Product Catalogue
Product Catalogue
1
Product overview
2
Power protection Contents
as easy as 3-5-9
9. HARMONIC DISTORTION
3
Powerware® 3105
Basic power protection
for PC
Technology:
Series 3 (offline)
Rating:
350-500 VA
Voltage:
230 Vac
Backup time:
3 min with full load
4
POWERWARE 3105 specifications table
Operational
Nominal Input voltage (VAC) 230 VAC
Input voltage range 184-265 VAC
Operating frequency 50/60 Hz auto sensing
Nominal Output voltage 230 VAC
Output voltage regulation Same as input
Overload capacity 120%+/- 10%
Efficiency 95%, normal mode
User interface
LED UPS On, UPS on Battery, Overload, Alarm
Standard communication ports USB Drivers available for Windows 98/ME/2000/XP/2003
Environmental
Operating temperature 0ºC - +40 ºC
Altitude < 3000 m
Audible noise at 1 meter < 40 dB
Certification
Markings CE
5
Powerware® 5110
Power protection
for office PC and
workstations
Technology:
Series 5 (Line-interactive)
Rating:
500-1000 VA
Voltage:
230 Vac
Backup time:
3-5 min with full load
6
POWERWARE 5110 specifications table
Rating 500 VA 700 VA 1000 VA
Part number 103004261-5501 103004262-5501 103004263-5501
Capacity (VA/Watts) 500/300 700/420 1000/600
Dimensions WxDxH ( mm) 87x260x270 mm 87x260x270 mm 87x384x270 mm
Weight (kg) 6 kg 8 kg 12 kg
Input connection IEC320/ 10A IEC320/10A IEC320/10A
4xIEC320 10A 4xIEC320 10A 4xIEC320 10A
Output connection
+ 4 IEC320 10A surge only + 4 IEC320 10A surge only + 4 IEC320 10A surge only
Typical runtime
full load 3 min 3 min 5 min
half load 8 min 8 min 15 min
(2) IEC-IEC cables (2) IEC-IEC cables (2) IEC-IEC cables
Bundled with Software & USB cable Software & USB cable Software & USB cable
RJ 11 cable RJ 11 cable RJ 11 cable
Operational
Nominal Input voltage (VAC) 230 VAC
Input voltage range 178-275 VAC
Operating frequency 50/60 Hz auto sensing
Nominal Output voltage 230 VAC
Output voltage regulation 230 V +/- 10%
130%+/- 10% immediate shutdown
Overload capacity
105% shutdown after 5 min
Efficiency 95%, normal mode
User interface
LED UPS On, UPS on Battery, Overload,
Standard communication ports USB Drivers available for Windows 98/ME/2000/XP/2003
Environmental
Operating temperature 0 ºC - +40 ºC
Altitude < 3000 m
Audible noise at 1 meter < 40 dB
Certification
Markings CE
7
Powerware® 5115
Cost effective power
protection for office
servers
Technology:
Series 5 (line interactive)
Rating:
500-1400 VA
Voltage:
220-240 Vac
Backup time:
Typical 5 min at full load
Model:
Cabinet
8
POWERWARE 5115 specifications table
Operational
Nominal input voltage (VAC) 220/230/240 Vac
Input voltage range 184-276 VAC (± 20% of nominal)
Operating frequency 50/60 Hz auto sensing
Input power factor Same as load
Nominal output voltage 220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Four LEDs; UPS on, UPS on battery, overload, alarm
Standard communication ports RS232 & USB
Optional External Web/SNMP adapter
Environmental
Operating temperature 0°C – +40°C, recommended 20°C –25°C
Storage temperature -15°C – +55°C
Altitude < 3000 m
Audible noise at 1 metre < 40 dB
Certification
Markings CE/GS/UL
Safety EN 50091-1-1 & UL 1778
EMC EN 50091-2, EN6100-3-2
9
Powerware® 5115 RM
Cost effective power
protection for office
servers
10
POWERWARE 5115 RM specifications table
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range (± 20% of nominal)
Operating frequency 50/60 Hz auto sensing
Nominal output voltage 220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Four LEDs; UPS on, UPS on battery, overload, alarm
