Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

ELECTRICAL EQUIPMENT LABORATORY

ENERGY UNIT

Test report
No. B126-06-BT-EE-02Ev2 Page 1 of 19
Temperature rise test

TEST OBJECT: Gas filled metal-clad switchgear insulated in SF6 of 36


kV
DESIGNATION:
DESIGNATION: CGM3621 L and CGM3621 P
REQUESTED BY:
BY: Ormazabal y Cía., S.A.
Bº Basauntz, 2 – 48140 IGORRE (Vizcaya)
MANUFACTURER:
MANUFACTURER: Ormazabal y Cía., S.A.
STANDARD:
STANDARD: IEC 62271-200:2003
RECEIVING DATE:
DATE: November 15th 2006
TESTS DATE:
DATE: November 15th-21st 2006

The tests objects have been subjected to the tests required by theclient,
applying the procedures specified in the standard indicated before.

Result: The obtained results are shown in this report.

THIS DOCUMENT CONSISTS OF:


OF:
No. of pages: 19 (and Annex of 6 pages)
Drawings: Annex
Photographs: Annex

Estibaliz Montes Luis Martínez


Test Chief Head of Electrical Equipment Laboratory
Barakaldo, June 10th 2013

* The present report refers only and exclusively to the sample tested and at the moment and conditions in which the measures were made.
* The partial reproduction of the present document is categorically forbidden without the permission in writing of de LABEIN.

Printed by i:0#.w|velatia\ims 28/10/2016


INDEX
NDEX

1. TEST OBJECT DESIGNATION .................................................................... 3

2. TESTS PERFORMED. STANDARD .............................................................. 5

3. TEST DESCRIPTION ................................................................................. 6

4. RESULTS............................................................................................... 10

ANNEX DRAWINGS
PHOTOGRAPHS

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 2 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


1. TEST OBJECT DESIGNATION
DESIGNATION

GAS FILLED METAL-CLAD SWITCHGEAR INSULATED IN SF6.

The characteristics of the switchgears, provided by the manufacturer, are the


following:

Line switchgear

Designation: CGM3621 L
Type: CGM3621
Serial No.: 3621-1010
Rated voltage, Ur: 36 kV
Rated power frequency withstand voltage, Ud: 70 kV
Rated lightning impulse withstand voltage, Up: 170 kV
Rated normal current, Ir: 630 A
Rated short-time withstand current, 1s, Ik: 21 kA
Rated peak withstand current, Ip: 54.6 kA
Rated pressure for insulation, Pre: 0.13 MPa
Minimum pressure for insulation, Pme: 0.11 MPa
Rated frequency, fr: 50/60 Hz

Protection switchgear

Designation: CGM3621 P
Type: CGM3621
No.: 3621-1011
Rated voltage, Ur: 36 kV
Rated power frequency withstand voltage, Ud: 70 kV
Rated lightning impulse withstand voltage, Up: 170 kV
Rated frequency, fr: 50/60 Hz
Main busbar rated normal current, Ir: 630 A

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 3 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


Rated short-time withstand current, 1s, Ik: 21 kA
Rated peak withstand current, Ip: 54.6 kA
Transformer rated derivation current: 200 A
Rated pressure for insulation, Pre: 0.13 MPa
Minimum pressure for insulation, Pme: 0.11 MPa

The tests have been performed at minimum functional pressure of the test objects.

See photographs and drawings of the test objects in the annex.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 4 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


2. TESTS PERFORMED.
PERFORMED. STANDARD

Test performed has been the following:

− Temperature rise test.

Test has been performed according to:

- IEC 62271-
62271-200:2003
200:2003,
:2003, “High
“High-
High-voltage switchgear and controlgear-
controlgear- Part 200:
AC metal-
metal-enclosed switchgear and controlgear for rated voltages above 1 kV
and up to and including 52 kV”.
kV”.

Quoted standard for the tests is the following:

- IEC 60694:2002, “Common specifications for high-voltage switchgear and


controlgear standards”.

The calculation of the uncertainties of the measurements is available.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 5 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


3. TEST DESCRIPTION

The tests are carried out with the switchgear mounted with all of its equipment as
used in normal service, with all the phases and the rated current flowing through
the main circuit.

