Professional Documents
Culture Documents
B126 06 BT EE 02ev2 Desbloqueado
B126 06 BT EE 02ev2 Desbloqueado
ENERGY UNIT
Test report
No. B126-06-BT-EE-02Ev2 Page 1 of 19
Temperature rise test
The tests objects have been subjected to the tests required by theclient,
applying the procedures specified in the standard indicated before.
* The present report refers only and exclusively to the sample tested and at the moment and conditions in which the measures were made.
* The partial reproduction of the present document is categorically forbidden without the permission in writing of de LABEIN.
4. RESULTS............................................................................................... 10
ANNEX DRAWINGS
PHOTOGRAPHS
Line switchgear
Designation: CGM3621 L
Type: CGM3621
Serial No.: 3621-1010
Rated voltage, Ur: 36 kV
Rated power frequency withstand voltage, Ud: 70 kV
Rated lightning impulse withstand voltage, Up: 170 kV
Rated normal current, Ir: 630 A
Rated short-time withstand current, 1s, Ik: 21 kA
Rated peak withstand current, Ip: 54.6 kA
Rated pressure for insulation, Pre: 0.13 MPa
Minimum pressure for insulation, Pme: 0.11 MPa
Rated frequency, fr: 50/60 Hz
Protection switchgear
Designation: CGM3621 P
Type: CGM3621
No.: 3621-1011
Rated voltage, Ur: 36 kV
Rated power frequency withstand voltage, Ud: 70 kV
Rated lightning impulse withstand voltage, Up: 170 kV
Rated frequency, fr: 50/60 Hz
Main busbar rated normal current, Ir: 630 A
The tests have been performed at minimum functional pressure of the test objects.
- IEC 62271-
62271-200:2003
200:2003,
:2003, “High
“High-
High-voltage switchgear and controlgear-
controlgear- Part 200:
AC metal-
metal-enclosed switchgear and controlgear for rated voltages above 1 kV
and up to and including 52 kV”.
kV”.
The tests are carried out with the switchgear mounted with all of its equipment as
used in normal service, with all the phases and the rated current flowing through
the main circuit.
The bottom side of the switchgears is covered with a thermal insulator in order to
simulate equivalents operation conditions (see photographs in the annex).
The tests are carried out with three-phase circuits, with a power supply current
which has approximately a sine wave form and a frequency of 60 Hz.
Test No. 1
Test scheme:
Short-circuit
Test No. 2
Test scheme:
Short-circuit
Test scheme:
Short-circuit
The three tests are performed indoors with an ambient substantially free from air
currents, excepting those generated by the heat of the object under test.
Provisional connections to the main circuit are performed in such a way that no
significant amount of heat is supplied or extracted from the object under test. The
temperature rise of the terminals of the main circuit and of the provisional
connections at a distance of 1m from the terminals must be measured and the
difference must be no more than 5 K.
The ambient air temperature is the average temperature of the air outside the
switchgear enclosure. It is measured by means of three thermocouples equally
distributed around the object, at a height approximately equal to the average
height of its current-carrying parts and at a distance of about 1m from the object.
The thermocouples are protected against air currents and abnormal effects of
heat.
In the last quarter of the whole period of test, the variation of the air ambient
temperature has not exceeded 1K in 1 h.
CORRECT. The temperature-rise of each part of the switchgear for which limits
are specified (and whose values have been measured) does not
exceed these limits.
The results obtained in test No. 1 are shown in the following table.
Note (1): The difference between the temperature rises of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.
Note
Note (1): The difference between the temperature rises of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.
Nota (1): The difference between the temperature rise of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.
CORRECT. The values measured before the beginning of the test and after the
end of the temperature-rise test do not differ by more than 20 %.
CGM3621 P
Phase R-r Phase S-s Phase T-t Phase R-r Phase S-s Phase T-t
CGM3621 L
Phase R-r Phase S-s Phase T-t Phase R-r Phase S-s Phase T-t
Fuse 80 A