13.8Kv Cable Sizing Calculation Construction of New 380/132Kv S/S AD-DAWADMI BSP (9037)

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 14

CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS
CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11
ISSUED FOR BASE DESIGN
DESCRIPTION

13.8kV CABLE SIZING CALCULATION

CONSTRUCTION OF NEW 380/132kV S/S


AD-DAWADMI BSP (9037)
SDC

SDC
BN
BY

29/08/12

15/10/12

23/01/13
DATE
NO.

REVISIONS
DRAWN

BY:-

DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 1 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-E (2004/10)

EDMS VECTOR EXCEL


CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS
CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

TABLE OF CONTENTS
ISSUED FOR BASE DESIGN

Sl. No. Description Page No.

1 Calculation Method 3
DESCRIPTION

2 Ampacity Calculation 3

3 Summary of Results 13

Attachment:

Annexure-A HV&MV Power Cable Data Schedule - Riyadh Cables


SDC

SDC

Annexure-B 13.8kV Cable Duct Bank Cross Section


BN
BY

29/08/12

15/10/12

23/01/13
DATE
NO.

REVISIONS
DRAWN

BY:-

DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 2 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-E (2004/10)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS

1.0 CALCULATION METHOD


CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS

Cable ampacity is calculated based on on IEC-60287 method of calculation.


The manufacturer's data for cable at standard installation methods, have been incorporated
in the given calculation method to obtain the actual derated ampacity of cable ,
in the site conditions
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

So, using the cable manufacturer's ( Riyadh cables) published data refer to the ampacity
as would have arrived by IEC-60287 method.
The 13.8 kV cables are laid through concrete ductbank from Auto Transformer
ISSUED FOR BASE DESIGN

to Control Buiding as 1 no. single core cable per phase, in trefoil formation inside a
PVC airfilled pipe.
DESCRIPTION

2.0 AMPACITY CALCULATION

Parameters

n = 1 number of conductor in a cable


Dq = Permissible Temperature Rise of Conductor above Ambient temperature
Dqd = Factor to account for dielectric loss for calculating T 4 in free air.
Dqds = Factor to account for dielectric loss and direct solar radiation for calculating
T4 in free air.
R = Alternating current resistance per unit length of conductor at max. operating
SDC

SDC
BN
BY

temperature (W/m)
Wd = Dielectric Loss per unit length for the insulation surrounding the
29/08/12

15/10/12

23/01/13
DATE

conductor (W/m)
T1 = Thermal Resistance per unit length between one conductor
NO.

and sheath (km/ W)


1

REVISIONS T2 = Thermal Resistance per unit length of the bedding between


DRAWN sheath & armour (km/ W)
BY:- T3 = Thermal Resistance per unit length of the external serving of the cable
DATE:- (km/W)
CHECKED T4 = Thermal Resistance per unit length between cable surface & surrounding
BY:- medium, as derived from 2.2 of part 2 (km/W)
DATE:- n = Number of load carrying conductors in the cable (conductors of equal
OPRG. DEPT size and carrying the same load)
BY l1 = The ratio of losses in the metal sheath to total losses in all conductors
DATE:- in that cable.
ENG'G. DEPT. l2 = The ratio of losses in the armouring to total losses in all conductors in that cable
BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 3 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-E (2004/10)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS

The Dielectric losses per unit length in each phase is given by :


CHK'D

APB

APB

NS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Wd = w C U02 tan
d
Where,
w = 2Pf = 377.04 s-1
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

U0 = Voltage to earth (V)


= 13.8x 1000/ Ö3 V = 7967.7 V
tan d = Loss factor of insulation = 0.004 (Ref. IEC 60287-1-1,
ISSUED FOR BASE DESIGN

Table-3, P.No-63)
C = Capacitance per unit length (F/m)
DESCRIPTION

The Capacitance for circular conductors is given by :-

e x 10-9
C =
18 ln (Di /dc)

Where,
ε = Relative Permittivity of the insulation
= 2.50 (Ref. IEC 60287-1-1, Table-3, P.No-65)
Di = External Diameter of the insulation (Excluding Screen)
SDC

SDC
BN
BY

= 26.6 mm (From Manufacturer's Data)


dc = Diameter of Conductor, including Screen (mm)
29/08/12

15/10/12

23/01/13

= 17.6 mm (From Manufacturer's Data)


DATE

C = 3.362826828E-10
NO.