Standard communication ports RS232/USB and X-slot
Optional Internal Web/SNMP adapter
Environmental
Operating temperature 0°C – +40°C, recommended 20°C –25°C
Storage temperature -15°C – +55°C
Altitude < 3000 m
Audible noise at 1 metre < 40 dB
Certification
Markings CE
Safety EN 50091-1-1 & UL 1778
EMC EN 50091-2, EN6100-3-2
11
Powerware® 5125
Power protection
for networked office
servers
Technology:
Series 5 (line interactive)
Rating:
1000-2200 VA
Voltage:
200-240 Vac
Backup time:
Typical 5 min
(extendable up to one
hour)
Model:
Cabinet
12
POWERWARE 5125 specifications table
Operational
Nominal input voltage (VAC) 220/230/240 Vac
Input voltage range 166 – 276 Vac (+20/-30% of nominal)
Operating frequency 50/60 Hz auto sensing
Input power factor Same as load
Nominal output voltage 220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Informative LED display
Standard communication ports RS232
Optional Web/SNMP card, USB card, Relay card
Environmental
Operating temperature 0°C – +40°C, recommended 20°C – 25°C
Storage temperature -15°C – +55°C
Altitude < 3000 m
< 45 dB normal mode
Audible noise at 1 metre
< 50 dB battery mode
Certification
Markings CE/GS/UL
Safety EN 50091-1-1 & UL 1778
EMC EN 50091-2, EN6100-3-2
13
Powerware® 5125 RM
Power protection for
rackmounted office
servers
14
POWERWARE 5125 RM specifications table
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range 166 – 276 Vac(± 20% of nominal)
Operating frequency 50/60 Hz auto sensing
Input power factor Same as load
Nominal output voltage 220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Informative LED display
Standard communication ports RS232
Optional Web/SNMP card, USB card, relay card
Environmental
Operating temperature 0°C – +40°C, recommended 20°C –25°C
Storage temperature -15°C – +55°C
Altitude < 3000 m
< 45 dB normal mode
Audible noise at 1 metre
< 50 dB battery mode
Certification
Markings CE/UL (1000 – 1500 VA, CE (3000 VA)
EN 50091-1-1 & UL 1778 (1000 – 1500 VA),
Safety
EN 50091-1-1 (3000 – 6000 VA)
EN 50091-2, EN6100-3-2 (1000 – 3000 VA)
EMC
EN 50091-2 (6000 VA)
15
Powerware® 9120
Power protection for
any critical applications
Technology:
Series 9 (double conversion)
Rating:
700-6000 VA
Voltage:
208-240 Vac
Backup time:
Typical 10 min (extendable
up to several hours)
Models:
Cabinet
Options:
• Web/SNMP card
• External battery cabinets
• Relay card
• Transformer options
• Maintenance bypass options
16
POWERWARE 9120 specifications table
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range 120/140/160-276 Vac (700-3000 VA)
120/140/184-276 Vac (5000-6000 VA)
Operating frequency 50/60 Hz auto sensing (± 3 Hz, adjustable)
> 0.97 (700-3000 VA)
Input power factor
> 0.99 (5000-6000 VA)
Nominal output voltage 208/220/230/240 Vac
Output voltage regulation ± 2% online; ± 3% on battery mode
Overload capacity Up to 125% for 1 minute, 125-150% for 10 sec
> 86% (700 VA); > 88% 1000-3000 VA; > 90% 5000-6000 VA (Online mode)
Efficiency
> 90% (700 VA); > 93% 1000-3000 VA; > 95% 5000-6000 VA (High efficiency mode)
User interface
LCD display LCD display showing both UPS meters and UPS settings
LED Four LEDs; UPS on, UPS on battery, UPS on bypass, alarm
Standard communication ports RS232 and USB as standard on all models
Optional Connectivity slot for Web/SNMP card and relay card
Environmental
Operating temperature 0°C – +40°C, recommended 20°C –25°C
Storage temperature -15°C – +40°C
Altitude < 3000 m
< 45 dB (700-1500 VA)
