Professional Documents
Culture Documents
PE452 - Lect9 - Differential Protection
PE452 - Lect9 - Differential Protection
PE452 - Lect9 - Differential Protection
1
Dot Markings
3
Differential Protection
During Load
• Current will be same on both sides of the equipment
• Instantaneous OC relay is used
• Spill Current will be there if there is current
mismatch
• Equipment????
4
Differential Protection
External Fault
• Same current through the primary of CT
• Same current through the secondary of CT
• No Spill current
• Why is this called External fault???
5
Differential Protection
Internal Fault
Minimum internal fault that will cause tripping
6
Differential Protection
Internal Fault (Double-end fed System)
What is 𝐼1 and 𝐼2 ????
7
Zone of Protection of Differential Relay
• Closed zone of protection
• Encompasses everything between two CTs
– Between CTs (Internal Faults)
– All other faults are external or through faults
• Ideal differential scheme
– Pickup smallest internal fault
– Restrain from tripping on the largest external fault
8
Actual Behavior of Differential Scheme
CT Limitations
• CTs are subjected to ratio and phase angle errors
• Errors depend on the burden on CTs
– Burden is dependent on the lead length and relay coil
impedance
• Error increases as the through fault current increase
• With the increase in error the spill current increases
9
Actual Behavior of Differential Scheme
CT Limitations
10
Actual Behavior of Differential Scheme
Through fault stability and stability Ratio
• Through fault increases, the spill current builds up
• At very high value, the difference between the
secondary I’s of the CT exceed the relay PS
• Loss of stability
11
Actual Behavior of Differential Scheme
12
Equivalent Circuit of CT
13
Differential Scheme
14
Draw backs
15
16