The bottom side of the switchgears is covered with a thermal insulator in order to
simulate equivalents operation conditions (see photographs in the annex).

The tests are carried out with three-phase circuits, with a power supply current
which has approximately a sine wave form and a frequency of 60 Hz.

Three consecutive tests have been carried out:

Test No. 1

Test scheme:

Short-circuit

The test currents are the following:

− Line switchgear: Ir = 630 A each phase


− Protection switchgear: If = 38.5 A each phase (out of phase 120º)
Fuses of 63 A are placed

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 6 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


The power supply is performed:

− Line switchgear: By means of 1 strip of 50X6 mm2 for each phase.


− Protection switchgear: By means of 1 strip of 30X10 mm2 for eac
phase.

Test No. 2

Test scheme:

Short-circuit

The test currents are the following:

− Line switchgear: Ir = 630 A each phase


− Protection switchgear: If = 46 A each phase (out of phase 120º)
Fuses of 80 A are placed

The power supply is performed:

− Line switchgear: By means of 1 strip of 50X6 mm2 for each phase.


− Protection switchgear: By means of 1 strip of 30X10 mm2 for eac
phase.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 7 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


Test No. 3

Test scheme:

Short-circuit

The test currents are the following:

− Line switchgear: Ir = 630 A each phase


− Protection switchgear: If = 200 A each phase (out of phase 120º)
Links are placed

The power supply is performed:

− Line switchgear: By means of 1 strip of 50X6 mm2 for each phase.


− Protection switchgear: By means of 1 strip of 30X10 mm2 for eac
phase.

The three tests are performed indoors with an ambient substantially free from air
currents, excepting those generated by the heat of the object under test.

Provisional connections to the main circuit are performed in such a way that no
significant amount of heat is supplied or extracted from the object under test. The
temperature rise of the terminals of the main circuit and of the provisional
connections at a distance of 1m from the terminals must be measured and the
difference must be no more than 5 K.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 8 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


The temperature of each element for which there are specified limits has to be
measured with thermocouples. See the thermocouples arrangement in the drawing
of the annex.

The ambient air temperature is the average temperature of the air outside the
switchgear enclosure. It is measured by means of three thermocouples equally
distributed around the object, at a height approximately equal to the average
height of its current-carrying parts and at a distance of about 1m from the object.
The thermocouples are protected against air currents and abnormal effects of
heat.

In order to avoid reading errors due to sudden changes of temperature,


thermocouples have been put into small bottles containing about 0.5 l of oil.

In the last quarter of the whole period of test, the variation of the air ambient
temperature has not exceeded 1K in 1 h.

The temperature-rise of each component refers to the air ambient temperature


outside the enclosure and must not exceed the specified limits.

The temperature-rise of accessible metallic parts will not exceed of 30 K. For


accessible metallic parts, not foreseen to be touched during its normal
performance, the temperature-rise limit may be 40 K.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 9 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


4. RESULTS

CORRECT. The temperature-rise of each part of the switchgear for which limits
are specified (and whose values have been measured) does not
exceed these limits.

The results obtained in test No. 1 are shown in the following table.

TEMPERAURE RISE TEST 1 (FUSE 63 A) Ambient temperature: 21 ºC


Temperature rise
No. Switchgear Thermocouple location Limit (K)
(K)
1 CGM3621 L Upper busbar - 75
2 CGM3621 L Upper busbar 42 75
3 CGM3621 L Upper busbar 42 75
4 CGM3621 L Upper fixed contact 48 65
5 CGM3621 L Switch Upper fixed contact 48 65
6 CGM3621 L Switch Upper fixed contact 49 65
7 CGM3621 L Switch Moving contact 52 65
8 CGM3621 L Switch Moving contact 51 65
9 CGM3621 L Switch Moving contact 49 65
10 CGM3621 L Switch Lower fixed contact 48 65
11 CGM3621 L Switch Lower fixed contact 47 65
12 CGM3621 L Switch Lower fixed contact 46 65
13 CGM3621 L Switch Lower busbar Connection 46 75
14 CGM3621 L Switch Lower busbar Connection 46 75
15 CGM3621 L Switch Lower busbar Connection 46 75
16 CGM3621 L Lower busbar Bushings Connection - 75
17 CGM3621 L Lower busbar Bushings Connection 42 75
18 CGM3621 L Lower busbar Bushings Connection 41 75
19 CGM3621 L Indoor ambient upper zone 35 -
20 CGM3621 L Indoor ambient lower zone 20 -