Audible noise at 1 metre < 50 dB (2000-3000 VA)
< 55 dB (5000-6000 VA)
Certification
CE/GS/UL (700-2000 VA)
Markings
CE/GS (3000-6000 VA)
EN 50091-1-1 & UL 1778 (700-2000 VA)
Safety
EN50091-1-1 (3000-6000 VA)
EN 50091-2, EN6100-3-2 (700-3000 VA)
EMC
EN50091-2 (5000-6000 VA)
17
Powerware® 9125 RM
For critical rack mounted
applications
Technology:
Series 9
(double conversion)
Rating: 1000-6000 VA
Voltage: 230 Vac
Backup time:
Typical 5-13 min
(extendable
up to several hours)
Model:
Rackmount
18
POWERWARE 9125 RM specifications table
Rating 1000 VA 1500 VA 2000 VA 3000 VA 5000 VA 6000 VA
Part number black 05146011-6501 05146006-6501 05146003-6501 103002723-6501 103003623-6501 103003625-6501
grey 05146011-5501 05146006-5501 05146003-5501 103002723-5501 103003623-5501 103003625-5501
Capacity (VA/watts) 1000/700 1500/1050 2000/1400 3000/2100 5000/3500 6000/4200
Dimensions WxHxD (mm) 432x89x490 432x89x490 432x89x490 432x89x610 440x220x635 440x220x635
Weight (kg) 15 23 23 37 93 93
Input connection IEC320/10A IEC320/10A IEC320/10A IEC320/16A Hardwired Hardwired
1xIEC320/16A
Output connection 6xIEC320/10A 6xIEC320/10A 6xIEC320/10A Hardwired Hardwired
4xIEC320/10A
Typical runtime at 20°C
full load 5 min 8 min 5 min 5 min 13 min 10 min
half load 15 min 25 min 15 min 15 min 35 min 30 min
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range 160-288 Vac (1000-3000 VA); 120-288 Vac (5000-6000 VA)
Operating frequency 50/60 Hz auto sensing
Input power factor > 0.95
Nominal output voltage 208/220/230/240 Vac
Output voltage regulation ± 3% online; ± 3% on battery mode
Overload capacity Up to 110% for 2 minute, 111-150% for 30 sec
Efficiency > 86% (1000-3000 VA); 90% (5000-6000 VA)
User interface
3 LEDs to inform status of UPS
LED
5 LEDs to inform about UPS alarms and status
Standard communication ports RS232 as standard on all models
Optional Web/SNMP, USB, multiport card and relay card
Environmental
Operating temperature 0°C – +40°C, recommended 20°C –25°C
Storage temperature Recommended 0°C – +25°C
Altitude < 3000 m
< 45 dB (normal mode)
Audible noise at 1 metre
< 50 dB (battery mode)
Certification
Markings CE/UL (1000-2000 VA) CE (3000 VA)
Safety EN 50091-1-1 & UL 1778 (1000-2000 VA), EN 50091-1-1 (3000 – 6000 VA)
EMC EN 50091-2, EN 6100-3-2 (1000 – 3000 VA), EN 50091-2 (5000 – 6000 VA)
19
Powerware® 9155
Powerful UPS with
extensive features
for 24/7 protection of
computers and servers
20
POWERWARE 9155 specifications table
Operational
S models: 220/230/240 Vac single phase;
Nominal input voltage (Vac)
N models: 220/380, 230/400, 240/415 Vac three phase
± 20% from nominal at 100% load,
Input voltage range
- 50%, +20% from nominal at 50% load
Operating frequency 50/60 Hz (45 to 65 Hz)
Input power factor 0,99 (5% THD)
Input current distortion 5% THD in normal network condition
Nominal output voltage 220/230/240 VAC single phase
±2% static;
Output voltage regulation
±5% dynamic at 100% load change, < 1 ms response time
150% for 5 sec / 125% for 1 min (online),
Overload capacity
1000% for 20 msec (bypass)
Efficiency 92% with computer load, 93% with linear load
User interface
LCD display Graphical LCD with blue backlight: English, French, German and Spanish (extendable) lanquages
LED 4 LED
Standard communication ports 1 x RS232 for local support, 2 x X-slot (empty);
1 x relay contact, 1 x emergency power-off input, 2 x environmental input
Optional External battery cabinets;
isolation transformer; external mechanical bypass switch
XSlot: Web/SNMP, Modbus/Jbus, Relay, Hot Sync cards
