EC2-711 Condenser Controller

Operating Instructions
GB
Note: This document contains short form instructions for experienced users. Mounting
Use last column in List of Parameters to document your individual settings. The EC2-711 can be mounted in panels with a 71 x
More detailed information can be found in the User Manual. 29 mm cutout. See dimensional drawing below for
space requirements including rear connectors.
Push controller into panel cutout.(1)
Make sure that mounting clamps are flush with
outside of controller housing
Insert allen key into front panel holes and turn
clockwise. Mounting clamp will turn and gradually
move towards panel (2)
Turn allen key until mounting clamp barely touches
panel. Then move other mounting clamp to the same
The EC2-711 has been designed to control condensers with up to four fans. The position (3)
purpose of the controller is to keep condensing pressure to a minimum by Tighten both sides very carefully until controller is
switching fans on or off. secured. Do not over tighten as mounting clamps
will break easily.

Electrical Installation
Refer to the electrical wiring diagram
(right) for electrical connections. A copy
of this diagram is labelled on the
controller.
The PT5 pressure transmitter (5) senses condensing pressure and feeds the signal Use connection wires/cables suitable for
into a condensing pressure dead band control loop. Condensing pressure is 90°C operation (EN 60730-1).
modulated by turning fan motors on and off. EC2 analog inputs are for dedicated
No change occurs as long as the condensing pressure remains within the dead band sensors only and should not be connected
(P1) around the condensing pressure setpoint (P0). The controller will add/remove to any other devices. Volt free digital
fan capacity when the condensing pressure goes beyond the limits of the inputs should only be connected to serial
condensing pressure dead band. For stable condenser operation, adjustable time control loops or relays with gold
delays for fan motor on and off are available. To avoid premature wear of contacts. They should not be connected
individual fan motors, run time equalization is built into the controller. to any other devices
remove capacity dead band add capacity Important: Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30mm.
Warning: Use a class II category transformer for 24VAC power supply
(EN 60742). Do not ground the 24VAC lines. We recommend to use one
Condensing Pressure transformer per EC2 controller and to use separate transformers for 3rd party
controllers, to avoid possible interference or grounding problems in the power
A fast recovery procedure can be used to immediately switch off all fans when the supply. Connecting any EC2 inputs to mains voltage will permanently damage the
condensing pressure falls below a set limit. Similarly an emergency routine can be EC2.
activated automatically if the condensing pressure exceeds a definable limit.
Set-up and Parameter Modification Using The Keypad
! Safety instructions:
For convenience, an infrared receiver for the optional IR remote control unit is
build-in, enabling quick and easy modification of the system parameters when a
• Read installation instructions thoroughly. Failure to comply can result in computer interface is not available.
device failure, system damage or personal injury. Alternatively, the parameters can be accessed via the 4-button keypad. The
• The product is intended for use by persons having the appropriate configuration parameters are protected by a numerical password. The default
knowledge and skills. password is “12”. To select the parameter configuration:
• Ensure electrical ratings per technical data are not exceeded. • Press the PRG button for more than 5 seconds, a flashing “0” is displayed
• Disconnect all voltages from system before installation.
• Keep temperatures within nominal limits. • Press or until “12” is displayed (password)
• Comply with local electrical regulations when wiring • Press SEL to confirm password
The first modifiable parameter code is displayed (/1).
Technical data: To modify parameters see Parameters modification below.
Power supply 24VAC ±10%; 50/60 Hz; Class II
Power consumption 4VA max.
Communication LonWorks® Interface, FTT10, RJ45 connector
Terminals Removable screw terminals
wire size 0.14 … 1.5mm2
Temperature
storage -20 … +65°C
operating 0 … +60°C
Pressure sensor input 24VDC, 4 … 20mA
Fan output relays SPDT contacts, AgCdO
Inductive (AC15) 250V / 2A
Resistive (AC1) 250V / 6A; 12A total return current
Fan variable output signal 0 … 10V; (3mA max)
Digital inputs Volt free contacts 5V/0,1mA
Humidity 0 … 80% rh. non condensing
Protection class IP65 (front protection with gasket)
Marking

EC2-711_65107_EN_R02.doc Replacement for Rev.: 01 1/4 16.09.2009


EC2-711 Condenser Controller
Operating Instructions
GB

Parameter Modification: Procedure Indications On The Display:


