ATS Basics - Finning Cat Feb 16 2021

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

WELCOME

AUTOMATIC TRANSFER SWITCHES

JIM DONNELLY
Senior Specifications Specialist
FINNING Canada
Finning Contacts:
Ben Mah – Power Systems Engine Sales
bmah@finning.com

Chris Schurmans – Project Development Manager


cschurmans@finning.com

Ryan Goertz – Business Development Manager


rgoertz@finning.com

Ian McMaster – Electric Power Generation Representative


Ian.McMaster@finning.com

Jim Boyd – Project Development Manager


Jim.Boyd@finning.com

Bryce Burgeson – Engine Sales Representative


bburgeson@finning.com

Moe Jabouri – Strategic Account Manager


Moe.Jabouri@finning.com

Jim Donnelly – Senior Specifications Specialist


Jim.Donnelly@finning.com

Sid Kuzmanovic – Project Development Manager


Sinisa.Kuzmanovic@finning.com

Mickey Randhawa – Technical Applications Representative


Malkiat.Randhawa@finning.com

Gavin Gunderson – Technical Applications Representative


Gavin.Gunderson@finning.com

Chris Koehler – Technical Applications Representative


Page 33 Chris.Koehler@finning.com
Automatic Transfer Switch (ATS) Basics
Outline
• Practical Definition of an ATS
• Seven Major functions of ATS
• ATS Technologies
• Transferring Loads
• Standards and Certifications

Cat® Electric Power


Caterpillar: Confidential Green 2
Practical Transfer Switch Definition
Transfer Switch - A device which transfers
electrical loads between two dissimilar sources
of power by using either automatic or manual
controls.

UTILITYLOAD GENERATOR

Cat® Electric Power


Caterpillar: Confidential Green 3
Transfer Switch Overview

Whether a system is required by statute, or just


desired to maintain continuity of one’s business,
it will fall into one of four general application
categories:
• Emergency system
• Legally required system
• Optional system
• Alternative system

Cat® Electric Power


Caterpillar: Confidential Green 4
Transfer Switch Overview
Emergency system - A system
legally required and classified as
emergency by municipal, state,
federal or other governmental
agencies.

• Automatically transfers from the


normal source to the emergency
source and generally cannot exceed
10 seconds and occurs
automatically.

• Facilities occupied by large


numbers of people ( hospitals,
airports, hotels, sports arenas,
health care facilities).
Cat® Electric Power
Caterpillar: Confidential Green 5
Transfer Switch Overview
Legally required system - Legally
required systems are those that are so
classified by municipal, state, federal or
other governmental agencies.

• Automatically supply power to selected loads,


other than those already classified as emergency.
The transfer from normal power to the emergency
power cannot exceed 60 seconds and occurs
automatically.

• Used in heating, refrigeration, communications,


smoke removal, sewage disposal and industrial
processes.

Cat® Electric Power


Caterpillar: Confidential Green 6
Transfer Switch Overview
Optional system - is intended to protect public or private
property or facilities, where life and safety do not depend
on the system’s performance.

• Generally, supplied to selected loads either automatically or


manually. There is no time limit associated with the transfer.

• Typical loads served include heating, data processing, and industrial


processes that when stopped could cause discomfort, and/or damage to
the product or process.

Cat® Electric Power


Caterpillar: Confidential Green 7
Transfer Switch Overview

Alternative system - Increasingly, on-site power


generation assets are being installed as a backup to the
normal power, or as a way to reduce utility bills, especially
when utility rates are extremely high or reliable utility
power is not readily available.

Cat® Electric Power


Caterpillar: Confidential Green 8
Seven Major Functions of Automatic Transfer Switches
• Carry Current Continuously
• Detect Power Failures
• Initiate Alternate Source
• Transfer Load
• Sense Restoration of Normal
• Re-Transfer Load to Normal
• Withstand and Close-In On
Fault Currents

Cat® Electric Power


Caterpillar: Confidential Green 9
ATS Technologies
USING DOUBLE THROW MECHANISM

INHERENTLY MECHANICALLY INTERLOCKED

UTILITY LOAD GENERATOR

Cat® Electric Power


Caterpillar: Confidential Green 11
USING CIRCUIT BREAKERS
MECHANICALLY & ELECTRICALLY INTERLOCKED

UTILITY LOAD GENERATOR

Cat® Electric Power


Caterpillar: Confidential Green 12
Contactor ATS vs. Breaker pair ATS

Service entrance applications are easier and less


expensive with a Breaker pair ATS

Cat® Electric Power


Caterpillar: Confidential Green 13
Contactor ATS vs. Breaker pair ATS
• 0.5 Second, Short Time withstand rating for Selective
Coordination – the Magnum w/ Short Time rating is
available from 200A to 5000A, while the contactor-
based equivalent is available from 1000A to 3000A
• Under Normal conditions, both function identically;
under abnormal conditions Breaker pair will perform
better. Breaker pair ATS are self protecting devices

