Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Optyma™ Plus

OP-LPQM, OP-MPXM
Name plate

A OP-MPXM034MLP00G Q W
B 114X4261 The condensing unit must only be used for
MADE IN INDIA
Y Z its designed purpose(s) and within its scope of
C Application MBP IP 54 application.
D Refrigerant (1) R404A R507 R448A/R449A (2) R134a
R407A/R407F/R452A R513A
E M.W.P. HP (1) 28 bar (2) 23 bar R Under all circumstances, the EN378 (or
M.W.P. LP (1) 7 bar (2) 5 bar other applicable local safety regulation)
F Voltage 230 V ~ 1N ~ 50Hz X requirements must be fulfilled.
LRA 60 A MCC 19 A
OIL INSIDE POE 46
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
G Serial No. 123456CG2816
be connected as it is; refer to the «installation»
118UXXXXXX

Picture 1 : Minimum mounting distances


EAN No. xxxxxxxxxxxxxx section for further details.
Q: Air in R: Air out
Danfoss A/S, 6430 Nordborg, Denmark The condensing unit must be handled with cau-
W X Y Z tion in the vertical position (maximum offset
A: Model Unit
[mm] [mm] [mm] [mm] from the vertical : 15°)
B: Code number Housing 4
250 900 700 700
C: Application, Protection (Code n° 114X34-- or 114X44--)
D: Refrigerant Installation and servicing of the condensing
E: Housing Service Pressure (Maximum units by qualified personnel only.
working pressure) Follow these instructions and sound
F: Supply voltage, Locked Rotor Ampere, refrigeration engineering practice relating to
Maximum Current Consumption installation, commissioning, maintenance and
G: Serial Number and bar code service.

V T
U
U

Picture 3 : Electronic controller display

Compressor running

Crankcase heater on
V
Fan running

T: Mounting brackets for stacked mounting (not supplied) Temperature value for suction pressure.
Push lower button to switch to tempera-
U: M8 bolts for stacked mounting (supplied) ture value for condensing pressure
Picture 2 : Stacked mounting V: Mounting bolts (not supplied)

Picture 4 : Normal wiring Picture 5 : Temporary wiring


© Danfoss | DCS (CC) | 2020.12 118A2221A - AN363632996019en-ZA0101 | 1
Instructions

Designation system for the Optyma™ Plus range

OP - MPXM 034 ML P06 G


1 2 3 4 5 6 7 8

Version control
1 Application
M = MBP Optyma™ Plus (P06)
L = LBP IP level IP54
2 Package Compressor technology Scroll/ Reciprocating
Condensing unit family: P = Optyma™ Plus Control box (pre-wired E-panel) yes
Microchannel condenser yes
3 Refrigerant
Q = R452A, R404A/R507 Fan speed controller* yes
X = R404A/R507, R134a, R407A, R407F, R448A, R513A Main switch (circuit breaker) yes
R449A,R452A Supply monitoring relay -
4 Condenser Filter drier (flare connections) yes
M = Microchannel heat condenser
Sight glass yes
5 Swept volume Crankcase heater yes
Displacement in cm3: Example 034 = 34 cm3 HP/LP adjustable pressostat Electronic
Fail safe mini-pressostat Mechanical
6 Compressor platform Access door(s) yes
ML = Fixed speed scroll MLZ
LL = Fixed speed scroll LLZ Acoustic insulation yes
7 Version Condensing unit electronic controller yes
P06: Optyma™ Plus with PRV Network connectivity yes
Stack mounting yes
8 Voltage code Discharge gas thermostat yes
E = 400V/3-phase/50Hz compressor & 230V/1-phase fan
HP/LP Alarm yes
Pressure relief valve yes
* Inbuilt function within Condensing unit electronic controller

