Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PG-2V500

2 Volt 525 A.H.


UPS / TELECOM BATTERY

FEATURES PRODUCT
Long Service Life
Thick plate design and efficient gas recombination yield a service
life expectancy of 15 years in standby mode.

Low Internal Resistance


Superb high-rate discharge characteristics ensure reliable
performance in UPS and Telecom applications.

Maintenance-Free, Non-Spillable
Proven VRLA technology guarantees safe operation without
maintenance and 'non-restricted article' status for transportation.

Low Self-Discharge
Lead-calcium alloy grids and use of high purity lead account for
superior shelf-life characteristics permitting storage for extended
periods of time.

Designed-In Reliability
Cutting-edge manufacturing and process control combined with
meticulous quality assurance procedures guarantee consistent
and dependable performance.

SPECIFICATIONS
Nominal Voltage 2 Volt (1 cell)
Nominal Capacity
20-hr. rate ( 28.4A to 1.80V ) 568.0AH
10-hr. rate ( 52.5A to 1.80V ) 525.0AH
5-hr. rate ( 91.9A to 1.75V ) 459.5AH
3-hr. rate (139.1A to 1.75V ) 417.3AH
1-hr. rate ( 341.3A to 1.60V ) 341.3AH
Approximate Weight 68.4 lbs. (31.0 kg)
Energy Density ( 10-hr. rate ) 1.21 W-hrs/in3 (74.27 W-hrs/l)
Specific Energy ( 10-hr. rate ) 14.62 W-hrs/lb (32.26 W-hrs/kg)
Internal Resistance 0.3 millohms
5-min. Discharge Current to 1.60V/cell 1500 A
Terminals threaded insert w. 8 mm stud fastener
Shelf Life — ( % of nominal capacity at 68° F (20° C) )
1 Month 97%
3 Months 91%
6 Months 83%
Operating Temperature Range
Charge -4°F (-20°C) to 122°F (50°C)
Discharge -4°F (-20°C) to 140°F (60°C)
Case Material ABS plastic
TECHNICAL DETAIL: PG-2V500

CONSTANT POWER DISCHARGE RATINGS

WATTS PER CELL @ 25°C


Model Final
5 min 10 min 15 min 20 min 30 min 45 min 60 min
1.80V 1730 1492 1315 1055 984 715 581
1.75V 1950 1594 1415 1290 1037 775 580
PG-2V500
1.67V 2036 1769 1576 1352 1049 762 614
1.60V 2490 1928 1601 1342 951 755 642

PERFORMANCE CHARACTERISTICS SELF-DISCHARGE & STORAGE

Discharge Time vs. Discharge Current 100 Charging is not


necessary unless

Capacity Retention Ratio (%)


100% of capacity
10 is required.
80
9 5ºC Charging before
use is necessary
(41ºF) to help recover
8 full capacity.
7 60
(h)

Charging may fail


6 to restore full
40ºC 30ºC 20ºC
5 capacity. Do not
40 (104ºF) (86ºF) (68ºF) let batteries reach
4 this state.
0
Discharge Time

3
0 2 4 6 8 10 12 14 16 18 20
2
Standing Period (Months)
60
50
40
30
CHARGING
20
Cycle Applications: Limit initial current to 150A. Charge until battery voltage (under
(min)

10 40°C (104°F) charge) reaches 2.40 to 2.45 volts at 68°F (20°C). Hold at 2.40 to 2.45 volts until
6 25°C ( 77°F) current drops to approximately 5A (0.01C).
3 0°C ( 32°F) “Float” or “Stand-By” Service: Hold battery across constant voltage source of
2 2.25 to 2.30 volts continuously.

45 50 55 70 80 130 140 300 400 486 600 1200 1600


PHYSICAL DIMENSIONS
Discharge Current (A)
20mm

Discharge Characteristics M8
6.69 (170)

7mm

2.1

2.0

1.9
9.45 (240)
1.8
52.5A 28.4A
Voltage (V)

1.75
1.6 139.1A 91.9A
341.3A
1.3
Sealed Long Life
UPS/TELECOM BATTERY

500A
POWER-GUARD SERIES ®
12.99 (330)

13.78 (350)

PG-2V500
2 Volt 525 A.H.
@ 10-hr. rate to 1.80V

0
2 3 10 20 25 60 2 3 5 10 20
UST BE R
M
EC
TTERY

YCL ED

Power-Sonic Corporation Pb
BA

www.power-sonic.com NONSPILLABLE

(min) (h)

Discharge Time

SALES & MARKETING ISO 9001-2000 CUSTOMER SERVICE


3106 Spring Street 9163 Siempre Viva Road
Redwood City, CA 94063 USA FM39170 San Diego, CA 92154 USA
Tel: 650-364-5001 Fax: 650-366-3662 Tel: 619-661-2030 Fax: 619-661-3648
battery@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN THE U.S.A. 04/04 1M

You might also like