Switchgear Type SIMOPRIME A4 Up To 24 KV, Air-Insulated Tested According To IEC 62271-200

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Medium-Voltage

Circuit-breaker
Switchgear
Switchgear Type SIMOPRIME A4 Catalog
up to 24 kV, Air-Insulated
Tested according to IEC 62271-200
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24kV, Air-Insulated

Contents Application

Page Benefits, typical uses

Application Benefits (see also page 10 for details)


Benefits 2 • Saves lives
Typical uses 2 and 3 • Peace of mind

Technical Data • Increases productivity


Ratings 4 • Saves money
Classification, dimensions, 4
room planning

Product Range
Panels 5 The circuit-breaker switchgear type
SIMOPRIME A4 is a factory-
Design assembled, type-tested switchgear
for indoor installation according to
Panel design 6 IEC 62 271-200 and VDE 0670-6.
Compartments, interlocks, 7
operation
Benefits and features 8

Standards
Standards, specifications, 9
guidelines

Notes
Notes 10

SIMOPRIME A4 panel
Maximum ratings 24kV / 25 kA / 2500 A

Typical uses
The SIMOPRIME A4 circuit-breaker switchgear can be used in transformer and
switching substations, e.g.:

Application: Power supply system ■ Chemical industry


■ Power supply companies ■ Petroleum industry
Application: Industry ■ Pipeline installations
■ Power stations ■ Offshore installations
■ Cement industry ■ Electrochemical plants
■ Automobile industry ■ Petrochemical plants
■ Iron and steel works ■ Shipbuilding industry
■ Rolling mills ■ Diesel power plants
■ Mining industry ■ Emergency power supply
installations
■ Textile, paper and food
industries ■ Lignite open-cast mines
■ Traction power supplies

2 Printed by Siemens
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24kV, Air-Insulated

Application

Typical uses

Application
Industry

R-HA26-012.tif

Application
Public power
supply system

SIMOPRIME A4 switchgear

Application
Industry

Printed by Siemens 3
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24 kV, Air-Insulated

Technical Data

Ratings, Classification, dimensions, room planning


Electrical data (maximum values) of SIMOPRIME A4
Ratings Rated values
(max.)

Switchgear up to 24kV
Rated voltage 24kV 24 kV
Rated frequency 50/60 Hz
Rated short-duration power-frequency withstand voltage 50 kV
Rated lightning impulse withstand voltage 125 kV
Rated short-time withstand current, 3 s 25 kA
Rated peak withstand current at 50/60 Hz 63 kA
Rated short-circuit breaking current 25 kA
Rated short-circuit making current at 50/60 Hz 63 kA
Rated normal current of busbar 2500 A
Rated normal current of feeders
– with circuit-breaker 2500 A
– with fused load break switch As per fuse

Classification of the SIMOPRIME A4 switchgear according to IEC 62 271-200


Resistance to internal arcs Construction and design
Classification IAC Class of partitions PM
Accessibility Service continuity category LSC2B
– Front Type A Compartment accessibility (standard)
– Rear Type A – Busbar compartment Tool-based
– Lateral Type A – Switching-device compartment Interlock-based
Test current kA 25 – Low-voltage compartment Tool-based
Test duration s 1.0 – Connection compartment
– Front connection Interlock-based and
Tool-based
– Rear connection * Tool-based

* Contact factory for rear connection option


Dimensions
Room planning (Minimum room height W 2850 mm)

Front connection

Front

Single-row arrangement (plan view)


For dimensions B (width) and T (depth) refer to table on this page
1) For panel replacement: Control aisle W 2000 mm
B T 2) Minimum distance to wall W 150mm

Dimensions
All panel types in mm
Width B For 1250 A vacuum circuit-breaker 800
For 2500 A vacuum circuit-breaker 1000
For load-break switch 500
Height H With standard low-voltage compartment 2250
Depth T Standard 1900

4 Printed by Siemens
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24kV, Air-Insulated

Product Range

Panels

Circuit-breaker panel Disconnecting panel Bus sectionalizer (mirror-image Metering panel


Installation also possible)

