Typical Installation Instructions: E/One Sewers
Typical Installation Instructions: E/One Sewers
TYPICAL
INSTALLATION
INSTRUCTIONS
Environment One Grinder Pump Feature Identification
1. Grinder Pump Basin – High density polyethylene (HDPE)
3. Electrical Quick Disconnect (EQD) – Electrical lead from pump core terminates here
(NEMA 6P).
4. Power and Alarm Lead – Circuits to be installed in accordance with local codes.
5. Alarm Panel – Hose down proof (NEMA 4X) enclosure. Equipped with circuit breakers
or disconnect switch. Locate according to local codes.
6. Alarm Device – Every installation is to have an alarm device to alert the homeowner of a
potential malfunction. Visual devices should be placed in conspicuous locations.
7. Inlet – 4-inch PVC socket (4.5 inches ID). For solvent cementing DWV pipe.
9. Gravity Service Line – 4-inch DWV (4.5 inches OD). Supplied by others.
12. Concrete Anchor – Reference station detail sheet for correct ballast weight. Supplied
by others.
13. Bedding Material – 6-inch minimum depth, rounded aggregate (gravel). Supplied by
others.
14. Finished Grade – Grade line should be 2 inches below the cover and slope away from
the accessway.
15. Conduit – 1 ¼-inch PVC to burial depth required by local code. Supplied by others.
16. Elbow – 1 ¼-inch PVC. Required to attach tank electrical fitting to conduit. Supplied by
others (not shown).
17. Rebar – Required to lift tank after ballast has been attached (4 places, evenly spaced
around tank).
1
FAILURE TO COMPLY WITH
INSTALLATION INSTRUCTIONS
WILL VOID WARRANTY
3
Installation Instructions for Model 1010F Grinder Pump
The Environment One Grinder Place the unit on a 6-inch bed sleeve over the inlet prior to
Pump is a well-engineered, of gravel, naturally rounded pouring the cement.
reliable and proven product; aggregate, clean and free-
proper installation ensures flowing, with particle size no 3. Discharge
years of trouble-free service. less than 1/8 inch or more than Using 1 ¼-inch PVC (SCH-40)
The following instructions 3/4 inch in diameter. The pressure pipe or polyethylene
define the recommended concrete anchor is required to water service tubing (SDR-9,
procedure for installing the keep the unit from floating as a Type PE3206 or PE3306) with
Model 1010F Grinder Pump. result of high groundwater a minimum pressure rating of
The Model 1010F is a sewage- levels. The amount of concrete 160 psi is recommended. If
handling pump and must be required varies for each unit polyethylene pipe is chosen,
vented in accordance with local (see station detail sheet for the use compression-type fittings
plumbing codes. Do not install correct ballast weight). to provide a smooth inner
the unit in locations classified The unit should be leveled and passage (insert fittings are
as hazardous in accordance filled with water to the bottom susceptible to clogging).
with the National Electric Code, of the inlet; doing so prevents Environment One recommends
ANSI/NFPA 70. All piping and the unit from shifting when that a redundant check valve
electrical systems must be in pouring the cement. The be installed between the pump
compliance with applicable cement must be manually discharge and the street main
local and state codes. vibrated to eliminate any voids. on all installations. The valve is
If pouring the cement to a level to be installed as close to the
1. Remove Packing Material higher than the inlet piping is street as possible. Check local
Give the User Instructions to necessary, place an 8-inch codes for applicable require-
the homeowner. Hardware ments.
supplied with the unit, if re-
quired, will be used during
installation.
2. Tank Installation
The tank is supplied with a
standard 4-inch PVC DWV (4.5
inches inside dia.) inlet for
connecting the incoming sewer
drain. If a concrete ballast is
attached to the tank, lift only by
the lifting eyes embedded in
concrete. Do not drop, roll or
lay the tank on its side. Doing
so may damage the unit and
void the warranty. Excavate a
hole to a depth so the remov-
able cover extends 2 inches
above the finished grade line;
the grade should slope away
from the unit. The diameter of
the hole must be large enough
to allow a concrete anchor.
4
4. Vent Several methods of backfill are advantage since they typically
The station must be vented to available and each yields reach a compaction level of 90
a height above the expected favorable results when done to 95 percent standard density
maximum flood level. Using 2 properly. with minimal compaction.
inch PVC pipe, insert pipe into Clean, compact, native soil that Another option is flowable fill
the grommet near the top of is free from rocks, roots or (i.e., low slump concrete). This
the tank. Route pipe above organic material may be used if is particularly attractive when
flood level, ensuring the pipe compacted in lifts not to exceed installing grinder pump stations
always angles down towards one foot. It must be compacted in augered holes where tight
the station so no traps are to a final Proctor density clearances make it difficult to
created. Place a gooseneck at between 85 and 90 percent. assure proper backfilling and
the top of the vent to prevent Heavy, non-compactable clays compaction with dry materials.
rainwater and other foreign are not acceptable backfill for Flowable fills should not be
objects from entering the vent. this or any underground struc- dropped more than four feet
Failure to vent the station ture such as inlet or discharge from the discharge nozzle to
properly will prevent the station lines. the bottom of the hole since
from venting and will void the Class 1 or Class 2 backfill this can cause separation of
warranty. material as defined by ASTM the constituent materials.
2321 may also be used.
5. Backfill Requirements Crushed stone and gravel 6. Electrical Connection
Proper backfill is essential to backfill materials offer an (Supply Panel to Environment
the long-term reliability of any One Control Panel)
underground structure. Before proceeding, verify that
the service voltage is the same
as the motor voltage shown on
the nameplate. The required
alarm device must be installed
in a conspicuous location.
Wire the supply panel and
Environment One control panel
per Figures 2a and 2b, control
wiring diagrams, and local
codes.
7. Electrical Connection
(Pump to Panel)
The cable provided for connec-
tion between the station and
control panel is a six-conductor
tray cable that meets NEC
requirements for direct burial
as long as a minimum of 24
inches of cover is maintained.
Those portions of cable that
have less than 24 inches of
cover must be contained within
suitable conduit. This includes
the vertical section that drops
to a 24-inch depth at the
station and the length exiting
5
panel. Note: Wiring must be
installed in compliance with
local codes (which may vary
from above).
www.eone.com