1 – Introduction •  Store and transport the unit in an upright • Ensure that the power supply corresponds to
These instructions pertain to Optyma™ Plus position. the unit characteristics (see nameplate).
condensing units OP-LPOM, & OP-MPXM used • Store the unit between -35°C and 50°C. •  When installing units for HFC refrigerants,
for refrigeration systems. They provide necessary • Don’t expose the packaging to rain or corrosive use equipment specifically reserved for HFC
information regarding safety and proper usage of atmosphere. refrigerants which was never used for CFC or
this product. • After unpacking, check that the unit is complete HCFC refrigerants.
and undamaged. • Use clean and dehydrated refrigeration-grade
The condensing unit includes following: copper tubes and silver alloy brazing material.
• Microchannel heat exchanger 3 – Installation precautions • Use clean and dehydrated system components.
• Reciprocating or scroll compressor Never place the unit in a flammable • The suction piping connected to the
• Receiver with stop valve atmosphere. compressor must be flexible in 3 dimensions
• Ball valves Place the unit in such a way that it is not to dampen vibrations. Furthermore piping has
• Sight glass blocking or hindering walking areas, doors, to be done in such a way that oil return for the
• High & low pressure switches windows or similar. compressor is ensured and the risk of liquid
• Replaceable filter drier slug over in compressor is eliminated.
• Electronic controller • Ensure adequate space around the unit for air
• Main circuit breaker (Main switch with overload circulation and to open doors. Refer to picture 4 – Installation
protection) 1 for minimal values of distance to walls. • The installation in which the condensing unit is
• Fan and compressor capacitors • Avoid installing the unit in locations which are installed must comply to pressure Equipment
• Compressor contactor daily exposed to direct sunshine for longer Directive (PED) 2014/68/EU. The condensing unit
• Robust weather proof housing periods. itself is not a ”unit” in the scope this directive.
•  Avoid installing the unit in aggressive and • It is recommended to install the unit on rubber
2 – Handling and storage dusty environments. grommets or vibration dampers (not supplied).
• It is recommended not to open the packaging • Ensure a foundation with horizontal surface • It is possible to stack units on top of each other.
before the unit is at the final place for (less than 3° slope), strong and stable enough Maximum
Unit
installation. to carry the entire unit weight and to eliminate stacking
• 
Handle the unit with care. The packaging vibrations and interference. Housing 4
2
(Code no. 114X34-- or 114X44--)
allows for the use of a forklift or pallet jack. Use • The unit ambient temperature may not exceed
appropriate and safe lifting equipment.. 50°C during off-cycle. • 
When stacking, the topmost unit must be