Load-break switch panel

Components

Current transformer Withdrawable voltage HV HRC fuse 1) The details refer to


transformer with conventional RXS
primary fuses single-core sealing
ends for XLPE cables or
other makes with similar
Voltage transformer Make-proof 3AH5 vacuum dimensions.
without primary fuses earthing switch circuit-breaker

Voltage transformer Disconnecting link Three-position


with primary fuses or dummy truck Switch-disconnector

Capacitive voltage Cable sealing ends 1) Surge arresstor


detection system max. 4 x 500 mm2 per
phase

5 Printed by Siemens
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24 kV, Air-Insulated

Design

Panel design
Legend for panel design: Basic panel design (example)
1 Door of low-voltage
compartment
2 Opening for locking or
unlocking the low-voltage
compartment door
3 High-voltage door of switching
-device compartment
4 Inspection window for checking
the switching-device truck
5 Opening for locking or
unlocking the high-voltage door
6 Opening for mechanical char-
ging of circuit-breaker closing
spring
7 Openings for manual opera-
tion (ON/OFF) of the circuit-
breaker
8 Inspection window for reading
the indicators
9 Door handle
10 Openings for switching-device
truck operation
11 Opening for earthing-switch
operation
12 Pressure relief duct
13 Busbars
14 Bushings
15 Post insulators
16 Block-type current transformer
17 Option: Make-proof earthing
swtich
18 Cable sealing ends Circuit-
Circuit-breaker panel Design:
19 Option: Voltage transformer
Connection from front with block current transformer
20 Earthing busbar
21 Low-voltage plug connector
22 Vacuum interrupters
23 Switching-device truck

All operations behind closed door

6 Printed by Siemens
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24 kV, Air-Insulated

Design

Compartments, interlocks, operation


Switching-
Switching-device Connection compartment Interlocks Low-
Low-voltage compartment
compartment • Interlocking conditions are • Accommodates equipment
• Pressure relief upwards
• All switching operations with through rear pressure relief satisfied according to for protection, control,
high-voltage door closed duct IEC 62 271-200 / VDE measuring and metering
• Pressure relief upwards 0670-6 • Separated from the high-
• Suitable for connection of
• Panel powder-coated with - Single-core cables • Earthing switch can only be voltage part of the panel,
- Three-core cables operated with circuit- safe-to-touch
epoxy resin
• Independent opening shutters breaker truck in test position
• Shutter operating mecha- Low-
Low-voltage cables
nisms separately for to permit cable testing • Circuit-breaker truck can
– Busbar bushings • Earthing busbar only be moved with circuit- • Control cables of the panel
– Connection bushings breaker are flexible and have
• Connection from front metallic covers
• Metallic, earthed shutters and “OPEN” and earthing switch
• Use of block-type current • Connection between switch-
partitions ensure partition transformers “OPEN”
class PM ing device truck and panel
• Interlocked high-voltage door • Mechanical coding on the wiring to low-voltage com-
• High-voltage door pressure- and bolted partitions between circuit-breaker truck prevents partment via 64-pole coded
resistant in the event of connection compartment and insertion of similar circuit- plug connectors
internal arcs in the panel switching-device compartment breaker trucks for lower rated
normal currents into panels • Option: Fire-resistance
• Metallic ducts for laying provide interlock-based and control wiring
control cables tool-based access for panels with higher rated normal cur-
with connection from front rents
• Interlocking between
high-voltage door and • Option: Connection from rear • Interlocking of high-voltage
circuit-breaker truck ensures door against circuit-breaker
interlock-based access Components at the panel truck
connection (option) • The high-voltage door can
• Switching-device compart-
ment to accommodate com- • Single-core XLPE cables only be opened when the
ponents for implementing up to max. 4 x 500 mm2 circuit-breaker truck is in test
various panel versions with per phase position
– Vacuum circuit-breaker with • Three-core XLPE cables • Option: Electromagnetic
or without voltage trans- up to max. 3 x 300 mm2 interlocks
formers on the truck per phase
– Disconnector truck
– Metering truck • Coupling electrode for
capacitive voltage detection
system
Busbar compartment
• Voltage transformers
• Pressure relief upwards
– Cast-resin insulated
and through rear pressure
– Max. 3 x 1-pole
relief duct.
– Fixed-mounted, without
• Option: Busbar transverse primary fuses
partition between panels
• Make-proof earthing switch
• Busbars made of flat copper, – With manual operating
bolted from panel to panel mechanism
- For rated normal currents up – In addition to standard inter-
to 2500 A locking of earthing switch/
- Option: Insulated busbars circuit-breaker truck,
• Bolted top covers provide optionally lockable or with
tool-based access electromagnetic interlock
• Option: Coupling electrode • Surge arresters
for capacitive voltage – Surge arresters for protecting
detection system the switchgear against exter-
nal overvoltages
• Options: Possibility of install-
ing the following components
- Voltage transformers
- Busbar earthing switch
- Current transformers in the
run of busbars

