in order to recover OVERCURRENT:
the availability of EXT PWR A. The BACK UP module is, in this The internal CT senses the overcurrent (OC).
case, supplied by the HOT BUS. An overcurrent condition exists when the current on any one phase
OVERVOLTAGE: exceeds 277 A.
Once an overcurrent situation is sensed, the GAPCU relays the
Overvoltage (OV) protection is accomplished by monitoring the information to the ECMU as network status information.
highest phase at POR.
An OV condition exists when the highest phase voltage exceeds
130+/-1,5 VAC for at least 50 ms.
After an inverse time delay, the IMR and EPRR are tripped.
UNDERVOLTAGE:
Undervoltage (UV) is sensed in the same way as overvoltage.
An undervoltage condition exists when the lowest phase voltage is
less than 101,5+/-1,5 VAC.
G4R06501 - G37T0DG - FM24D2000000002
After a 4,5 second time delay max, the EPRR and the IMR are tripped.
OVERLOAD:
The internal CT senses the overload.
An Overload condition exists when the current is greater than 260+
-15 A on any phase for 10 seconds max.
The galley-shed relay sends a signal to the ECMUs and to the galley
P/BSW.
The ECMUs reply by shedding galley loads, depending on the supply
configuration faults.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 88
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 89
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 90
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 91
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 92
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 93
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 94
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 95
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 96
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 97
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 98
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D2000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 AUXILIARY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 99
A330 TECHNICAL TRAINING MANUAL
to the DC ESS network. If the automatic control fails, the CSM/G can be manually started by
depressing the momentary MANual ON P/BSW located on the
CONTROL AND LOGIC EMERgency ELECtrical PoWeR panel on panel 211VU. When
CSM/G is manually started, it has priority over on the other main AC
The CSM/G can be started manually or automatically. The supply logic sources (GENs, APU GEN...) on the AC and DC ESS network.
differs according to the CSM/G supply and the aircraft configuration.
AUTOMATIC CONTROL
The CSM/G is automatically started when the two main AC buses are
lost. As soon as AC main busbars are lost (contactor 3XC / AC
ESSential Bus Switching Contactor is de-energized), the start up
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 100
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 101
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 102
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 103
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 104
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 105
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 106
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 107
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 108
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 109
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 110
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 111
A330 TECHNICAL TRAINING MANUAL
In EMER configuration (AC buses not available), the STAT INV parallel to the STAT INV and also to the DC ESS BUS.
operates automatically in the following cases: The STAT INV parameters have to be checked on the ECAM AC
- when the CSM/G is not available (at slat extension with RAT ELEC page.
extended) and the aircraft speed above 50 Kts,
- at landing with aircraft speed lower than 50 Kts and both BAT1 and
BAT2 P/BSW's pressed in and CSM/G not available.
MONITORING
The parameters (400 Hz and 115 V) of the STAT INV are displayed
on the ECAM ELEC AC page. The STAT INV is monitored for:
- fan failure,
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 112
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 113
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 114
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 115
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 116
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 117
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 118
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 119
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 120
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D3000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 EMERGENCY AC GENERATION D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 121
A330 TECHNICAL TRAINING MANUAL
Manual control of the galley RCCBs is achieved via the GALLEY P/BSW
(1XA on 235VU) and COMMERCIAL P/BSW (22XN on 235VU).
Manual control of the flight/ground buses (service buses) RCCBs is
achieved via the COMMERCIAL P/BSW (22XN on 235VU).
The DC BUSES status is monitored by the ECMUs to automatically
control the DC BUS CONTACTORS 1 and 2, to ensure supply of the
DC BUSES.
The ECMS authorizes and supervises the No Break Power Transfer
(NBPT) function to momentarily connect two AC power sources in
parallel to create a power transfer with no power transients (bus power
interruption). This function is only available on ground.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 122
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
GENERAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 123
A330 TECHNICAL TRAINING MANUAL
ECMU1 controls the left hand side of the electrical network and the
GROUND CONTROL LOGIC SIC while ECMU 2 controls the right hand side.
The ECMUs interface with Air Data / Inertial Reference Unit 1 The BUS TIE P/B should be in auto position for normal system
(ADIRU 1) and 3, and Landing Gear Control and Interface Unit 1 operation.
(LGCIU 1). In this position, the SIC and the four BTCs are automatically controlled
LGCIU 1 provides the ground/flight information to both ECMUs. according to the AC power sources available.
