The document summarizes lighting calculations for 8 rooms across two floors of a building. It calculates the room area, recommended light coverage ratio, utilization coefficient, light loss factor, and number of LED lamps needed to provide sufficient lighting for each room based on standardized lighting equations. A total of 29 lamps at 14 watts each are needed for the first floor, providing 417 watts of lighting plus other electrical loads. The second floor requires 27 lamps at 14 watts each, for a total power load of 3922 watts across both floors.
The document summarizes lighting calculations for 8 rooms across two floors of a building. It calculates the room area, recommended light coverage ratio, utilization coefficient, light loss factor, and number of LED lamps needed to provide sufficient lighting for each room based on standardized lighting equations. A total of 29 lamps at 14 watts each are needed for the first floor, providing 417 watts of lighting plus other electrical loads. The second floor requires 27 lamps at 14 watts each, for a total power load of 3922 watts across both floors.
The document summarizes lighting calculations for 8 rooms across two floors of a building. It calculates the room area, recommended light coverage ratio, utilization coefficient, light loss factor, and number of LED lamps needed to provide sufficient lighting for each room based on standardized lighting equations. A total of 29 lamps at 14 watts each are needed for the first floor, providing 417 watts of lighting plus other electrical loads. The second floor requires 27 lamps at 14 watts each, for a total power load of 3922 watts across both floors.
1. Teras L = 3.35 x 2 = 6.7 m2 2 lampu Phillips LED
RCR = 6.7 / (5.35 x 3) = 0.42 DN 390B LED 6 / 840 PSU D100 WH GM CU = 67% 5.5 watt LLF = 75% CT = 4000 K T = 600 60 = 600 x N x 0.67 x 0.75 / 6.7 N = 1.33 = 2 lampu 2. Garasi L = 3.15 x 6 = 18.9 m2 2lampu Phillips LED RCR = 18.9 / (9 x 3) = 0.7 DN 392B LED 16 / 840 PSU D150 WH GM CU = 64% 14 watt LLF = 75% CT = 4000 K T = 1600 60 = 1600 x N x 0.64 x 0.75 / 18.9 N = 1.47 = 2 lampu 3. Ruang kerja L = 3.85 x 3.5 = 13.475 m2 4 lampu Phillips LED RCR = 13.475 / (7.35 x 2.25) = 0.815 DN 392B LED 16 / 840 PSU D150 WH GM CU = 64% 14 watt LLF = 88% CT = 4000 K T = 1600 250 = 1600 x N x 0.64 x 0.88 / 13.475 N = 3.7 = 4 lampu 4. Ruang tamu L = 5 x 3.85 + 2.15 x 2 = 23.55 m2 7 lampu Phillips LED RCR = 23.55 / (8.35 x 2.25) = 1.25 DN 392B LED 16 / 840 PSU D150 WH GM CU = 61% 14 watt LLF = 88% CT = 4000 K T = 1600 250 = 1600 x N x 0.61 x 0.88 / 23.55 N = 6.85 = 7 lampu Lantai 1 NO. Ruang Hitungan Jumlah Jenis
5. Ruang keluaga L = 3.5 x 3.5 = 12.25 m2 4 lampu Phillips LED
RCR = 12.25 / (7 x 2.55) = 0.68 DN 392B LED 16 / 840 PSU D150 WH GM CU = 65% 14 watt LLF = 88% CT = 4000 K T = 1600 250 = 1600 x N x 0.65 x 0.88 / 12.25 N = 3.34 = 4 lampu 6. Ruang makan L = 6.5 x 3.5 = 22.75 m2 8 lampu Phillips LED RCR = 22.75 / (10 x 2.2) = 1.03 DN 392B LED 16 / 840 PSU D150 WH GM CU = 63% 14 watt LLF = 88% CT = 4000 K T = 1600 250 = 1600 x N x 0.63 x 0.88 / 22.75 N = 7.4 = 8 lampu 7. Dapur L = 3.5 x 2.5 = 8.75 m2 3 lampu Phillips LED RCR = 8.75 / (6 x 2.2) = 0.66 DN 392B LED 16 / 840 PSU D150 WH GM CU = 66% 14 watt LLF = 80% CT = 4000 K T = 1600 250 = 1600 x N x 0.66 x 0.8 / 8.75 N = 2.58 = 3 lampu 8. Kamar mandi L = 2.15 x 1.8 = 3.87 m2 1 lampu Phillips LED RCR = 3.87 / (3.95 x 1.46) = 0.67 DN 392B LED 16 / 840 PSU D150 WH GM CU = 65% 14 watt LLF = 80% CT = 4000 K T = 1600 250 = 1500 x N x 0.65 x 0.8 / 3.87 N = 1.1 = 1 lampu Lantai 1 Total lampu Pompa air @ 14 watt = 29 lampu @ 5.5 watt = 2 lampu P = 200 watt = 220 x I Total wattage 406 watt Total wattage 11 watt I = 0.91 A [C2] Total daya lampu lantai 2 = 417 watt Teras + garasi + R. tamu Elektronik Daya Jumlah Total daya Pl = 11 x 14 = 156 Pe = 600 AC inverter 1 pk 600 3 1800 Ptot = 756 watt = 220 x I I = 3.44 A [C4] Tv LED 32” 50 1 50 R. Kerja + kamar mandi Kulkas 285 1 285 Pl = 5x14 = 70 Rice cooker 350 1 350 Pe = 600 Ptot = 670 watt = 220 x I Dispenser 420 1 200 I = 3.05 A [C4] miyako Pompa air 200 1 200 Dapur Pl = 3 x 14 = 52 Microwave 400 1 400 Pe = 285+350+420+400 = 1455 Ptot = 1507 watt = 220 x I Total daya elektronik lain 3505 watt I = 6.85 A [C10]