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 10 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


1 CGM3621 P Switch Upper fixed contact 42 65
2 CGM3621 P Switch Upper fixed contact 41 65
3 CGM3621 P Switch Upper fixed contact 41 65
4 CGM3621 P Switch Moving contact 40 65
5 CGM3621 P Switch Moving contact 39 65
6 CGM3621 P Switch Moving contact 38 65
7 CGM3621 P Switch Fuse holder busbar connection 34 75
8 CGM3621 P Switch Fuse holder busbar connection 35 75
9 CGM3621 P Upper busbar 48 75
10 CGM3621 P Upper busnar 50 75
11 CGM3621 P Upper busbar 52 75
12 CGM3621 P Fuse holder busbar Switch connection 33 75
13 CGM3621 P Fuse holder busbar Switch connection 33 75
14 CGM3621 P Fuse holder busbar Switch connection 37 75
15 CGM3621 P Switch Lower fixed contact 37 65
16 CGM3621 P Switch Lower fixed contact 36 65
17 CGM3621 P Switch Lower fixed contact 29 65
18 CGM3621 P Switch Fuse holder busbar connection 34 75
19 CGM3621 P Fuse holder Bushings Connection Phase R 33 75
20 CGM3621 P Connection Bushings Fuse holder 11 75
21 CGM3621 P Connection Bushings Fuse holder - 75
22 CGM3621 P Connection Bushings Fuse holder 12 75
23 CGM3621 P Indoor ambient 11 -
45 CGM3621 P Fuse holder Back contact 43 65
46 CGM3621 P Fuse holder Back contact 44 65
47 CGM3621 P Fuse holder Back contact 38 65
48 CGM3621 P Fuse-carrier carriage Moving contact 38 65
49 CGM3621 P Fuse-carrier carriage Moving contact 44 65
50 CGM3621 P Fuse-carrier carriage Moving contact 44 65
51 CGM3621 P Fuse-carrier carriage Front contact 52 65
52 CGM3621 P Fuse-carrier carriage Front contact 55 65

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 11 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


53 CGM3621 P Fuse-carrier carriage Front contact 57 65
CGM3621 P Enclosure front zone 11 30
CGM3621 P Enclosure back zone 19 40
CGM3621 P Enclosure lateral left 20 40
CGM3621 L Enclosure lateral right 18 40
CGM3621 L Incoming connection Phase S 66 75
Incoming connection at a distance of 1 m
CGM3621 L 67 Note (1)
Phase S

CGM3621 P Incoming connection Phase S 20 75


Incoming connection at a distance of 1 m
CGM3621 P 21 Note (1)
Phase S

Note (1): The difference between the temperature rises of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 12 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


The results obtained in test No. 2 are shown in the following table

TEMPERATURE RISE TEST 2 (FUSE 80 A) Ambient temperature:


21 ºC
Temperature rise
No. Switchgear Thermocouple location Limit (K)
(K)
1 CGM3621 L Upper busbar - 75
2 CGM3621 L Upper busbar 43 75
3 CGM3621 L Upper busbar 43 75
4 CGM3621 L Upper fixed contact 50 65
5 CGM3621 L Switch Upper fixed contact 50 65
6 CGM3621 L Switch Upper fixed contact 50 65
7 CGM3621 L Switch Moving contact 53 65
8 CGM3621 L Switch Moving contact 52 65
9 CGM3621 L Switch Moving contact 50 65
10 CGM3621 L Switch Lower fixed contact 50 65
11 CGM3621 L Switch Lower fixed contact 49 65
12 CGM3621 L Switch Lower fixed contact 49 65
13 CGM3621 L Switch Lower busbar Connection 48 75
14 CGM3621 L Switch Lower busbar Connection 47 75
15 CGM3621 L Switch Lower busbar Connection 48 75
16 CGM3621 L Lower busbar Bushings Connection - 75
17 CGM3621 L Lower busbar Bushings Connection 44 75
18 CGM3621 L Lower busbar Bushings Connection 43 75
19 CGM3621 L Indoor ambient upper zone 36 -
20 CGM3621 L Indoor ambient lower zone 22 -