• Press or to show the code of the parameter that has to be changed; Condenser fan controller
• Press SEL to display the selected parameter value; • State
• Alarm in combination with alarm message and alarm LED
• Press or to increase or decrease the value;
• Condensing pressure or saturation temperature from condensing pressure
• Press SEL to temporarily confirm the new value and display its code;
• Parameter
• Repeat the procedure from the beginning "press or to show..." Other display
To exit and save the new settings: • Pressure: Pressure value in bar (g)
• Press PRG to confirm the new values and exit the parameters modification • Alarm: Alarm condition
procedure.
• IR: IR communication enabled
To exit without modifying any parameter:
• Do not press any button for at least 60 seconds (TIME OUT).
• Press “ESC” on IR remote control. Alarm Codes
hP High pressure alarm
Condensing pressure higher than the maximum limit
Load Default Parameters:
The default parameter settings can be reloaded into the controller memory by using lP Low pressure alarm
the special function described below Condensing pressure lower than the minimum limit

EP Error pressure
Special Functions:
Condensing pressure sensor failure
The Special Functions can be activated by:
• Press and together for more than 5 seconds, a flashing “0” is displayed. Fr Fast recovery alarm
• Press or until the password is displayed (default = 12). If password was Fast recovery form low condensing pressure
changed, select the new password.
• Press SEL to confirm password, a “0” is displayed and the Special Function hr High discharge pressure alarm
mode is activated. High condensing pressure recovery
• Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below. E1 Feedback alarm 1
Digital input associated with fan 1 has changed into alarm state (safety chain)
• Press SEL to activate the function without leaving the special function mode.
• Press PRG to activate the function and leave the special function mode.
E2 Feedback alarm 2
Most of the Special Functions work in a toggle mode, the first call activates the Digital input associated with fan 2 has changed into alarm state (safety chain)
function, and the second call deactivates the function.
The indication of the function can only be displayed after exiting the special
E3 Feedback alarm 3
function mode. Digital input associated with fan 3 has changed into alarm state (safety chain)
• 0: Display test function
• 1: Resets all parameters to the factory default setting. The controller will E4 Feedback alarm 4
indicate “oF” during the reset and the valve will close. Digital input associated with fan 4 has changed into alarm state (safety chain)

n1 Service alarm 1
Display of Data:
Fan 1 operating time higher than run limit
The data to be permanently shown on the display can be selected by the user (parameter
/1). In case of an alarm, the alarm code is displayed alternately with the selected data.
n2 Service alarm 2
The user can inhibit the alarm code. Fan 2 operating time higher than run limit
It is possible to temporarily display these values. This is a useful feature when
initially setting-up the system without the aid of the WebPages. Press the SEL
n3 Service alarm 3
button to scroll through all possible displayable data.. The display will show for one Fan 3 operating time higher than run limit
second the numerical identifier of the data (see /1 parameter) and then the selected data.
After two minutes the display will return to the by parameter /1 selected data. This
n4 Service alarm 4
action is only valid when parameter H2 = 3. Fan 4 operating time higher than run limit
LON activity LED IR LED Fan 4 on
(only active when service pin is pressed) Er Data error
Data send to the display is out of range
Display indicates condenser controller
Messages
Display indicates pressure in bar
--- No data to display
Alarm condition The display will show an “---” at node start up and when no data is send to the
display.
Fan 3 on
Fan 2 on Fan 1 on In Reset to default values activated
The display will show an “In” when the factory default configuration data set
is initialized.

Id Wink request received


The display will show a flashing “Id” when the wink request was received.
The flashing “Id” will be shown on the display until the service button will be
pressed, or a 30 min delay timer will expire or a second wink request is
received.

OF Node is offline
The node is offline and no application is running. This is the result of a
network management command and will happen for example during node
installation.

