K Factor For Light Hasard
K Factor For Light Hasard
Ordinary-Temperature Intermediate-Temperature
Location Rating Rating High-Temperature Rating
8.3.4 Sprinklers with K-Factors Less than K-5.6 (80). 8.3.4.3 Sprinklers with nominal K-factors of less than K-5.6
8.3.4.1 Sprinklers shall have a minimum nominal K-factor of (80) shall be permitted to be installed in conformance with
5.6 (80) unless otherwise permitted by 8.3.4. 11.3.2 for protection against exposure fires.
8.3.4.2 For light hazard occupancies not requiring as much 8.3.4.4 Sprinklers with nominal K-factors of K-4.2 (57) shall
water as is discharged by a sprinkler with a nominal K-factor of be permitted to be installed on dry pipe and preaction systems
K-5.6 (80) operating at 7 psi (0.5 bar), sprinklers having a protecting light hazard occupancies where piping is corrosion
smaller orifice shall be permitted, subject to the following re- resistant or internally galvanized.
strictions:
8.3.5 Thread Size Limitations. Sprinklers having a K-factor ex-
--```,`,,,``,`,,,`,``,,``,,,`,`,-`-`,,`,,`,`,,`---
(1) The system shall be hydraulically calculated. ceeding K-5.6 (80) and having 1⁄2 in. (15 mm) National Pipe
(2) Sprinklers with nominal K-factors of less than K-5.6 (80) Thread (NPT) shall not be installed in new sprinkler systems.
shall be installed only in wet pipe sprinkler systems or in
accordance with the limitations of 8.3.4.3 or 8.3.4.4. 8.4* Application of Sprinkler Types. Sprinklers shall be se-
(3) A listed strainer shall be provided on the supply side of lected for use as indicated in this section and shall be posi-
sprinklers with nominal K-factors of less than K-2.8 (40). tioned and spaced as described in Section 8.5.
2016 Edition