Printed by Siemens 7
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24kV, Air-Insulated

Design

Benefits and features

Benefits Features

• Saves lives • All switching operations including emergency manual operations


with high-voltage door closed
• Interlocking between high-voltage door and switching devices
• Rack-in, rack-out operations of the circuit-breaker truck with high-voltage door closed
• Metallic, earthed shutters and partitions, partition class: PM
• Internal arc tested design up to 25 kA, 1 s, according to IEC 62 271-200, Annex A
• Use of vacuum circuit-breakers

• Peace of mind • Factory-assembled, type-tested switchgear according to IEC 62 271-200


• Type testing of the circuit-breaker inside the panel
• Use of standard, worldwide available components
• Use of maintenance-free vacuum circuit-breakers
• Quality management according to DIN EN ISO 9001
• Design based on global best practice sharing and experience

• Increases productivity • Use of metallic, earthed shutters and partitions between the compartments ensures highest service
continuity of the switchgear (LSC2B according to IEC 62 271-200) during maintenance
• Use of maintenance-free vacuum circuit-breakers

• Saves money • Use of maintenance-free vacuum circuit-breakers

Truck-type design

8 Printed by Siemens
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24 kV, Air-Insulated

Standards

Standards, specifications, guidelines


Standards Overview of standards (August 2004)
The switchgear complies with IEC standard VDE standard EN standard
the relevant standards and current in future current in future current
specifications applicable at
Switchgear IEC 60 694 IEC 62 271-1 VDE 0670-1000 VDE 0671-001 EN 60 694
the time of type tests.
IEC 62 271-200 IEC 62 271-200 VDE 0670-6 VDE 0671-200 EN 62 271-200
Type of service location Devices 1) IEC 62 271-100 IEC 62 271-100 VDE 0671-100 VDE 0671-100 EN 62 271-100
The switchgear can be used 2) IEC 62 271-102 IEC 62 271-102 VDE 0671-102 VDE 0671-102 EN 62 271-102
for indoor installation in 3) IEC 62 265-1 IEC 62 271-103 VDE 0670-301 VDE 0671-103 EN 60 265-1
accordance with IEC 61 936 4) IEC 62 271-105 IEC 62 271-105 VDE 0671-105 VDE 0671-105 EN 62 271-105
(Power installations exceeding 5) IEC 61 243-5 IEC 61 243-5 VDE 0682-415 VDE 0682-415 EN 61 243-5
1 kV AC) and VDE 0101 6) IEC 60 282 IEC 60 282 VDE 0670-4 VDE 0670-4 EN 60 282
• Outside lockable electrical Degree of IEC 60 529 IEC 60 529 VDE 0470-1 VDE 0470-1 EN 60 529
service locations at places protection
which are not accessible to Insulation IEC 60 071 IEC 60 071 VDE 0111 VDE 0111 EN 60 071
the public. Enclosures of Current IEC 60 044-1 IEC 60 044-1 VDE 0414-1 VDE 0414-1 EN 60 044-1
switchgear can only be transformers
removed with tools. Voltage IEC 60 044-2 IEC 60 044-2 VDE 0414-2 VDE 0414-2 EN 60 044-2
transformers
• Inside lockable electrical
service locations. A lockable 5) Voltage detection systems
1) Circuit-breaker 3) Switch
electrical service location is a 2) Disconnector and earthing switch 4) Switch-fuse combination
6) HV HRC fuses
place outdoors or indoors that
is reserved exclusively for
housing electrical equip-
ment and which is kept un- Table – Insulating capacity
Resistanc
Resistance
sistance to internal
internal arc
arc faults
der lock and key. Access is Rated voltage (rms value) kV 24
restricted to authorized per- Rated short-duration power-frequency withstand voltage (rms value) • Safety of operating perso-
sonnel and persons who have nnel ensured by tests to
– Across isolating distances kV 60
been properly instructed in verify resistance to
electrical engineering. – Between phases and to earth kV 50
internal arc faults.
