Professional Documents
Culture Documents
9.3.2 Earth Fault Loop Impedance Corrections For Temperature
9.3.2 Earth Fault Loop Impedance Corrections For Temperature
3 of BS 7671 Maximum earth fault loop impedance (Zs) for circuit-breakers with Uq of 230 V,
for instantaneous operation giving compliance with the 0.4 s disconnection time of Regulation
411.3.2.2 and 5 s disconnection time of Regulation 411.3.2.3
Note: The circuit loop impedances given in the table should not be exceeded when the conductors are at their
norm al operating tem perature. If the conductors are at a different tem perature when tested, the reading
should be adjusted accordingly. See Appendix 14.
The simplest approach is to apply the correction factor Cr also used in Chapter 6 .
See Table F.3 in Appendix F which shows conductor temperature correction factor Cr,
correcting from 20 °C to conductor operating temperature.
See Table F.2 in Appendix F, which shows the ambient temperature multipliers Cf2 to
be applied to Table F.l resistances to convert resistances at 20 °C to other ambient
temperatures. See also section 10.2.