Total daya lantai 1 = 3922 watt R. Makan + R. keluarga
Pl = 12 x 14 = 168 Pe = 600 + 50 = 650 P=VxI Ptot = 818 watt = 220 x I 3922 = 220 x I I = 3.72 A [C4] I = 17.8 A [C20] Lantai 2 NO. Ruang Hitungan Jumlah Jenis
1. Kamar tidur utama L = 3.85 x 6.1 = 23.485 m2 6 lampu Phillips LED
RCR = 23.485 / (9.95 x 2.6) = 0.9 DN 392B LED 16 / 840 PSU D150 WH GM CU = 63% 14 watt LLF = 92% CT = 4000 K T = 1600 200 = 1500 x N x 0.63 x 0.92 / 23.485 N = 5.4 = 6 lampu 2. Walk in – closet L = 3.85 x 1.9 = 7.315 m2 2 lampu Phillips LED RCR = 7.315 / (5.75 x 3) = 0.42 DN 392B LED 16 / 840 PSU D150 WH GM CU = 67% 14 watt LLF = 90% CT = 4000 K T = 1600 200 = 1500 x N x 0.67 x 0.9 / 7.315 N=1.6 = 2 lampu 3. Balkon L = 3 x 1 = 3 m2 1 lampu Phillips LED RCR = 3 / (4 x 2.6) = 0.28 DN 390B LED 6 / 840 PSU D100 WH GM CU = 68% 5.5 watt LLF = 75% CT = 4000 K T = 600 60 = 600 x N x 0.68 x 0.75 / 3 N = 0.58 = 1 lampu 4. Kamar mandi utama L = 3.85 x 2 = 7.7 m2 2 lampu Phillips LED RCR = 7.7 / (5.85 x 2.82) = 0.46 DN 392B LED 16 / 840 PSU D150 WH GM CU = 67 % 14 watt LLF = 88 % CT = 4000 K T = 1600 250 = 1600 x N x 0.67 x 0.88 / 7.7 N = 2.04 = 2 lampu Lantai 2 NO. Ruang Hitungan Jumlah Jenis
5. Lorong L = 2.15 x 8 = 17.2 m2 6 lampu Phillips LED
RCR = 17.2 / (10.15 x 3) = 0.56 DN 392B LED 16 / 840 PSU D150 CU = 65% WH GM LLF = 88% 14 watt CT = 4000 K 250 = 1600 x N x 0.65 x 0.88 / 17.2 T = 1600 N = 5.69 = 6 lampu 6. Kamar tidur anak L = 3.5 x 4 = 14 m2 4 lampu Phillips LED RCR = 14 / (7.5 x 2.2) = 0.84 DN 392B LED 16 / 840 PSU D150 CU = 64% WH GM LLF = 90% 14 watt CT = 4000 K 200 = 1500 x N x 0.64 x 0.9 / 14 T = 1600 N = 3.24 = 4 lampu 7. Ruang hobi L = 2.5 x 2 = 5 m2 2 lampu Phillips LED RCR = 5 / (4.5 x 2.2) = 0.51 DN 392B LED 16 / 840 PSU D150 CU = 65% WH GM LLF = 90% 14 watt CT = 4000 K 250 = 1600 x N x 0.65 x 0.9 / 5 T = 1600 N = 1.3 = 2 lampu 8. Kamar mandi anak L = 2.15 x 2 = 4.3 m2 1 lampu Phillips LED RCR = 4.3 / (4.15 x 2.82) = 0.36 DN 392B LED 16 / 840 PSU D150 CU = 67% WH GM LLF = 88% 14 watt CT = 4000 K 250 = 1600 x N x 0.67 x 0.88 / 4.3 T = 1600 N = 1.14 = 1 lampu Lantai 2 NO. Ruang Hitungan Jumlah Jenis
9. Ruang cuci L = (2.7 x 3.5)+1.2+(2 x 1.75) = 14.95 m2 6 lampu Phillips LED
RCR = 14.95 / ((4.5+4.7) x 3) = 0.54 DN 392B LED 16 / 840 PSU D150 CU = 65% WH GM LLF = 80% 14 watt CT = 4000 K 250 = 1600 x N x 0.65 x 0.8 / 14.95 T = 1600 N = 5.5 = 6 lampu Total lampu @ 14 watt = 33 lampu @ 5.5 watt = 1 lampu Total wattage 462 watt Total wattage 5 watt Total daya lampu lantai 2 = 467 watt Lorong + kamar mandi anak Kamar tidur anak 2 + R. Hobi Elektronik Daya Jumlah Total daya Pl = 7 x 14 = 98 watt = 220 x I Pl = 6 x 14 = 84 AC inverter 1 600 w 3 1800 w I = 0.45 A [C2] Pe = 600 PK Ptot = 684 watt = 220 x I Tv 32” LED 50 w 1 50 w Kamar tidur utama + walk in closet + kamar mandi utama I = 3.10 A [C4] Pl = 11 x 14 = 154 Mesin cuci 460 w 1 460 w Pe = 600 + 50 = 650 R. Cuci + R. Jemur Ptot = 804 watt = 220 x I Pl = 6 x 14 = 84 Total daya elektronik lain 2310 watt I = 3.65 A [C4] Pe = 460 Ptot = 544 watt = 220 x I Total daya lantai 2 = 2777 watt Kamar tidur anak 1 I = 2.47 A [C4] Pl = 4 x 14 = 56 P=VxI Pe = 600 2721 = 220 x I P tot = 656 watt = 220 x I I = 12.4 A [C16] I = 2.98 A [C4]