Environmental
Operating temperature 0°C to +40°C, +45°C with 7,5% derating; Batteries recommended max. +25°C
Storage temperature -15°C to +45°C
Altitude < 1000 m
Audible noise < 50 dB(A) at 1 meter (noise less room); 53 dB(A) according to ISO 7779
Certification
Quality ISO 9001: 2000 and ISO 14001:1996
Markings CE and GOST marking
Safety IEC 62040-1-1, IEC 60950, EN 62040-1-1
EMC EN 50091-2 Class A
21
Powerware® 9355
Three phase UPS for
high class protection
22
POWERWARE 9355 specifications table
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 Vac three phase
±20% from nominal at 100% load,
Input voltage range
-50%, +20% from nominal at 50% load
Operating frequency 50/60 Hz (45 to 65 Hz)
Input power factor 0,99 (5% THD)
Input current distortion 5% THD in normal network condition
Nominal output voltage 220/380, 230/400, 240/415 Vac
±2% static;
Output voltage regulation
±5% dynamic at 100% load change, < 1 ms response time
150% for 5 sec / 125% for 1 min (online),
Overload capacity
1000% for 20 msec (bypass)
Efficiency 92% with computer load, 93% with linear load
User interface
LCD display Graphical LCD with blue backlight: English, French, German and Spanish (extendable) languages
LED 4 LED
1 x RS232 for local support, 2 x X-slot (empty);
Standard communication ports
1 x relay contact, 1 x emergency power-off input, 2 x environmental input
External battery cabinets;
Optional isolation transformer; external mechanical bypass switch
XSlot: Web/SNMP, Modbus/Jbus, Relay, Hot Sync cards
Environmental
Operating temperature 0°C to +40°C, +45°C with 7,5% derating; Batteries recommended max. +25°C
Storage temperature -15°C to +45°C
Altitude < 1000 m
Audible noise < 50 dB(A) at 1 meter (noise less room); 53 dB(A) according to ISO 7779
Certification
Quality ISO 9001: 2000 and ISO 14001:1996
Markings CE and GOST marking
Safety IEC 62040-1-1, IEC 60950, EN 62040-1-1
EMC EN 50091-2 Class A
23
Powerware® 9305
Three-phase UPS for
servers and industrial
applications
Options:
• ConnectUPS-E Web/SNMP adapter
• LanQuattro
• Remote ViewUPS LCD display
• External battery cabinets and battery racks
24
POWERWARE 9305 specifications table
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 Vac three-phase
170/294 to 275/476 Vac (20/30 kVA);
Input voltage range 170/294 to 279/484 Vac (40/50 kVA);
180/312 to 279/484 Vac (60 kVA)
Operating frequency 50/60 Hz (45–65 Hz)
Input power factor 0.96
Input current distortion 10% THDi with input filter
Nominal output voltage 220/380, 230/400, 240/415 Vac three-phase
± 1% static, 100% unbalanced load accepted;
Output voltage regulation
± 5% dynamic at 100% load change, < 1 ms recovery time
101–110% for 10 min (online);
111–125% for 1 min (online);
Overload capacity 126–150% for 30 sec (online);
150–170 % for 5 sec (online);
1000% for one cycle (bypass)
Efficiency 93–94% with rated non-linear load; 97% with Efficiency Optimiser
User interface
Multilingual LCD display : 9 languages;
LCD display
Remote ViewUPS optional
LED UPS on, on battery, on bypass, alarm
2xRS232 for local support, one with modem support;
4 relay contacts: UPS OK/alarm, line failure, low battery, UPS bypassed;
Standard communication ports
4 programmable inputs: generator on, external bypass, inverter on/off,
environment alarm; 1 emergency power off input
20/30/40/50/60 kVA models: Parallel capacity/redundancy systems (max. 4 modules),
external battery cabinets and high capacity charger; output transformer; input 10%