Untrained or unskilled per- Rated lightning impulse withstand voltage (peak value) • Internal arc tests in accord-
sons may only enter under the
supervision of authorized – Across isolating distances kV 145 ance with IEC 62 271-200,
– Between phases and to earth kV 125 Annex A.
personnel or properly in-
structed persons. • The switchgear complies with
criteria 1 to 5 specified in the
Terms Climate and ambient conditions
conditions mentioned standards for the
basic version up to 25 kA.
“Make-proof earthing switches” The switchgear may be used, subject to possible additional
are earthing switches with measures, under the following ambient conditions and climate • Definitions of the criteria:
short-circuit making capacity classes: – Criterion 1
according to Ambient conditions Correctly secured doors and
– IEC 62 271-102 and – Natural foreign materials covers do not open.
– VDE 0671-102 / – Chemically active pollutants Deformations are accepted
EN 62 271-102 – Small animals conditionally.
– Criterion 2
Current-
Current-carrying capacity Climate classes No fragmentation of
– 3K3 enclosures occurs within the
• According to IEC 60 694 / VDE – 3K5 time specified for test.
0670-1000 and IEC 62 271-200 Projections of small parts up
current- carrying capacities refer The climate classes are classified according to IEC 60 721-3-3. to 60 g are accepted.
to the following ambient tempera-
tures: – Criterion 3
Protection against solid foreign bodies, electric shock and ingress of Arcing does not cause holes in
– Maximum of water SIMOPRIME A4 switchgear fulfills acc. to the standards
24-hour mean +35°C the accessible sides up to a
– IEC 62 271-200 height of 2 m.
– Maximum +40°C – IEC 60 529
• The current-carrying capacity of – Criterion 4
– VDE 0470-1 Indicators do not ignite due to
the panels and busbars depends – VDE 0670-6
on the ambient temperature the effect of hot gases.
the following degrees of protection: Ignition caused by glowing
outside the enclosure.
– Enclosure: IP 4X particles rather than hot gases
• To attain the maximum rated
normal currents, the panels are – Compartments: IP 2X is allowed. Ignitions as a result
provided with natural or forced of paint or sticker burning are
ventilation. also excluded.
– Criterion 5
The enclosure remains
connected to its earthing
point.

Printed by Siemens 9
Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24 kV, Air-Insulated

Notes

Notes
If not stated otherwise on
the individual pages of this
catalog, we reserve the right
to include modifications, espe-
cially regarding the stated val-
ues, dimensions and weights.
Drawings are not binding.
All product designations used
are trademarks or product
names of Siemens AG or
other suppliers.
If not stated otherwise, all
dimensions in this catalog are
given in mm.
The information in this document
contains general descriptions of
the technical options available,
which do not always have to be
present in individual cases.
The required features should
therefore be specified in each
individual case at the time of
closing the contract.

Responsible for
Technical contents: Thevar Tharmalinga
PT Siemens Indonesia, PTD M1
General editing: Edmund Chua,
Siemens AG, PTD M1
Innovasia+

10 Innovasia Siemens Printed by Siemens


If you have any questions
tions about
Power Transmission
ransmission and
and Distribution,
our Cust
our ustomer
mer Suppor
Support Center is
available
ailable at
Tel: +62 21 24555 100
Fax: +62 21 24555 543
E-Mail: Trevor.holden@siemens.com
www.siemens.co.id/ptd

Published by
PT. Siemens Indonesia
Power Transmission and Distribution
Medium Voltage Division
Jl. A. Yani Kav B 67-68
Pulo Mas, Jakarta 13210
Indonesia

www.siemens.com/medium-voltage-switchgear Printed by Siemens

You might also like