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 13 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


1 CGM3621 P Switch Upper fixed contact 40 65
2 CGM3621 P Switch Upper fixed contact 39 65
3 CGM3621 P Switch Upper fixed contact 40 65
4 CGM3621 P Switch Moving contact 38 65
5 CGM3621 P Switch Moving contact 37 65
6 CGM3621 P Switch Moving contact 36 65
7 CGM3621 P Switch Fuse holder busbar connection 33 75
8 CGM3621 P Switch Fuse holder busbar connection 33 75
9 CGM3621 P Upper busbar 48 75
10 CGM3621 P Upper busnar 50 75
11 CGM3621 P Upper busbar 52 75
12 CGM3621 P Fuse holder busbar Switch connection 31 75
13 CGM3621 P Fuse holder busbar Switch connection 30 75
14 CGM3621 P Fuse holder busbar Switch connection 33 75
15 CGM3621 P Switch Lower fixed contact 34 65
16 CGM3621 P Switch Lower fixed contact 35 65
17 CGM3621 P Switch Lower fixed contact 18 65
18 CGM3621 P Switch Fuse holder busbar connection 32 75
19 CGM3621 P Fuse holder Bushings Connection Phase R 30 75
20 CGM3621 P Connection Bushings Fuse holder 11 75
21 CGM3621 P Connection Bushings Fuse holder - 75
22 CGM3621 P Connection Bushings Fuse holder 11 75
23 CGM3621 P Indoor ambient 11 -
45 CGM3621 P Fuse holder Back contact 38 65
46 CGM3621 P Fuse holder Back contact 38 65
47 CGM3621 P Fuse holder Back contact 33 65
48 CGM3621 P Fuse-carrier carriage Moving contact 34 65
49 CGM3621 P Fuse-carrier carriage Moving contact 40 65
50 CGM3621 P Fuse-carrier carriage Moving contact 39 65
51 CGM3621 P Fuse-carrier carriage Front contact 46 65
52 CGM3621 P Fuse-carrier carriage Front contact 49 65
53 CGM3621 P Fuse-carrier carriage Front contact 50 65

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 14 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


CGM3621 P Enclosure front zone 11 30
CGM3621 P Enclosure back zone 18 40
CGM3621 P Enclosure lateral left 17 40
CGM3621 L Enclosure lateral right 18 40
CGM3621 L Incoming connection Phase S 45 75
Incoming connection at a distance of 1 m
CGM3621 L 46 Note (1)
Phase S

CGM3621 P Incoming connection Phase S 4 75


Incoming connection at a distance of 1 m
CGM3621 P 8 Note (1)
Phase S

Note
Note (1): The difference between the temperature rises of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 15 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


The results obtained in test No. 3 are shown in the following table

TEMPERATURE RISE TEST 3 (LINKS 200 A) Ambient temperature:


19 ºC
Temperature rise
Nº Switchgear Thermocouple location Limit (K)
(K)
1 CGM3621 L Upper busbar - 75
2 CGM3621 L Upper busbar 42 75
3 CGM3621 L Upper busbar 41 75
4 CGM3621 L Upper fixed contact 48 65
5 CGM3621 L Switch Upper fixed contact 49 65
6 CGM3621 L Switch Upper fixed contact 50 65
7 CGM3621 L Switch Moving contact 52 65
8 CGM3621 L Switch Moving contact 52 65
9 CGM3621 L Switch Moving contact 50 65
10 CGM3621 L Switch Lower fixed contact 49 65
11 CGM3621 L Switch Lower fixed contact 49 65
12 CGM3621 L Switch Lower fixed contact 49 65
13 CGM3621 L Switch Lower busbar Connection 47 75
14 CGM3621 L Switch Lower busbar Connection 47 75
15 CGM3621 L Switch Lower busbar Connection 47 75
16 CGM3621 L Lower busbar Bushings Connection - 75
17 CGM3621 L Lower busbar Bushings Connection 44 75
18 CGM3621 L Lower busbar Bushings Connection 43 75
19 CGM3621 L Indoor ambient upper zone 36 -
20 CGM3621 L Indoor ambient lower zone 21 -