Optional
THD filter; Remote ViewUPS (LCD display); ConnectUPS-E (Web/SNMP adapter); LanQuattro
(4xRS232 data manager)
Environmental
Operating temperature 0ºC – +40ºC, batteries max. +25ºC
Storage temperature -25ºC – +40ºC
Altitude < 1000 m
55 dB (20/30 kVA)
Audible noise at 1 metre
60 dB (40/50/60 kVA)
Certification
Quality ISO 9001: 2000 ISO 14001:1996
Markings CE / CCA / GOST
Safety EN 50091-1-1: 1996; IEC 60950
EMC EN 50091-2: 1995
25
Powerware® 9370
Performance and
reliability for any kind
of critical application
26
POWERWARE 9370 specifications table
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 Vac three phase
Input voltage range 342 to 456 Vac
Frequency 50/60 Hz (45–65 Hz)
Input power factor 0.83 lag , 0.95 with filter (full load)
Input current distortion (THD) 30% 6P, 7% 12P, 4% 12P + filter
Nominal output voltage 220/380, 230/400, 240/415 Vac three-phase
Output voltage regulation ±1% static; ±5% dynamic 100% load change, < 3 ms recovery time
101–125% for 10 min (online);
Overload capacity 126–150% for 1 min (online);
1000% for 1 cycle (bypass)
Efficiency 93%
Parallel capacity/redundancy; ABM; backfeed protection;
isolation transformer; 12 pulse (160-300 kVA); input filters; external bypass;
Option external battery cabinets; external battery breaker in box
transformers/autotransformers for voltage adaptation;
top cable entry (160-300 kVA)
User interface
LCD display Graphical LCD display showing status, measurements of performance, alarms and event log
Led UPS on, on battery, on bypass, notice, alarm
1xRS232 for local support; 4x AS/400 relays;
4 programmable input: generator on, external bypass,
Standard communication ports inverter on/off, environment alarm;
Remote Emergency Power Off;
4 empty connectivity slots for optional cards
RS232 extension, SNMP/WEB, Modbus/Jbus, modem,
Optional
Remote ViewUPS display panel, additional relays
Environmental
Operating temperature 0°C – +40°C
Storage temperature -25°C – +60°C
Altitude < 1000 m
Audible noise at 1 meter (dBA) 70 dBA (According to ISO 3747)
Certification
Markings CE/GOST
Safety IEC EN 62040-1-1, IEC 60950
EMC EN 50091-2
Test & Performance IEC EN 62040-3
27
Powerware® 9390
Power protection
for high availability
systems
Options:
• System Parallel cabinets
Typical applications: • Wall-mounted external bypass switch modules
• Data centres, server farms (120-160 kVA)
• Building, banking and telecommunication systems • X-slot communication options
• Industrial automation equipment • Isolation transformer
• Healthcare systems • Long-life battery cabinets and racks
28
POWERWARE 9390 specifications table
Rating 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA 160 kVA
9390-40-N 9390-60-U 9390-80-N 9390-100-U 9390-120-U 9390-160-N
9390-BAT10-40x55Ah 9390-BAT10-40x55Ah 9390-BAT10-40x55Ah 9390-120-N
Part number
9390-BAT10-40x67Ah 9390-BAT10-40x67Ah 9390-BAT10-40x67Ah 9390-BAT10-40x67Ah 9390-BAT10-40x67Ah 9390-BAT10-40x67Ah
9390-BAT10-40x125Ah 9390-BAT10-40x125Ah 9390-BAT10-40x125Ah 9390-BAT10-40x125Ah 9390-BAT10-40x125Ah 9390-BAT10-40x125Ah
Capacity (kVA/kW) 40/36 60/54 80/72 100/90 120/108 160/144
Dimensions WxHxD (mm) 519x1872x804 519x1872x804 519x1872x804 900x1872x804 900x1872x804 900x1872x804
Weight (kg) UPS 285 313 313 430 430 460
Weight (kg) BAT 1270 1270 1270 1270 1270 1270
1430 1430 1430 1430 1430 1430
2350 2350 2350 2350 2350 2350
Input connection Dual input, hardwired
Output connection Hardwired
Typical runtime
UPS+1xBAT 55 Ah 30 min 17 min 10 min 8 min 6 min –