EC2-711_65107_EN_R02.doc Replacement for Rev.: 01 2/4 16.09.2009


EC2-711 Condenser Controller
Operating Instructions
GB

Fan controller
/ DISPLAY PARAMETERS Min Max Unit Def Individ. u STEP ENABLE PARAMETERS Min Max Unit Def Individ.
u0 Reset operating time 0 5 - 0
/1 Value to be shown on display 0 2 - 0 0 = do nothing
0 = Fan states 1 = reset operating time fan 1
1 = condensing pressure (bar) 2 = reset operating time fan 2
2 = condensing temperature (°C) 3 = reset operating time fan 3
4 = reset operating time fan 4
5 = reset operating time all fans
r SENSOR PARAMETERS u1 Enable/disable fan 1 0 1 flag 1
r0 Condensing pressure sensor -1.0 50 bar 0.0 u2 Enable/disable fan 2 0 1 flag 1
minimum value
u3 Enable/disable fan 3 0 1 flag 1
r1 Condensing pressure sensor -1.0 50 bar 30
u4 Enable/disable fan 4 0 1 flag 1
maximum value
r2 Pressure offset for condensing -1.0 1.0 bar 0.0
C APPLICATION PARAMETERS
pressure
C1 Number of fans 1 4 - 4
r3 Refrigerant type 0 5 - 4
C4 Fan 1 (0 = standard control loop 0 1 - 0
0 = no temperature conversion;
1 = fan 1 act as base load)
1 = R22; 2 = R134a; 3 = R507; 4 = R404A; 5 = R407C
C5 Fan switch logic (Rotation) 0 1 flag 1
0 = FILO logic (First In, Last Out)
P SET-POINT PARAMETERS Capacity demand: Adds first fan.
P0 Pressure set-point (condensing) for -1.0 50 bar 14.0 Capacity excess: Removes last fan.
fan circuit 1 = Rotation enabled
P1 Pressure band (dead band for dead 0.0 50 bar 4.0 Capacity demand: Adds fan with lowest runtime out of
band control mode) available fans.
P3 Fast recovery from low pressure -9.9 50.0 bar 9 Capacity excess: Removes fan with highest runtime out of
P4 Enable set-point compensation 0 1 - 0 available fans.
0 = disabled; 1 = enabled C6 Number of fans to switch on in case 0 4 - 0
P5 Maximum pressure compensation -3.0 3.0 bar -3.0 of sensor failure
P6 Temperature at minimal shift value -50.0 50 °C 30
(0) H OTHER PARAMETERS
P7 Temperature at maximal shift value -50.0 50 °C 15.0 H2 Keyboard and IR remote control 0 3 - 3
(Shift Max) 0 = all disabled
P8 High discharge pressure recovery. -9.9 50 bar 20 (Caution, access to controller only via LON network possible)
Activates sprinkler valve 1 = Keyboard enabled
2 = IR remote control enabled
A ALARM PARAMETERS 3 = Keyboard and IR remote control enabled
A2 Minimum condensing pressure -1.0 50 bar 10.0 H3 IR remote control access code 0 199 - 0
alarm limit H5 Password 0 199 - 12
A3 Maximum condensing pressure -1.0 50 bar 27
alarm limit
A4(1) Delay time for minimum pressure 0 99 10sec 0
alarm limit
A5(1) Delay time for maximum pressure 0 99 10sec 0
alarm limit
A8(1) Fan serial alarm delay 0 99 10sec 0
A9(2) Fan run limit 0 99 10000hr 0

(1)
These values have a resolution of 10 sec, on the local display. Ex. a value 1 means 10 sec.
(2)
These values have a resolution of 10.000 hours, on the local display. Ex. a value 1 means 10.000 hours.

• Note: Concerning the indicated parameters, it is recommended to check, before installing, if the factory value is suitable for the required use

EC2-711_65107_EN_R02.doc Replacement for Rev.: 01 3/4 16.09.2009


EC2-711 Condenser Controller
Operating Instructions
GB

Visualising Data: LON Monitoring Server


The EC2-711 has a LON communication interface enabling the controller to be
directly connected to a Monitoring Server. It can be connected by using the
optional cable assembly to a LON network (ECC-014, order nr. 804 381, with
RJ45 to open, cable length 3m).

Neuron ID / Service PIN:


The service pin is available on the display. It is used to identify the controller in a
LON network. Press the button for app. 1 second to send the Neuron ID. The
LED in the left upper corner will indicate the transmission of the Neuron ID.
The default settings may be modified remotely from the Monitoring Server via the
LON network. Consult the EMS__64074 user manual for more information.
It is also possible to display live graphical data on the server or to log data
containing the control temperature at defined intervals.

Emerson Electric GmbH & Co OHG is not to be held responsible for erroneous knowledge of today. It is intended only for use by persons having the appropriate
literature regarding capacities, dimensions, applications, etc. stated herein. technical knowledge and skills, at their own discretion and risk. Since conditions of
Products, specifications and data in this literature are subject to change without use are outside of EMERSON’s control we cannot assume any liability for results
notice. The information given herein is based on technical data and tests which obtained or damages occurred due to improper application.
EMERSON believes to be reliable and which are in compliance with technical This document replaces all former versions

Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200
www.emersonclimate.eu

EC2-711_65107_EN_R02.doc Replacement for Rev.: 01 4/4 16.09.2009