Smartsense - Chiller Insights Report For York Chiller 1, SKF Technologies India PVT LTD, Jun 2020
Smartsense - Chiller Insights Report For York Chiller 1, SKF Technologies India PVT LTD, Jun 2020
%&%&
1. As per the latest Set Point value, the chiller is able to maintain the required Set Point
2. No Condenser Fouling was observed, as the Condenser Approach always lies below the critical limit.
3. The Oil Pressure difference is above the critical value, this implies a oil filter clogging in the chiller.
4. The Chilled water flow rate is not within the optimal range and is below the rated value by -51.07%. It is
advised to increase the Chilled water flow rate.
5. No Cooling Tower Fouling was observed, as the Cooling Tower Approach always lies below the critical limit.
6. No Evaporator Fouling was observed, as the Evaporator Approach always lies below the critical limit.
7. The Condenser water flow rate is not within the optimal range and is below the rated value by -45.39%. It
is advised to increase the Condenser water flow rate.
Comments: Evaporator load is always below the rated value(850.0). For most of the time Evaporator load is
around the values 301.58, which is 35.5% of the rated value.
Comments: KW - Comp is always below the rated value(495.0). It is bound between the upper and lower
bounds for 98.41% of the time. For most of the time KW - Comp is around the values 296.06, which is 59.8% of
the rated value.
2.3 kW/TR
Comments: KW/TR is decreasing with time. It is above the rated value(0.7) for most of the time. For most of
the time KW/TR is around the values 0.99, which is 141.4% of the rated value.
Comments: COP is increasing with time. It is always below the rated value(6.04). For most of the time COP is
around the values 3.55, which is 58.9% of the rated value.
Comments: Utilization shows total chiller run time. However analytics is performed only on steady state chiller
condition
Comments:. As per the latest Set Point value, the chiller is able to maintain the required Set Point
Comments: Chilled Water Temp. Difference is bound between the upper and lower bounds for 97.48% of the
time.
Comments: Chilled Water Flow Rate is slightly increasing with time. It is always below the rated value(2040.0).
It is below the lower bound for 100.00% of the time For most of the time Chilled Water Flow Rate is around
the values 987.40, which is 48.4% of the rated value. Thus It is advised to increase Chilled Water Flow Rate.
Comments: Evaporator Approach Temperature is bound between the upper and lower bounds for 100.00% of
the time. Thus No Evaporator Fouling observed.
Comments: Condenser Water Temp. Difference is bound between the upper and lower bounds for 97.90% of
the time.
Comments: There were no sudden jumps or dips in Condenser Water Outlet Temp. value during the time.
Comments: Condenser Water Flow Rate is slightly increasing with time. It is always below the rated
value(2550.0). It is below the lower bound for 100.00% of the time For most of the time Condenser Water
Flow Rate is around the values 1379.88, which is 54.1% of the rated value. Thus It is advised to increase
Condenser Water Flow Rate.
Comments: Condenser Approach Temperature is bound between the upper and lower bounds for 100.00% of
the time. Thus No Condenser Fouling observed.
Comments: Differential Oil Pressure 1 is above the upper bound for 100.00% of the time. Thus it implies Oil
filter Clogging.
5.4 Frequency
Comments: Cooling Tower Approach Temperature is slightly decreasing with time. It is below the rated
value(10.0) for most of the time and is above rated value only for 19.33% of the time For most of the time
Cooling Tower Approach Temperature is around the values 7.73, which is 77.3% of the rated value. Thus No
Cooling Tower Fouling observed.
Comments: Cooling Tower Effectiveness is always below the rated value(65.0). For most of the time Cooling
Tower Effectiveness is around the values 45.88, which is 70.6% of the rated value.