UPS+1xBAT 67 Ah 39 min 21 min 15 min 12 min 10 min –
UPS+1xBAT 125 Ah 87 min 53 min 36 min 27 min 20 min 12 min
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 VAC 50/60 Hz
Input voltage range -15%, +10% from nominal at 100% load
Operating frequency 50 Hz or 60 Hz (45-65 Hz)
Input power factor 0,99
Input current distortion < 5% THDi typical
Nominal output voltage 220/380, 230/400, 240/415 VAC
Output voltage regulation ±1% static, ±5% dynamic at 10% to 90% load change, < 1 ms recovery time
101-110% for 10 min
111-125% for 1 min
Overload capacity
126-150% for 10 sec
1000% for one cycle (bypass)
Efficiency up to 94%
User interface
LCD display Graphical LCD with blue backlight
LED 4 status indicators
Standard communication (2 or 4) x X-slot, 1 x relay contact,
ports 1 x emergency power-off input, 2 x environmental inputs
External battery cabinets and racks,
Optional isolation transformer, system Parallel Cabinets;
XSlot: SNMP/Web/HUB, ModBus/JBus, Relay, Hot Sync cards
Environmental
Operating temperature 0°C to +40°C, +45°C with 7,5% derating, batteries max +25°C
Storage temperature -15°C to +45°C
Altitude < 1500 m
65 dB(A) 40-80 kVA
Audible noise at 1 metre
70 dB(A) 120-160 kVA
Certification
Quality ISO 9001 : 2000, ISO 14001 : 1996
Markings CE, GOST
Safety IEC 62040-1-1, IEC 60950, EN 62040-1-1
EMC EN 50091-2
29
Powerware® 9315
Three-phase UPS for
data centres and
enterprise applications
30
POWERWARE 9315 specifications table
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 Vac three phase
Input voltage range 340 to 440 Vac
Operating frequency 50/60 Hz (47–63 Hz)
Input power factor 0.95 with input filter option 0.9 with input filter
Input current distortion 7% THD with input filter option
Nominal output voltage 220/380, 230/400, 240/415 Vac three-phase
±1% static;
Output voltage regulation
±5% dynamic at 100% load change
101–125% for 10 min (online);
126–150% for 30 sec (online);
Overload capacity
300% phase to neutral without bypass
1000% for 10 cycles (bypass)
Efficiency 92–94% (online); depending on model
User interface
LCD display Status, measurements of performance, alarms and event log
LED UPS on, on battery, on bypass, notice, alarm
1xRS232 for local support; 1 x XSlot
2 relay contacts: programmable
Standard communication ports
6 programmable inputs: generator on, go to UPS, go to bypass, environment alarm;
1 emergency power off input
External battery cabinets and racks;
Optional remote monitor panel; relay interface module; maintenance bypass module; system
bypass module; parallel capacity/redundancy systems
Environmental
Operating temperature 0°C – +40°C, 25°C recommended
Storage temperature -25°C – +60°C
Altitude < 1500 m
Audible noise at 1 metre 67–75 dB(A) according to ISO 7779; depending on model
Certification
Markings CE
Safety EN 50091-1, UL1778 listed
EMC EN 50091-2 and FCC Class A
31
Building solutions
to manage and
monitor your UPS
32
Software Compatible with Operating system support*
NetWatch All models with ConnectUPS Windows 95/98/ME, NT, 2000, XP, 2003
OS Support Web/SNMP card Server, Novell NetWare,
SGI IRIX, HP-UX, IBM AIX, Linux, BSD, SCO,
Solaris, Mac OS X
33
Service
If you feel your chosen service package requires enhancement to comply with your needs, or you need a one-off
service to solve a particular problem, you can choose individual services for a small fee. Above is a brief list of what
we have to offer. Your Eaton representative will be delighted to tell you more.