ADIRU 1 provides the "less than 50 Kts" speed signal to ECMU1 The five contactors open or close according to the priority logic in
while ADIRU 3 provides the same signal to ECMU 2. This information order to supply the whole AC network.
is used for the NBPT function when the aircraft is on ground and for In the off position, the OFF legend on the BUS TIE P/B comes on.
inhibition of manual BITE functions in flight. In this case, the SIC and the two BTCs (four BTCs for A340) are
permanently open.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 124
A330 TECHNICAL TRAINING MANUAL
With the BUS TIE P/B selected off, the message "ELEC BUS TIE BITE
OFF" is displayed on the ECAM. Each ECMU has one ARINC 429 data link output that permits
monitoring data to be sent to the System Data Acquisition
CAUTION: Caution: In the case of BUS TIE P/B in OFF position, Concentrators (SDACs) 1 and 2 for display on the ECAM, and the
no external or APU power is possible. BITE data to Central Maintenance Computer (CMC) 1 and 2. The
DC CONTACTOR CONTROL ECMU communicates to the CMCs in two modes:
Both ECMUs receive DC contactor status. The DC contactor status - the first (normal mode) is a power-up test and fault monitoring /
is to ensure a correct supply of the DC bus bars when an AC supply fault recording,
connection occurs, according to AC power supply logic. - the second mode (interactive mode) is only possible on ground via
ECMU 1 receives: the MCDU for a manual test activation and fault display access.
- status of Transformer Rectifier 2 (TR 2) for fault and over current Each ECMU continually monitors its inputs, outputs and internal
detection. The acquisition of the TR 2 fault and Over current detection functions to determine if a failure condition exists. Failure information
is to provide DC bus power transfer with a TR 2 failure or NOT to will be stored in the internal Non-Volatile Memory (NVM) and also
allow DC bus power transfer if TR 2 is failed due to an over current, sent to the CMCs.
- 28 VDC from TR 1 to supply DC BUS 1, 2 and BAT BUS (BUS 3)
through (1PC1 - 28VDC BUS 1/BUS 3 SuPpLY CoNTactOR and
1PC2 - 28VDC BUS 2/BUS 3 SPLY CNTOR) DC BUS power transfer
control logic,
- voltage from 101PP (DC BUS 1 sub-bus bar). It is used to indicate
DC BUS 1 is supplied.
ECMU 2 receives:
- status of TR 1 for fault and over current detection. The acquisition
of the TR 1 fault and over current detection is to provide DC bus
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 125
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 126
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 127
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 129
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 130
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 131
A330 TECHNICAL TRAINING MANUAL
same two sub buses (AC BUS 2 sub buses for A330, AC BUS 2-4
sub buses for A340) supplied by 6XN2 and 7XN2. These are alternate
RCCB service bus supplies (1XX, 2XX, 3XX, 4XX) and are used
when only ground service from EXT PWR A is selected (used) on
the aircraft.
ECMU 2 acquires the position of the MAINT BUS selector switch
(16XX on 5001VE) and electro-magnetically holds the MAINT BUS
selector switch in the ON position.
ECMU 2 monitors the normal TR 2 supply contactor 2PU.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 132
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 133
A330 TECHNICAL TRAINING MANUAL
- unknown, if neither open nor closed position can be confirmed in corresponding optional equipment is not installed. If one of these C/Bs
case of failure. is detected not pulled, a maintenance message is sent to the CMCs.
CIRCUIT BREAKER IDENTIFICATION CBMU DATA BASE
The CBMU contains in a NVM, the aircraft circuit breaker database The Multipurpose Disk Drive Unit (MDDU - 1TD) is used only on
containing the data about all the monitored C/Bs and RCCBs. the ground to perform the up-loading of the C/B database in the CBMU
The identification of open C/Bs and/or RCCBs is made by designation, by means of a floppy disk.
panel position and FIN. The open circuit breaker information is viewed
on the ECAM C/B page by selecting the C/B P/BSW on the ECAM NOTE: Note: The C/B database is customized for each aircraft.
Control Panel. An ARINC bus 429 enables the automatic transfer between the MDDU
(1TD) and the CBMU via the Data Loading Routing Box (DLRB -
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 134
A330 TECHNICAL TRAINING MANUAL
102TD) when the Data Loading Selector (DLS -101TD) is selected
to CBMU.
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 135
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
CIRCUIT BREAKER MONITORING DESCRIPTION: CBMU - CIRCUIT BREAKERS STATUS ... CBMU DATA BASE
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 136
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 137
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 139
A330 TECHNICAL TRAINING MANUAL
as the reference for synchronization, only on the ground. The FRU - S2: indicating the end of the NBPT function,
AC reference priority is determined by the AC power source
configuration and may or may not be the same reference sent to the From the GAPCU to GCU:
left side of the network or to the right side of the network. - FRU: indicating the FRU change signal, once the APU GEN is
- FRU priority: connected to the network,
- EXT PWR A, From the GAPCU to Electronic Control Box (ECB):
- EXT PWR B,
- APU RAMP: signal (ARINC 429) to "ramp" the APU shaft speed
- APU GEN,
up or down for phase alignment purposes.
