00 (HFC-227ea)
UL: EX4623 / Component of FM Approved System
System calculated within limits of Fike's UL listing and FM approval.
CNS Engineering
70A, XX Commercial, Khayaban-e-Iqbal, D.H.A Phase-
File Name: NEW CTH Data Center RV CV FV.FC4
Consolidated Report
Customer Information
Company Name: CNS
Address:
Phone:
Contact:
Title:
Project Data
Project Name:
Designer:
Number:
Account:
Location:
Description:
Enclosure Report
Page: 1 of 16
Consolidated Report
Adjusted: 7.21 % Non-permeable: 0.00 m ³
Minimum: 7.20 % Total Volume: 431.97 m ³
Min. Agent Required: 244.82 kg
Adjusted Agent Required: 245.03 kg
E1-Pos (+)
16 E1-Neg (-)
14
Equivalent Leakage Area (in^2)
12
10
0
0 2 4 6 8 10 12 14
Enclosure Pressure (psf)
Page: 2 of 16
Consolidated Report
Enclosure 2 CTH NEW DATA CENTER CV
Enclosure Temperature: Number of Nozzles: 4
Minimum: 20.0 C Width: 11.90 m
Maximum: 20.0 C Length: 12.00 m
Max. Concentration: 0.00 % Height: 1.00 m
Design Concentration: Volume: 142.80 m ³
Adjusted: 7.37 % Non-permeable: 0.00 m ³
Minimum: 7.20 % Total Volume: 142.80 m ³
Min. Agent Required: 80.93 kg
Adjusted Agent Required: 82.96 kg
E2-Pos (+)
E2-Neg (-)
5
Equivalent Leakage Area (in^2)
0
0 2 4 6 8 10 12 14
Enclosure Pressure (psf)
Page: 3 of 16
Consolidated Report
Enclosure 3 CTH NEW DATA CENTER FV
Enclosure Temperature: Number of Nozzles: 2
Minimum: 20.0 C Width: 11.90 m
Maximum: 20.0 C Length: 12.00 m
Max. Concentration: 0.00 % Height: 0.70 m
Design Concentration: Volume: 99.96 m ³
Adjusted: 7.36 % Non-permeable: 0.00 m ³
Minimum: 7.20 % Total Volume: 99.96 m ³
Min. Agent Required: 56.66 kg
Adjusted Agent Required: 58.01 kg
E3-Pos (+)
4 E3-Neg (-)
3.5
Equivalent Leakage Area (in^2)
2.5
1.5
0.5
0
0 2 4 6 8 10 12 14
Enclosure Pressure (psf)
Page: 4 of 16
Consolidated Report
Agent Source Report
Page: 5 of 16
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40T 25 mm 10.54 m 15 0 0 0
40T 50 mm 7.10 m 4 0 1 0
40T 65 mm 9.50 m 1 0 4 0
40T 80 mm 8.10 m 2 0 2 0
Other
Objects Name Quantity Part Number
Page: 6 of 16
Consolidated Report
Percent Agent Before First Tee: 10.6%
Enclosure Number: 1
Enclosure Name: CTH NEW DATA CENTER RV
Minimum Design Concentration: 7.20%
Adjusted Design Concentration: 7.21%
Predicted Concentration: 7.22%
Maximum Expected Agent Concentration: 7.22% (At 20.0 C)
Enclosure Number: 2
Enclosure Name: CTH NEW DATA CENTER CV
Minimum Design Concentration: 7.20%
Adjusted Design Concentration: 7.37%
Predicted Concentration: 7.20%
Maximum Expected Agent Concentration: 7.20% (At 20.0 C)
Page: 7 of 16
Consolidated Report
Minimum Adjusted Predicted Average
Agent Agent Agent Nozzle
Nozzle Required Required Delivered Pressure
Enclosure Number: 3
Enclosure Name: CTH NEW DATA CENTER FV
Minimum Design Concentration: 7.20%
Adjusted Design Concentration: 7.36%
Predicted Concentration: 7.55%
Maximum Expected Agent Concentration: 7.55% (At 20.0 C)
Page: 8 of 16
Consolidated Report