Cat® Electric Power


Caterpillar: Confidential Green 14
Breaker ATS: Pros and Cons
Pros Cons
• Service entrance • Higher Cost
applications • To replace one breaker,
• Selective Coordination – you must replace the
Magnum Only complete power panel
• Higher Withstands • Many specs from other
• Maintenance free contacts manufacturers try to
• Deadfront exclude breaker ATS’
• Safe manual operation
under full load

Cat® Electric Power


Caterpillar: Confidential Green 15
Transferring Loads
What are the types of Transfer Switches?
• Open Transition
• Delayed Transition
• Closed Transition
• Bypass Isolation Variants
• Service Entrance Rated
• Soft load
• Three Source

Cat® Electric Power


Caterpillar: Confidential Green 17
Typical Transfer Switch Types:
Power Contactor Style

Standard Delayed Closed


Transition Transition Transition
(Break-Before Make (With Center OFF Position) (Make-Before-Break Operation)
Operation) Note: “Off” Position indicates Note: “P” Position indicates
No Center OFF Position Neither source Connected both sources paralleled for 6
cycles

Cat® Electric Power


Caterpillar: Confidential Green 18
Open Transition

• Standard double-throw type mechanism


with single-stroke action
• Two position ATS
– Either “Normal” or “Emergency”
positions
– No center position
• Inherent mechanical interlock
• Contact transfer times are 100 msec = 6
electrical cycles at min. settings
• General application ATS - multipurpose
(except large motor load system)

Cat® Electric Power


Caterpillar: Confidential Green 19
Transferring Large Motors in Open Transition
VS

f =180° Engine Generator


Utility
Transformer
Vm

Synchroscope

N E

ATS

L
Back
EMF

Motor
Cat® Electric Power
Caterpillar: Confidential Green 20
Open In-Phase Transition
• Allows a live transfer between two sources
only when the phase difference is near zero
• Two ATS positions plus a neutral
– Either “Normal” or “Emergency”
positions
– Has a neutral position, but does not
stop in that position
• Inherent mechanical interlock
• Contact transfer times are >150 msec.
(must transfer in less than 10 electrical
cycles)
• Allows the ATS to be programmed as
“open” or “delayed” transition

Cat® Electric Power


Caterpillar: Confidential Green 21
Open Transition w/In-Phase Monitor
VS

f = +/- 60° V Engine Generator


m

Utility
Transformer

In-Phase Monitor

N E

ATS
L

Cat® Electric Power


Caterpillar: Confidential Green 22
Delayed Transition
• Adds an “off position” to the double-throw
mechanism
• ATS positions: “Normal” or “Emergency” or
Center “OFF” position
• Delayed transition (center off) transfer times
are adjustable
• Inherent mechanical interlock, can not
interconnect sources
• Used primarily with large inductive and UPS
loads (to allow coast or die-down before
transfer) (not required on Cat UPS)

Cat® Electric Power


Caterpillar: Confidential Green 23
Why use Delayed Transition?
• Allows for motors to coast down and transformer
fields to decay so inductive loads can be re-
energized with normal inrush currents.
• Transferring between unsynchronized sources can
cause transient high current that can exceed the
instantaneous trip settings of protective devices
• Release of stored energy in the transformer can
generate a surge even though the two power
sources are in sync when transfer is initiated
• VFD’s do not work well with open transition ATS.
VFD’s need time to reset.
• Certain UPS manufacturers recommend delayed
transition to ensure proper operation of rectifier
circuits and battery systems

Cat® Electric Power


Caterpillar: Confidential Green 24
Transfer Modes:
Motor Load Disconnect Circuit
Single Motor
• Motor Load disconnect control circuit
• Disconnects a large motor prior to transfer in either direction
• Auxiliary contacts opens thus de-energizing the selected
load
• Adjustable Time delay

Multiple Motors
• “Sequential Universal Motor Disconnect Circuit”
• Motor disconnect contact with staged restart
• Disconnects motors prior to transfer
• Brings them back on-line sequentially

Cat® Electric Power


Caterpillar: Confidential Green 25
Closed Transition
• Purpose-built mechanism/protection scheme to allow
“Make-Before-Break” operation between live sources
• Closed transition allows the new source to close to the
load before opening previous source (both switch
elements are closed in the “P” position)
• Protective function precludes paralleling until sources
are within 5% voltage, .2 Hz frequency and 5 degrees
phase angle
• Passive synchronization parallels both sources
for 5 cycles (100 msec) - synch check function
• ATS reverts to Open Transition on source failure
• Primary uses: Inductive, Electronic, and other critical
loads where the number of transfer related interruptions
must be minimized
• Standard double-throw type mechanism

Cat® Electric Power


Caterpillar: Confidential Green 26
Why use Closed Transition?

