Professional Documents
Culture Documents
Daisy Chain Modbus Devices
Daisy Chain Modbus Devices
Ensure all devices are linked in a daisy chain – (NO star or spurs coming off main line)
Ensure there is a common ground running to every device
Ensure a twisted pair signal cable is used
Ensure screen are grounded at one end only
OPTION 1
Disable termination resistors on all devices
Fit a 125Ohm termination resistor across Data + and Data- wires at the end of the daisy chain
OPTION 2
Disable termination resistors on all devices except the last in line
Enable Termination resistor on the last device