Professional Documents
Culture Documents
Specification For Surge/Transient Protection: Part 1 - General 1.1 Related Documents
Specification For Surge/Transient Protection: Part 1 - General 1.1 Related Documents
PROTECTION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. IEEE C62.41-1991
B. BS6651-1992 Appendix C
3. Where SPDs are intended for use in hazardous areas, the SPD manufacturing
facility shall be certified by a recognised approvals body.
PART 2 - PRODUCTS
2.1 GENERAL
A. Provide a surge/transient protection system where indicated in the Contract Documents
containing surge/transient protection devices (SPDs) on all services entering the
protected system with cabled connections to/from other systems and devices external to
the main system installation room/building;-
2. SPDs shall be auto-resetting without manual intervention and shall either indicate
failed devices by external automatic monitoring or through internal fail-safe
operation.
3. SPDs requiring periodic disconnection for testing or manual resetting are not
acceptable.
1. Local surge protection shall be provided on all loops exceeding 500 feet (150m) in
total or further than 200 feet (60m) from the main control system location.
Particular attention shall be paid to measurement and control devices located in
tank farms, on waste water / effluent discharges or process / combustion stack
emission monitoring.
2. Protect all 4/20mA signal lines and instrument AC power feeds where applicable
Page 2 of 8
Location Surge Level Exposure Level
Primary service entrance 20kA high exposure locations
Main service / back panel 10kA medium exposure locations
Sub-panel 6kA low exposure locations
Field/individual panel 6kA local
7. All SPDs shall carry the 'CE' mark and their certificates of conformity shall be
available for inspection at any time.
Hybrid SPDs shall be rated for minimum 10kA (8/20µs) peak impulses,
MOV-based SPDs for 6kV (1.2/50µs) /3kA (8/20µs) peak impulses.
Page 3 of 8
SPDs shall be encapsulated or otherwise protected from casual interference, and
all SPD components shall be within one housing per loop.
Means shall be provided for individual loop identification, which shall positively
identify that loop and be transferable to any replacement device. Adhesive labels
are not acceptable.
SPDs with less than 2 Ohm series resistance shall be provided with individual fuses
where connected to bulk I/O power supplies not already protected by hold-up
resistors or individual line fusing.
Where SPDs are intended for use in hazardous areas, both the SPD manufacturing
facility and the surge protection device shall be certified by a recognised approvals
body. The SPD shall be rated to at least EEx ia IIC T4 (intrinsically safe) or EEx d
IIC T4 (explosionproof).
C. DATA-COMMUNICATION SPDS:
1. Duties herein described are private wire / leased line telephone, Ethernet
(Thick/Thin), Arcnet, TwinAx and other proprietary communication protocols /
electrical specifications.
SPDs shall provide full hybrid protection using both gas-filled discharge tube
(GDT) plus secondary semiconductor devices.
Hybrid SPDs shall be rated for minimum 10kA (8/20µs) peak impulses.
SPDs for PSTN applications shall have the appropriate bandwidth required by the
telephone system.
Page 4 of 8
SPDs shall be encapsulated or otherwise protected from casual interference, and
all SPD components shall be within one housing per loop.
Means shall be provided for individual loop identification, which shall positively
identify that loop and be transferable to any replacement device. Adhesive labels
shall not be acceptable.
Where SPDs are intended for use in hazardous areas, both the SPD manufacturing
facility and the surge protection device shall be certified by a recognised approvals
body. The SPD shall be rated to at least EEx ia IIC T4 (intrinsically safe) or EEx d
IIC T4 (explosionproof).
D. FIELD-MOUNTING SPDS:
part of loop wiring in excess of 500 feet (150m) installed in locations where access
is difficult (defined as:- where ladders or other access gear is necessary or where
apparatus is located in confined spaces or requiring more than one person for
replacement)
Page 5 of 8
2. SPDs shall be as specified above for appropriate duty i.e. AC power, 4/20mA,
dial-up telephone, etc. 2-wire 4/20mA transmitters shall be protected with hybrid
electronic devices encapsulated and designed for location directly into transmitter
conduit entries unless installation conditions prohibit use of conduit entry on
transmitter.
3. SPDs shall be single-ended or be supplied with all necessary mounting and loop
wiring accessories required. It shall not be for the wiring installer or others to
provide additional accessories to complete installation into 2-wire circuits.
Conduit T-pieces can be used where necessary.
5. Where SPDs are intended for use in hazardous areas, both the SPD manufacturing
facility and the surge protection device shall be certified by a recognised approvals
body. The SPD shall be rated to at least EEx ia IIC T4 (intrinsically safe) or EEx d
IIC T4 (explosionproof).
Page 6 of 8
PART 3 - EXECUTION
3.1 Panel /Control Room Installation
A. Contractor shall install equipment in accordance in applicable Codes and Manufacturers'
installation guides.
B. Route conduit and wiring as required to make neat and operational system. Tubing shall
be void of kinks, sags and other irregularities. All bends shall be made with a tube bender
or with standard fittings.
C. Field wiring prior to SPDs (exposed wiring) must be segregated by at least 2 inches
(50mm) from, and not run in the same conduit/raceway as, wiring from SPDs (protected
wiring).
D. Ground (earth) wiring from SPD dedicated busbar or insulated DIN rail must be
independently run to the Main Electrical System Ground (earth) bar as per Manufacturers'
installation guide. Ground (Earth) wire shall be 12AWG (2mm) minimum and clipped or
otherwise secured every 3 feet (0.9m) if installed using raceway. Resistance of ground
(earth) wire shall not exceed 0.1 Ohm between SPD ground (earth) and Main Electrical
System Ground (Earth) bar.
E. Main Electrical System Ground (Earth) bar may or may not be connected to a local
Ground (Earth) Rod(s) or Mat, as required by local Codes. Where so connected, bonding
link shall be 10AWG (2.6mm) minimum, and have resistance of 0.1 Ohm or less.
B. Route conduit and wiring as required to make neat and operational system. Tubing shall
be void of kinks, sags and other irregularities. All bends shall be made with a tube bender
or with standard fittings.
C. Where separate enclosures are provided, field wiring prior to SPDs (exposed wiring)
must be segregated by at least 2 inches (50mm) from, and not run in the same
conduit/raceway as, wiring from SPDs (protected wiring). Installer shall dress wiring of
internally-connected SPDs as separately as possible.
D. Ground (Earth) wiring from local enclosure SPD dedicated busbar or insulated DIN rail
must be independently run to a local Grounding (Earthing) Point or Building Steel.
Ground (earth) wire shall be 12AWG (2mm) minimum and clipped or otherwise secured
every 3 feet (0.9m) if installed using raceway. Resistance of ground (earth) wire shall not
exceed 0.1 Ohm between SPD ground (earth) and local Building Steel. Mounting posts or
stanchions are acceptable as Building Steel.
Page 7 of 8
E. 2-wire 4/20mA transmitter-mounted SPDs shall be grounded (earthed) as recommended
by Manufacturer.
B. Provide 2 complete Operations and Maintenance manuals including parts list and as-built
drawings.
A. Every year after final acceptance until expiration of warranty (see below) system shall be
inspected with regard to wiring security, labelling, mounting integrity and ground (earth)
connections, including resistance measurement.
C. System shall be provided with one (1) year warranty and all applicable recommended
spare and consumable parts for one (1) year's operation.
Page 8 of 8