AKJ-LSD 2000-20m
Illustrative Example
DESIGN OF 2000 kL Tank on 20 m Staging
At Noida
Sponsored by
Designed by
March 2020
Ahinsa Khand 1, Indirapuram, Ghaziabad, UP 201014
email: ashokjain_iitr@yahoo.co.in
1 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
Design conforms to :
IS:3370-Parts 1 and 2-2009
IS:456-2000, IS 1893-4-2014, IS 1893-1-2016
The structural elements of container are designed by using the limit state
philosophy in accordance with IS 3370-2009.
The stagings, stair case and footings are designed by limit state design
in accordance with IS 456.
INPUT :
CAPACITY OF WATER TANK = 2000.000 kilo-litres
MEAN DIAMETER OF STAGING (DC3) = 17.000 m
CONCRETE MIX FOR THE TANK CONTAINER = M30
GRADE OF STEEL = Fe500
Modulus of elasticity of concrete = 2738.613 kN/cm**2
Modular ratio = 9.33
* MATERIAL PROPERTIES
UNIT WEIGHT OF CONCRETE = 25.00 kN/m**3
UNIT WEIGHT OF WATER = 10.00 kN/m**3
CONCRETE :
Cement: 33 grade / IS:269-2015
or 43 grade / IS:8112-2013
or 53 grade / IS:12269-2013
or Composite/ Blended/ PPC / IS:1489-2015 - part 1
Fine and coarse aggregate : IS:383-2019
PERMISSIBLE STRESS IN DIRECT COMPRESSION = 8.00 MPa
PERMISSIBLE STRESS IN HOOP TENSION = -1.50 MPa
PERMISSIBLE STRESS IN BENDING COMPRESSION = 10.00 MPa
PERMISSIBLE STRESS IN BENDING TENSION = -2.00 MPa
2 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
3 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
4 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
5 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
6 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
Provide 8 mm bars @ 150 c/c at top face (Ap = 3.33 cm**2 OK)
and 8 mm bars @ 300 m c/c at bottom face in balcony
7 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
8 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
DESIGN MOMENTS :
MOMENT IN TOP DOME = -.3810E+01 kNm/m
MOMENT IN TOP RING BEAM = .5711E-02 kNm/m
MOMENT IN WALL AT TOP = .3805E+01 kNm/m
MOMENT IN WALL AT BOTTOM = -.2449E+02 kNm/m
MOMENT IN MIDDLE RING BEAM = -.7718E-02 kNm/m
MOMENT IN CONICAL DOME AT TOP = .2125E+02 kNm/m
MOMENT IN CONICAL DOME AT BOTTOM = .5580E+02 kNm/m
MOMENT IN BOTTOM DOME = -.5363E+02 kNm/m
MOMENT IN BOTTOM RING BEAM = -.2174E+01 kNm/m
9 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
All elements are designed using the Limit State Procedure in accordance
with IS 3370-part 2. Details are enclosed.
Provide 7-25 mm bars at top and 2-25 mm bars at bottom, near supports,
and 5-25mm bars at bottom near midspan.
Provide 12mm str-2 leg @ 125 mm c/c throughout.
10 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
CONCRETE MIX :
1. Column = M30.
2. Brace = M25.
3. Raft = M25.
Modulus of elasticity of column conc = 2475.00 kN/cm**2
11 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
1 2 3 4
WIND SHEAR 283.67 246.89 210.10 173.32
EARTHQUAKE ZONE = 4
SEISMIC ZONE FACTOR (Z) = .2400
IMPORTANCE FACTOR (I) = 1.5000
RESPONSE REDUCTION FACTOR (R) = 4.0000
TYPE OF SOIL = 1
STIFFNESS OF STAGING = .230E+03 kN/cm
12 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad
Provide 2-16 + 1-12 mm bars at each face (Ap = 5.13 cm2 OK)
Provide 8 mm- 2 leg str @ 200 c/c in each brace.
13 Dr Ashok K. Jain, Former Head of Civil Engineering, IIT Roorkee, Ahinsa Khand 1,
Indirapuram, GZB <ashokjain_iitr@yahoo.co.in>
Design of 2000 Kl Tank over 20 m staging at Noida
For M/s ABC Builders and Contractors, Ghaziabad