REVISIONS Therefore substituting the above values in the formula,


DRAWN

BY:- Wd = 0.032 (W/m)


DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 4 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS

AC Resistance of Conductor
CHK'D

APB

APB

NS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
R=R΄(1+Ys+Yp) = 0.000128

Where
R΄=DC resistance of conductor at maximum operating temperature
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

Ys= Skin effect factor


Yp=Proximity effect factor
ISSUED FOR BASE DESIGN

DC Resistance of Conductor
DESCRIPTION

R΄=R0[1+α20(Ѳ-20)] = 0.00012636241 ohm/m

Where
R0= DC resistance of conductor at 200C = 9.91E-05 ohm/m
α20= Constant mass temperature coefficient at 20 0C per kelvin = 0.00393
Ѳ= Maximum operating temperature = 90.00 Deg.C

Skin effect factor Ys

Ys=Xs4/(192+0.8Xs4) = 0.007366105321926
Where
SDC

SDC
BN
BY

Xs2 = (8Πf/R΄) * 10-7*Ks = 1.19275977721539


29/08/12

15/10/12

23/01/13
DATE

f = Supply frequency = 60 Hz
Ks = Coefficient given in Table-2 as per IEC-60287-1-1 1
NO.

REVISIONS Proximity effect factor Yp


DRAWN 03
BY:- Xp4 1.18
Yp = *(dc/s)2* 0.312 * (dc/s)2+ = 0.0032844559378
DATE:- 192+0.8Xp4 Xp4
+0.27
CHECKED 192+0.8Xp4
BY:- Where
DATE:- Xp2 = 8Πf/R΄* 10-7*Kp = 0.954208
OPRG. DEPT

BY dc Diameter of conductor 16 mm 03
DATE:- s Distance between conductor axes(for cables in trefoil formation) 40 mm
ENG'G. DEPT. Kp Coefficient given in Table-2 as per IEC-60287-1-1 0.8
BY:-

DATE:- Loss Factor for Sheath and Screen


Where,
CERTIFIED.
l1 = l1' + l1'' l1 ' = Factor for losses due to Circulating Current
BY:- l1'' = Factor for losses due to Eddy Current
DATE:-
AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF DRAWING TITLE
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 5 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS

Factor for losses due to Circulating Current


CHK'D

APB

APB

NS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Rs x 1
l1 ' =
R (1+(Rs/X)2)
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

Where,
Rs = Resistance of sheath or screen per unit length of cable at its maximum
operating temperature of 900C (in W/m)
W/m (Manufacturer's data) 03
ISSUED FOR BASE DESIGN

= 0.000165
DESCRIPTION

R = Resistance of conductor per unit length of cable at its maximum


operating temperature of 900C (in W/m)
= 0.000128 W/m

X = Reactance of sheath or screen per unit length of cable (W/m)

X = 2 ω 10-7 ln (2s/d)

w = 2 π x frequency (1/s)
= 377.04 s-1
03
s= Distance between conductor axes(for cables in trefoil formation) 40 mm
SDC

SDC
BN
BY

d= Mean diameter of the sheath = 35.8 mm 03


29/08/12

15/10/12

23/01/13
DATE

Therefore X = 6.06339697214791E-05 03
NO.

REVISIONS
DRAWN Put the values in above equation for calculating the factor for losses due to
BY:- circulating current, we get
DATE:-

CHECKED l1' = 0.154 03


BY:-

DATE:- Factor for losses due to Eddy Current


OPRG. DEPT l1'' = 0 i.e. Eddy Current Loss is ignored.
BY

DATE:- The Loss Factor for Sheath and Screen can be written as :
ENG'G. DEPT.

BY:- l1 = l1' + l1''


DATE:- l1 = 0.154

CERTIFIED.
03
Loss Factor for Armour and Screen
BY:- l2 = 0 (As there is no Armour)
DATE:-
AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 6 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS

Calculation of Thermal Resistances


CHK'D

APB

APB

NS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. Calculation of Thermal Resistances between Conductor and Sheath, T 1

The Thermal Resistance between Conductor and Sheath, T 1 can be calculated as :


REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

ρT
T1 = ln (1 + 2 t1/ dc)

ISSUED FOR BASE DESIGN

Where,
DESCRIPTION

ρT = Thermal Resistivity of Insulation = 3.5 K.m/W

dc = Diameter of conductor = 16 mm

t1 = Thickness of Insulation between conductor and sheath (mm)


= 4.5 mm

T1 = 0.249 K.m/W

2. Calculation of Thermal Resistances between Sheath and Armour, T 2


SDC

SDC
BN
BY

T2 = 0 K.m/W
29/08/12

15/10/12

23/01/13
DATE

Since there is no Armour, Therefore, the Thermal resistance between the


Sheath and armour is considered as 0.
NO.