2 | AN363632996019en-ZA0101 - 118A2221A © Danfoss | DCS (CC) | 2020.12


Instructions

secured to the wall, as shown in picture 2. overload protection. The overload protection is condenser or liquid receiver. Ensure a slow
•  Slowly release the nitrogen holding charge factory preset but it is recommended to check charging of the system to 4 – 5 bar for R404A/
through the schrader port. the value before taking the unit in operation. R448A/R449A/R407A/R407F/R452A and
• Connect the unit to the system as soon as The value for the overload protection can be approx. 2 bar for R134a and R513A.
possible to avoid oil contamination from found in the wiring diagram in the front door of • 
The remaining charge is done until the
ambient moisture. the unit. installation has reached a level of stable
• Avoid material entering into the system while • 
The unit is equipped with high and low nominal condition during operation.
cutting tubes. Never drill holes where burrs pressure switches, which directly cut the power • Never leave the filling cylinder connected to
cannot be removed. supply to the compressor in case of activation. the circuit.
•  Braze with great care using state-of-the-art Parameters for high and low pressure cut outs
technique and vent piping with nitrogen gas are preset in the controller, adapted to the 10 – Setting the electronic controller
flow. compressor installed in the unit. • The unit is equipped with an electronic controller
•  Connect the required safety and control • 
P05 models are also equipped with phase which is factory programmed with parameters
devices. When the schrader port is used for this, sequence relay to protect the unit against for use with the actual unit. Refer to Manual
remove the internal valve. phase loss/sequence/ asymmetry and under-/ 118U3808 for details.
• It is recommended to insulate the suction pipe over-voltage. •  By default, the electronic controller display
up to the compressor inlet with 19 mm thick shows the temperature value for the suction
insulation. For units with a 3-phase scroll compressor (OP- pressure in °C. To show the temperature value for
MPXMxxxxxxxxE), correct phase sequence for the condensing pressure, push the lower button
5 – Leak detection compressor rotation direction shall be observed. (picture 3).
Never pressurize the circuit with oxygen or dry • 
Determine the phase sequence by using a
air. This could cause fire or explosion. phase meter in order to establish the phase The electronic controller is factory preset for R404A
orders of line phases L1, L2 and L3. or R449A or R452A or R134a depending on the
• Do not use dye for leak detection. • Connect line phases L1, L2 and L3 to main model of compressor mounted and application
• Perform a leak detection test on the complete switch terminals T1, T2 and T3 respectively. (Refer Annexx in Optyma Controller installation
system. manual). If another refrigerant is used, the
• The maximum test pressure is 31 bar. 8 – Safety refrigerant setting must be changed. Parameter
• When a leak is discovered, repair the leak and Fusible Plug is not installed in unit, it is replaced r12 must be set to 0 before (software main switch=
repeat the leak detection. with adapter blanking plug. off).
Unit has liquid receiver with an Adapter Plug with • Push the upper button for a couple of seconds.
6 – Vacuum dehydration 3/8” NPT connection. installer/end user can select The column with parameter codes appears.
• 
Never use the compressor to evacuate the various options as mentioned in EN378-2 : 2016 • Push the upper or lower button to find parameter
system. Article § 6.2.2.3 code o30.
• Connect a vacuum pump to both the LP & HP • Optyma Plus fitted with atmospheric pressure • Push the middle button until the value for this
sides. relief valve. Don’t connect any tube at end of the parameter is shown.
pressure relief valve.
• Pull down the system under a vacuum of 500 • Push the upper or lower button to select the new
• Once the pressure relief valve opens, don’t use
µm Hg (0.67 mbar) absolute. dry air or oxygen to evacuate the refrigerants. value: 2 = R22, 3 = R134a, 36 = R513A, 17 = R507,
• Do not use a megohmmeter nor apply power • Optyma Plus (P06 version only) factory fitted 19 = R404A, 20 = R407C , 21 = R407A, 37 = R407F,
to the compressor while it is under vacuum as with pressure relief valve at 33 bar setting. 40 = R448A, 41 = R449A, 42 = R452A.
this may cause internal damage. • 
Once pressure relief valve opens, Danfoss • Push the middle button to confirm the selected
recommended to replace new pressure relief
value.
valve.
7 – Electrical connections • Push the upper or lower button to find parame­
• Switch off and isolate the main power supply. ter code r84.
• Ensure that power supply can not be switched • Push the middle button until the value for this
on during installation. parameter is shown as 125
• All electrical components must be selected as • Push the upper button to select the new value:
per local standards and unit requirements. 130.
• Refer to wiring diagram for electrical
connections details. 11 – Verification before commissioning
•  Ensure that the power supply corresponds • The unit/installation into which the condensing Use safety devices such as safety pressure
to the unit characteristics and that the power unit is mounted/integrated, must be in switch and mechanical relief valve in compliance
supply is stable (nominal voltage ±10% and accordance with the PED. with both generally and locally applicable
nominal frequency ±2,5 Hz). • Beware of extremely hot and cold components. regulations and safety standards. Ensure that
• Dimension the power supply cables according • Beware of moving components. Power supply they are operational and properly set.
to unit data for voltage and current. should be disconnected while servicing. Check that the settings of high-pressure
• Protect the power supply and ensure correct switches and relief valves don’t exceed the
earthing. 9 – Filling the system maximum service pressure of any system
•  Make the power supply according to local • 
Never start the compressor under vacuum. component.
standards and legal requirements. Keep the compressor switched off. • Verify that all electrical connections inside the
•  The unit is equipped with an electronic • Use only the refrigerant for which the unit is condensing unit are properly fastened as they
controller. Refer to Manual 118U3808 for details. designed for. could have worked loose during transportation.
• The unit is equipped with a main switch with • 
Fill the refrigerant in liquid phase into the • When a crankcase heater is required, the unit