• To prevent the momentary outages that occur


during re-transfer to utility or during system
testing
• Electronic equipment, HID lighting, and motor
starters are sensitive to even the tiniest outage
during switch operation
• Peak shaving and Utility incentives rates require
the ability to transfer without power interruptions

Cat® Electric Power


Caterpillar: Confidential Green 27
Bypass Isolation Transfer Switch

Switch, Bypass Isolation – A device


used in conjunction with a transfer switch
to provide a means of directly connecting
load conductors to a power source and of
disconnecting the transfer switch.

Cat® Electric Power


Caterpillar: Confidential Green 28
Service Entrance Rated
Traditional ATS Installation
Utility Service

Service
Disconnect

G
Generator ATS
Breaker

Load

Cat® Electric Power


Caterpillar: Confidential Green 29
Service Entrance
ATS with Service Entrance
Utility Service
Equipment Rating

Service
Disconnect

G
Generator
Breaker
ATS

Load

Breaker Pair ATS Contactor ATS


Service Entrance Service Entrance

Cat® Electric Power


Caterpillar: Confidential Green 30
Applicable Standards and Certifications
CSA C22.2 No. 178.1-07*
• Most CAT Contactor and Breaker Type ATS are CSA Listed (Wall
Mount and Magnum, up to 3200a)
– Excludes SE rated, as well as CG Series (which are cUL)

*C22.2 No. 178.1-14 certification in


flight

Cat® Electric Power


Caterpillar: Confidential Green 32
UL 1008 – 8th Edition_____
• All CAT ATS’s (Breaker or Contactor) 30-5000Amp are
listed to UL1008
– Note that the upper product range can vary between 3000A &
4000A (depending on Series); 5000A units are comprised of a
breaker pair

Cat® Electric Power


Caterpillar: Confidential Green 33
UL 1008 Withstand Ratings
• Time-based Rating – Relates to circuits protected by a
circuit breaker, expressed in fractions of a second
– Replaces previous ‘Any Breaker’ nomenclature; time duration
expressed in seconds
– Typically 0.025 seconds for short-circuit currents up to 10kA and a
transfer switch ratings of 400 amps or less
– Typically 0.050 seconds for most other short-circuit levels

Cat® Electric Power


Caterpillar: Confidential Green 34
UL 1008 Withstand Ratings
• Specific Breaker Rating – Leverages the tripping
characteristics of specific circuit breaker to achieve
higher ratings
– Utilizes data derived from original Time-based rating tests
– Generally a collaborative development with UL – no additional
testing required
– Captured in a list of specific breakers associated with the rating

Cat® Electric Power


Caterpillar: Confidential Green 35
UL 1008 Withstand Ratings
• Fuse Rating – Tested with a “current limiting” fuse
– High ratings as a result of very short clearing times

• Short Time – Current applied for 0.5 Sec.


– ATS must remain functional after test.

Cat® Electric Power


Caterpillar: Confidential Green 36
Withstand / Close-in Ratings
Time-based Rating
• 0.05 or 0.025 seconds
• Depends on ATS size &
fault current value

A Specific Breaker Rating


• Valid only when applied
with a breakers shown
in the list on the
manufacturers label
• Such lists are generally
broad ensure flexibility

Cat® Electric Power


Caterpillar: Confidential Green 37
Specific Breaker Lists
• CAT has broad Specific
Breaker List

• Includes current and


vintage breakers

Cat® Electric Power


Caterpillar: Confidential Green 38
Finning Contacts:
Ben Mah – Power Systems Engine Sales
bmah@finning.com

Chris Schurmans – Project Development Manager


cschurmans@finning.com

Ryan Goertz – Business Development Manager


rgoertz@finning.com

Miroslav Misic – Technical Applications Representative


Miroslav.Misic@finning.com

Jim Boyd – Project Development Manager


Jim.Boyd@finning.com

Bryce Burgeson – Engine Sales Representative


bburgeson@finning.com

Moe Jabouri – Strategic Account Manager


Moe.Jabouri@finning.com

Jim Donnelly – Senior Specifications Specialist


Jim.Donnelly@finning.com

Sid Kuzmanovic – Project Development Manager


Sinisa.Kuzmanovic@finning.com

Mickey Randhawa – Technical Applications Representative


Malkiat.Randhawa@finning.com

Gavin Gunderson – Technical Applications Representative


Gavin.Gunderson@finning.com

Chris Koehler – Technical Applications Representative


Page 33 Chris.Koehler@finning.com