REVISIONS 3. Calculation of Thermal Resistance Outer Covering (Serving), T 3


DRAWN

BY:- The Thermal Resistance Outer Covering (Serving), T 3 can be calculated as:
DATE:-

CHECKED rT
T3 = ln (1 + 2 t3/ Da')
BY:- 2π
DATE:- Where,
OPRG. DEPT rT = Thermal Resistivity of Outer covering = 6 K.m/W
BY (For, PVC)
DATE:- Da' = External Diameter of metallic screen (for unarmoured cable)
ENG'G. DEPT. = 35.8 mm
03
BY:- t3 = Thickness of Serving = 2.10 mm 03
DATE:-

T3 = 0.106 K.m/W
CERTIFIED.
03

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF AS BUILT BY
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 7 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS

4. Calculation of Thermal Resistance of a cable in a duct


CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS

a) Thermal resistance of the air space between the cable surface & duct internal - T'4
b) The thermal resistance of the Duct itself - T ''4
c) The external thermal resistance of the duct - T''' 4

T4 = T'4 +T''4+ T'''4


REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

a) T'4 = U
(1 + 0.1(V+Yθm)De
ISSUED FOR BASE DESIGN

As per Table 4.
DESCRIPTION

U = 1.87
V = 0.312 03
Y = 0.0037
θm = 65 0
C
De = 40.0 mm 03 ( External diameter of the cable)

T'4 = 0.582555
03

b) T''4 = rT ln (D0/ Dd)



SDC

SDC
BN
BY

D0 = 217 ( Outside dia of Duct )


Dd = 200 ( Inside dia of Duct)
29/08/12

15/10/12

23/01/13

rT
DATE

= 6 ( Thermal resistivity of duct material -


As per Table 1)
NO.

REVISIONS T''4 = 0.077893


DRAWN

BY:-

DATE:- c) N (ρe - ρc) ln (u + √(u2 - 1))


T'''4 =
CHECKED 2π
BY:-

DATE:- N = 3 ( no of Loaded Cables )


OPRG. DEPT ρe = 1.2 Km/W (thermal resistivity of earth around duct bank)
BY ρc = 1 Km/W (thermal resistivity of concrete)
DATE:- U = LG/rb
ENG'G. DEPT. LG = 1000 mm ( Depth of laying to center of duct bank)
BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF AS BUILT BY
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 8 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS
CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS

rb is the equivalent radius of concrete bank (mm) given by:

ln rb = 1/2 * x/y * (4/π - x/y) ln (1 + y2/x2) + ln x/2

The quantities x and y are the shorter and longer sides, respectively of the duct bank section
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

irrespective of its position, in mm

x= 350 mm
ISSUED FOR BASE DESIGN

y= 750 mm
DESCRIPTION

ln rb = 5.904926246446

rb = 366.8401690233

Therefore U= 2.725982824243

T'''4 = 1.564187

03
T4 = 2.224634955264
SDC

SDC
BN
BY

29/08/12

15/10/12

23/01/13
DATE
NO.

REVISIONS
DRAWN

BY:-

DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF AS BUILT BY
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 9 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS

Therefore,
Soil Thermal Resistivity = 1.2 Km/W
CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS

Soil Temperature = 40 0
C

Maximum Allowable Conductor Temp = 90 0


C
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

No. of Circuits = 1

Dqamb = 40 0
C
ISSUED FOR BASE DESIGN

Dqc = 90 0
C
DESCRIPTION

Dq = Dqc-
Dqamb
Dq = 50 C
0

Wd = 0.032197

T1 = 0.249

T2 = 0
SDC

SDC
BN
BY

T3 = 0.106
03
29/08/12

15/10/12

23/01/13
DATE

T4 = 2.225
NO.

R = 0.00012771
1

REVISIONS
DRAWN l1 = 0.154 03
BY:-

DATE:- l2 = 0
CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 10 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC
Saudi Electricity Company ‫الشركة السعودية للكهرباء‬
APPR'D

PKS

PKS

PKS

The Amapcity of the cable can be calculated as :


CHK'D

APB

APB

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
NS

Dq-W (0.5 T + n (T +T +T )
d 1 2 3 4
I2 =
(R. T +n. R. T (1+l ) + n. R (1+l +l ). (T + T ))
1 2 1 1 2 3 4
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

I2 = 133078.003787672
I = 364.799 A 03
ISSUED FOR BASE DESIGN

Hence, The Current Ampacity of the Cable is 364.8 A


DESCRIPTION

Hence, The Current Ampacity of the Cable per phase is 364.8 A

Required Load Current as per PTS

kVA Rating of Station Service Transformer = 2000 kVA

Rated Voltage = 13.8 kV


SDC

SDC
BN
BY

Rated Current = 83.68 A


29/08/12

15/10/12

23/01/13
DATE

kVA rating of earthing transformer = 6000 kVA


NO.