© Danfoss | DCS (CC) | 2020.12 118A2221A - AN363632996019en-ZA0101 | 3


Instructions

must be energized at least 12 hours before phase may be added in the low-pressure side To prevent system related problems, following
initial start-up and start-up after prolonged as far as possible from the compressor. The periodic maintenance is recommended:
shutdown for belt type crankcase heaters. compressor must be operating during this • Verify that safety devices are operational and
• The unit is equipped with a main switch with process. properly set.
overload protection. Overload protection is • Do not overcharge the system. • Ensure that the system is leak tight.
preset from factory, but it is recommended • Follow the local regulations for restoring the • Check the compressor current draw.
to check the value before taking the unit in refrigerant from unit. • Confirm that the system is operating in a way
operation. The overload protection value can • Never release refrigerant to atmosphere. consistent with previous maintenance records
be found in the wiring diagram in the unit front • Before leaving the installation site, carry out and ambient conditions.
door. a general installation inspection regarding • Check that all electrical connections are still
• Check if discharge temperature sensor is firm cleanliness, noise and leak detection. adequately fastened.
and has proper contact with discharge pipe. • Record type and amount of refrigerant charge • Keep the unit clean and verify the absence of
as well as operating conditions as a reference rust and oxidation on the unit components,
12 – Start-up for future inspections. tubes and electrical connections.
•  Never start the unit when no refrigerant is The condenser must be checked at least once
charged. 14 – Emergency running without controller a year for clogging and be cleaned if deemed
• All service valves must be in the open position. In case of controller failure, the condensing unit necessary. Access to the internal side of the
•  Rotalock valve on the receiver must be can still be operated when the controller standard condenser takes place through the fan door.
turned 1 round to close direction to get the wiring (picture 4) is modified into a temporary Microchannel coils tend to accumulate dirt on
right condensing pressure for the pressure wiring (picture 5) as described below. the surface rather than inside, which makes them
transmitter This modification may be done by authorized easier to clean than fin-&-tube coils.
•  Check compliance between unit and power electricians only. Country legislations have to be •  Switch off the unit at main switch before
supply. followed. opening the fan door.
• Check that the crankcase heater is working. Disconnect the condensing unit from power • Remove surface dirt, leaves, fibres, etc. with
• Check that the fan can rotate freely. supply (turn hardware main switch off ) a vacuum cleaner, equipped with a brush or
•  Check that the protection sheet has been • Contact of Room Thermostat must be possible other soft attachment. Alternatively, blow
removed from the backside of condenser. to switch 250VAC. compressed air through the coil from the inside
• Balance the HP/LP pressure. • Remove wire 22 (safety input DI3) and wire 24 out, and brush with a soft bristle. Do not use
•  Energize the unit. It must start promptly. If (room thermostat DI1) and put them together a wire brush. Do not impact or scrape the coil
the compressor does not start, check wiring with an insulated 250 Vac 10mm² terminal with the vacuum tube or air nozzle.
conformity and voltage on terminals. bridge. • Before closing the fan door, turn the fan blade
• Eventual reverse rotation of a 3-phase • Remove wire 25 (room thermostat DI1) and in a safe position, to avoid that the door hits the
compressor can be detected by following wire 11 (compressor supply) and put them fan.
phenomena; the compressor doesn’t build up together with an insulated 250VAC 10mm²
pressure, it has abnormally high sound level terminal bridge. If the refrigerant system has been opened, the
and abnormally low power consumption. P05 • Remove wire 6 and connect it with terminal system has to be flushed with dry air or nitrogen
models are equipped with a phase-reversal bridge for wire 11 and 25. A fan pressure switch to remove moisture and a new filter drier has to
relay and compressor doesn’t start, the or fan speed controller can be connected in be installed. If evacuation of refrigerant has to
compressor doesn’t build up pressure, in case series to wire 6. be done, it shall be done in such a way that no
of wrong phase sequences. In such case, shut • Remove wire 14 (crankcase heater) and connect refrigerant can escape to the environment.
down the unit immediately and connect the it to the compressor contactor terminal 22.
phases to their proper terminals. •  Remove wire 12 (supply crankcase heater), 16 – Declaration of incorporation
• If the rotation direction is correct the low pressure extend this wire by using an 250 Vac 10mm² • Pressure Equipment Directive 2014/68/EU
indication on the controller (or low pressure terminal bridge and 1,0mm² brown cable and EN 378-2:2016 - Refrigerating systems and Heat
gauge) shall show a declining pressure and connect it to compressor contactor terminal 21 Pumps - Safety and environmental requirements-
the high pressure indication (or high pressure •  Remove the large terminal block from the Parts 2: Design, construction, testing, marking
gauge) shall show an increasing pressure. controller terminals 10 to 19. and documentation.
• Connect the condensing unit to power supply Low Voltage Directive 2014/35/EU EN
13 – Check with running unit (turn hardware main switch on). 60335-1:2012 + A11:2014- Household and
• Check the fan rotation direction. Air must flow similar electrical appliances-Safety-Part 1:
from the condenser towards the fan. 15 – Maintenance General requirements-for all above mentioned
• Check current draw and voltage. Always switch off the unit at main switch condensing units Eco-design DIRECTIVE
•  Check suction superheat to reduce risk of before opening the fan door (s). 2009/125/ EC, establishing a framework for the
slugging. Internal pressure and surface temperature setting of Eco-design requirements for energy-
• When a sight glass is provided observe the oil are dangerous and may cause permanent injury. related products.
level at start and during operation to confirm Maintenance operators and installers require REGULATION (EU) 2015/1095, implementing Eco-
that the oil level remains visible. appropriate skills and tools. Tubing temperature design Directive 2009/125/EC with regard to Eco-
• Respect the operating limits. may exceed 100°C and can cause severe burns. design requirements for professional refrigerated
• Check all tubes for abnormal vibration. Ensure that periodic service inspections to storage cabinets, blast cabinets, condensing units
Movements in excess of 1.5 mm require ensure system reliability and as required by local and process Chiller.
corrective measures such as tube brackets. regulations are performed. • Condensing unit measurements are made
•  When needed, additional refrigerant in liquid according to standard “EN 13771-2:2017”