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 16 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


1 CGM3621 P Switch Upper fixed contact 46 65
2 CGM3621 P Switch Upper fixed contact 46 65
3 CGM3621 P Switch Upper fixed contact 48 65
4 CGM3621 P Switch Moving contact 45 65
5 CGM3621 P Switch Moving contact 45 65
6 CGM3621 P Switch Moving contact 44 65
7 CGM3621 P Switch Fuse holder busbar connection 48 75
8 CGM3621 P Switch Fuse holder busbar connection 51 75
9 CGM3621 P Upper busbar 52 75
10 CGM3621 P Upper busnar 55 75
11 CGM3621 P Upper busbar 57 75
12 CGM3621 P Fuse holder busbar Switch connection 37 75
13 CGM3621 P Fuse holder busbar Switch connection 48 75
14 CGM3621 P Fuse holder busbar Switch connection 52 75
15 CGM3621 P Switch Lower fixed contact 46 65
16 CGM3621 P Switch Lower fixed contact 47 65
17 CGM3621 P Switch Lower fixed contact 41 65
18 CGM3621 P Switch Fuse holder busbar connection 38 75
19 CGM3621 P Fuse holder Bushings Connection Phase R 30 75
20 CGM3621 P Connection Bushings Fuse holder 24 75
21 CGM3621 P Connection Bushings Fuse holder - 75
22 CGM3621 P Connection Bushings Fuse holder 19 75
23 CGM3621 P Indoor ambient 11 -
45 CGM3621 P Fuse holder Back contact 30 65
46 CGM3621 P Fuse holder Back contact 30 65
47 CGM3621 P Fuse holder Back contact 27 65
48 CGM3621 P Fuse-carrier carriage Moving contact 42 65
49 CGM3621 P Fuse-carrier carriage Moving contact 45 65
50 CGM3621 P Fuse-carrier carriage Moving contact 46 65
51 CGM3621 P Fuse-carrier carriage Front contact 41 65
52 CGM3621 P Fuse-carrier carriage Front contact 45 65
53 CGM3621 P Fuse-carrier carriage Front contact 45 65

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 17 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


CGM3621 P Enclosure front zone 8 30
CGM3621 P Enclosure back zone 17 40
CGM3621 P Enclosure lateral left 15 40
CGM3621 L Enclosure lateral right 17 40
CGM3621 L Incoming connection Phase S 45 75
Incoming connection at a distance of 1 m
CGM3621 L 46 Note (1)
Phase S

CGM3621 P Incoming connection Phase S 18 75


Incoming connection at a distance of 1 m
CGM3621 P 15 Note (1)
Phase S

Nota (1): The difference between the temperature rise of the terminals of the main
circuit and of the provisional connections at a distance of 1 m from the
terminal is no more than 5 K.

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 18 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


Verification of the resistance of the main circuit

CORRECT. The values measured before the beginning of the test and after the
end of the temperature-rise test do not differ by more than 20 %.

Values of resistance in µΩ.

CGM3621 P

Before the temperature rises After the temperature rises

Phase R-r Phase S-s Phase T-t Phase R-r Phase S-s Phase T-t

968 976 1144 963 999 1086

CGM3621 L

Before the temperature rises After the temperature rises

Phase R-r Phase S-s Phase T-t Phase R-r Phase S-s Phase T-t

157 157 160 167 163 172

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Page 19 of 19

Printed by i:0#.w|velatia\ims 28/10/2016


Report No. B126-
B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 1 of 6

Printed by i:0#.w|velatia\ims 28/10/2016


Report No. B126-
B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 2 of 6

Printed by i:0#.w|velatia\ims 28/10/2016


Test objects

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 3 of 6

Printed by i:0#.w|velatia\ims 28/10/2016


Test arrangement

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 4 of 6

Printed by i:0#.w|velatia\ims 28/10/2016


Short-
Short-circuit 1L1P

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 5 of 6

Printed by i:0#.w|velatia\ims 28/10/2016


Fuse 63 A

Fuse 80 A

Report No. B126-


B126-06-
06-BT-
BT-EE-
EE-02Ev2
02Ev2 Annex. Page 6 of 6

Printed by i:0#.w|velatia\ims 28/10/2016

You might also like