Rated voltage of earthing transformer = 13.8 kV


1

REVISIONS
DRAWN Current corresponding to earthing = 251.03 A per phase
BY:- transformer
DATE:-

CHECKED As per PTS, 130% of Rated Load Current = 326.34 A per phase
BY:-

DATE:-

OPRG. DEPT

BY Hence 1C x 185 sqmm Cu/ XLPE Unarmoured, PVC Jacketed


DATE:- cable per phase is sufficient.
ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 11 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
APPR'D CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


PKS

PKS

PKS

4. Voltage Drop Calculation

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

APB

APB

NS

1. Conductor AC resistance = 0.1282 ohm/km


2. Conductor star reactance = 0.138 ohm/km

P.F Considered = 0.85


REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11

cosѲ = 0.85
sinѲ = 0.53
Voltage drop per amp = √3 (RcosѲ+XsinѲ)
per km = √3 (0.1282X0.85+0.138X0.53)
ISSUED FOR BASE DESIGN

= 0.127 V/A/Km
DESCRIPTION

A. From Transformer SGT01 to 13.8 kV Switchgear

Distance from transformer SGT01 = 0.180 km ( tentative )


to 13.8 kV SWGR

100 % load current = 83.68 A ( As per 2000kVA


SST Rating)

Total Voltage Drop = 1.908056 V

Percentage Voltage Drop (%) = 0.013826


SDC

SDC
BN
BY

B. From Transformer SGT01 to Grounding Transformer ET01


29/08/12

15/10/12

23/01/13
DATE

Distance from transformer SGT01 to = 0.020 km ( tentative )


Earthing Transformer
NO.

REVISIONS 100 % load current = 251.03 A ( As per


DRAWN 6000kVA
BY:- ET Rating)
DATE:- Total Voltage Drop = 0.636 V
CHECKED
BY:- Percentage Voltage Drop (%) = 0.005 %
DATE:-

OPRG. DEPT C. From 13.8kV Switchgear to SST-01


BY

DATE:- Distance from 13.8kV Switchgear to SST= 0.030 km ( tentative )


ENG'G. DEPT.

BY:- 100 % load current = 83.68 A ( As per 2000kVA SST Rating)


DATE:-

Total Voltage Drop = 0.318009


CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012


THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
A C470 CE - 310365 12 OF 14 03
CERTIFIED AND
DATED
AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)
EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4.0 SUMMARY OF RESULTS
CHK'D

APB

APB

NS

The Ampacity of 13.8kV, 1C X 185mm2, Cu/ XLPE cable is 364.8 A,


against the requirement of 326.34 A considering 130% of the load current as
per PTS.
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11
ISSUED FOR BASE DESIGN
DESCRIPTION

SDC

SDC
BN
BY

8/29/2012
29/08/12

23/01/13
DATE
NO.

REVISIONS
DRAWN

BY:-

DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 13 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx
CERT'D

RJC

RJC

RJC Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D

PKS

PKS

PKS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
ANNEXURE - B
CHK'D

APB

APB

NS
REVISED AS PER SEC LTR. NO. 12021001/230E/12, DT. 26/11/12
REVISED AS PER SEC LTR. NO. 12021001/153E/12 DT. 30/09/11
ISSUED FOR BASE DESIGN
DESCRIPTION

03
SDC

SDC
BN
BY

8/29/2012
29/08/12

23/01/13
DATE
NO.

REVISIONS
DRAWN

BY:-

DATE:-

CHECKED

BY:-

DATE:-

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE 15/10/2012

THIS DRAWING IS NOT


DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 13.8kV CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C470 CE - 310365 14 OF 14 03
CERTIFIED AND CONSTRUCTION OF NEW 380/132kV S/S AD-DAWADMI BSP (9037)
DATED

AD DAWADMI SAUDI ARABIA JOB ORDER NO. 11131169100 DWG. CONT. SHT. CE-310298
SEC-ERB CAD-E (2002/03)

EDMS VECTOR EXCEL

510913609.xlsx