4 | AN363632996019en-ZA0101 - 118A2221A © Danfoss | DCS (CC) | 2020.12


Instructions

– Compressor and condensing units for • Absence of nameplate. maintenance.


refrigeration-performance testing and test •  External modifications, in particular, drilling, • Use in mobile applications.
methods- part 2: Condensing units. welding, broken feet and shock marks. • Use in explosive atmospheric environment.
• Compressor opened or returned unsealed. • No model and serial number transmitted with
17 - Warranty • Rust, water or leak detection dye inside the the warranty claim.
Always transmit the model number and serial compressor.
number with any claim filed regarding this • Use of a refrigerant or lubricant not approved 18 – Disposal
product. by Danfoss. Danfoss recommends that condensing
The product warranty may be void in following • Any deviation from recommended instructions units and oil should be recycled by a
cases: pertaining to installation, application or suitable company at its site.

© Danfoss | DCS (CC) | 2020.12 118A2221A - AN363632996019en-ZA0101 | 5


Instructions

OP-LPQM215-271 & OP-MPXM125-162

E H D

B F
G

A H4

English Legend D Air in H Nameplate


A Ø12 Hole for Mounting E Air out Electrical Cables
B Sight Glass F Suction Port Note: all dimension are in mm
C Controller Display G Liquid Port

6 | AN363632996019en-ZA0101 - 118A2221A © Danfoss | DCS (CC) | 2020.12


Instructions

P06 Models: OP-LPQM215-271 & OP-MPXM125-162

3
B1 R1

B3 P1
PRV

4
T4
T1 R2 R1 5

1 6

B4 T3 R3
B2 P2

8 7

1 Compressor 8 Suction Ball Valve R2 Discharge Temperature Sensor (T2)


2 Electric Expansion Valve B1 Condensing Pressure Transducer (P1) R3 Suction Temperature Sensor (T3)
3 Micro Channel Heat Exchanger with axial fan B2 Suction Pressure Transducer (P2) S1 Pressure Relief Valve
4 Refrigerant receiver with rotalock valve B3 High Pressure cartridge Switch (auto-reset)(PSH) R8 Discharge Temperature Sensor (T1)
5 Filter Drier B4 Low Pressure cartridge Switch (auto-reset) (PSL) Insulation
6 Sight Glass D1 Pressure relief valve (PRV)
7 Liquid Ball Valve R1 Ambient Temperature sensor (T4)

© Danfoss | DCS (CC) | 2020.12 118A2221A - AN363632996019en-ZA0101 | 7


Code E: OP-LPQM215-271 & OP-MPXM125-162

WD1

English Legend C2 : Run Capacitor (Compressor) Q1 : Main Switch Supply : Supply


A1 : Optyma™ Plus Controller C3 : Run Capacitor (Fan 1) R1 : Ambient Temp. Sensor Fan : Fan
A2 : EMI Filter C4 : Run Capacitor (Fan 2) R2,R8 : Discharge Temp. Sensor Alarm : Alarm
A3 : Liquid Injection Controller F1 : Fuse (Control Circuit) R3 : Suction Temp. Sensor Comp. : Compressor
B1,B5 : Condensing Pressure Transducer F2,F3 : Motor protector R4,R5 : Auxiliary Temp. Sensor (optional) CCH : Crankcase Heater
B2 : Suction Pressure Transducer K1 : Contactor R6 : Crankcase Heater Aux : Auxiliary
B3 : High Pressure Switch (OFF = 31bar(g), K2 : Start Relay R7 : NTC Resistor
ON = 24bar(g)) M1 : Compressor S1 : Room Thermostat (optional)
B4 : Low Pressure Switch (OFF = -0,3bar(g), M2 : Fan Motor 1 S2 : Door Limit Switch
ON = 0,5bar(g)) M3 : Fan Motor 2 X1 : Terminal
C1 : Start Capacitor (Compressor) M4 : Electronic Expansion Valve

Danfoss A/S
6430 Nordborg
Denmark

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This
also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trade-
marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

8 | AN363632996019en-ZA0101 - 118A2221A © Danfoss | DCS (CC) | 2020.12

You might also like