- Master 400HZ reference.
FROM THE ECMU TO GAPCU AND GCU: From the ECB to GAPCU:
- S2: indicating the end of the NBPT function. - APU READY: signal when the APU speed is greater than 95%.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 140
A330 TECHNICAL TRAINING MANUAL
NOTE: Note: The APU READY signal is performed once APU
speed is greater than 95 %.
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 141
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 142
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 143
A330 TECHNICAL TRAINING MANUAL
and when they are within accepted limits, it sends the "D" signal to adjustment. The FRU for the LH side of the aircraft changes from
both ECMUs. EXT PWR B frequency to the APU GEN frequency.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 144
A330 TECHNICAL TRAINING MANUAL
The APU GEN supplies the LH side. As long as the APU MASTER
P/B is ON, the APU GEN remains valid for an NBPT function. When
it is set to OFF the GAPCU receives a discrete "shutdown" signal.
Prior to APU shutdown (or APU MASTER P/B to OFF) the GAPCU
will:
- remove the "D" signal to the ECMUs indicating that the APU GEN
is being shutdown and NBPT is requested,
- issue the frequency change request signal (S4) to the FRU (the FRU
switches reference to EXT PWR B and provides this signal to the LH
side GCU).
When the APU GEN control part receives the frequency reference
signal (EXT PWR B) from the FRU, it generates the RAMP signal
to the ECB. If the frequency reference signal is within the limits of
390 to 410 Hz, the ECB adjusts the APU speed. The speed adjustment
rate and direction depends on the difference between the reference
frequency (FRU) of EXT PWR B and APU GEN.
When the APU GEN frequency and phase angle are within limits of
the frequency reference signal, the S1 signal is sent to the ECMUs
indicating that the APU GEN is ready to be momentarily placed in
parallel with the EXT PWR B source. Upon EXT PWR B connected
to A/C network, the paralleling function is terminated; APU GEN is
removed from the network.
After a short time delay, ECMU 1 opens the APU GLC and EXT
PWR B supplies the LH side. If no other power sources (EXT PWR
G4R06501 - G37T0DG - FM24D4000000003
A or IDG) are connected to the RH side, ECMU 1 closes the SIC and
EXT PWR B also supplies the RH side network.
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 145
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
NBPT OPERATION - A/C CONFIGURATION ... APU GEN / EXT PWR B NBPT SHUTDOWN
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 146
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 147
A330 TECHNICAL TRAINING MANUAL
NBPT OPERATION - GEN 1 / APU GEN NBPT STARTING ... BTC FAILURE
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 149
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
NBPT OPERATION - GEN 1 / APU GEN NBPT STARTING ... BTC FAILURE
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 150
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 151
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 152
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24D4000000003
ABNORMAL OPERATION - ECMU CLASS 2 FAILURE ... GAPCU RESET AFTER NBPT INHIBITION
CLASSIC A330 ----> ENHANCED A330 - T1+T2 CONTACTORS MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 153
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 154
A330 TECHNICAL TRAINING MANUAL
LOAD RESTORATION
A manual reset (contactor function of a RCCB) can be performed
through the RESET P/BSW located on the front face of ECMU or
through an ECMU test using the CMS or using the GALLEY P/BSW
(for galley and sub-busbar RCCBs) by cycling the GALLEY P/BSW
to OFF then back to AUTO. When a RCCB opens automatically after
an overload detection (circuit breaker tripping function), it is possible
to reset the RCCB by manually pushing the corresponding RCCB
RESET P/B, located on the front face of the RCCB. The circuit breaker
tripping function is indicated on the RCCB by the RESET P/BSW
released (out position) and the visual indication on the RCCB indicates
OPEN.
G4R06501 - G37T0DG - FM24DB000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 155
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DB000000002
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 156
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 157
A330 TECHNICAL TRAINING MANUAL
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 158
A330 TECHNICAL TRAINING MANUAL
G4R06501 - G37T0DG - FM24DB000000002
GENERAL - INDICATING
CLASSIC A330 ----> ENHANCED A330 - T1+T2 LOAD MANAGEMENT D/O (3) Dec 21, 2006
24 - ELECTRICAL POWER Page 159
AIRBUS S.A.S.
31707 BLAGNAC cedex, FRANCE
STM
REFERENCE G4R06501
DECEMBER 2006
PRINTED IN FRANCE
AIRBUS S.A.S. 2006
ALL RIGHTS RESERVED