34
Site inspections: Consultative service that aims at
securing the best possible operational environment for
your UPS system to ensure its fault-free operation.
Reports: After each maintenance visit, whether regular batteries in an environmentally sound fashion. When the
or emergency, you will receive a full written report on batteries are changed, all cabling will also be replaced
the fault and steps undertaken to repair it. to prevent problems through oxidisation. Finally,
the battery system is tested under normal operating
24-hour telephone support: 24-hour, 365-days-a- conditions.
year access to Eaton’s support engineers for immediate
help on your UPS system. Available free of charge to all System upgrades: During maintenance visits, our
BasicCare, PlusCare and PremiumCare customers. service engineers will analyse the load and performance
of your UPS system and, if necessary, suggest changes
ExpressChange: For “plug-and-play” units below to accommodate new needs. You will never find yourself
3 kVA, we offer the ExpressChange service. If a fault running an obsolete or undersized system.
develops in your device, Eaton will replace the unit
either permanently or for the time it takes to repair it. Spare parts: Entering a Eaton service agreement will
guarantee you the use of only the best quality, factory-
Extended warranty: For a small fee, you can extend approved spare parts. Authorised Eaton’s service
the warranty of your Powerware UPSs incrementally up representatives stock the most often needed spares,
to 2–3 years, depending on the product. and their stocks are quickly replenished from Eaton’s
strategically located regional logistics centres. The cost
Power quality analysis: As time goes by, the loads of spares is included in the PremiumCare service option.
on both your UPS system and the mains may change.
Eaton’s service engineers can analyse the quality of FORS (Full On-line Remote Service): Your UPSs can
the power being fed to your equipment and suggest link directly to Eaton’s regional Service Centre via a
remedies if necessary. modem. Remote monitoring software residing on Eaton’s
computers will keep an eye on your UPS status, sounding
Battery analysis and replacement: Because batteries an alarm immediately if its monitored parameters are out
are the most important part of a UPS system, we pay of the ordinary. The remote monitoring system can only
particular attention to their condition. Only rigorously link into your UPS system, it has absolutely no access to
tested, high-quality batteries are used in Powerware your business data. Alarms received through FORS will
UPSs. Battery life is optimised through our patented be relayed by mobile phone to Eaton’s duty engineer
ABMTM battery charging method. Eaton’s service who will take action immediately. FORS is an ideal
engineers will keep your batteries as good as new, enhancement to your service package. Ask your Eaton
changing them when necessary and disposing of the old representative for details.
35
Feature focus
36
Eaton’s Hot Sync™ Technology Moreover, the Hot Sync™ technology allows full
The absolute reliability of UPS system can be increased maintenance to be performed one-by-one on redundant
close to 100% with the patented Hot Sync™ parallel UPS modules without the external maintenance bypass
load sharing technology. It is designed for parallel switch. The critical load needs not to be removed from
redundant N+1 systems to satisfy the 7/24h applications. the conditioned power. Scheduled or unscheduled
The Hot Sync™ can also be used in parallel capacity maintenance needs can be perfomed with the critical
systems to benefit from the scalability for customer’s load supported constantly by the UPS grade clean
everincreasing load demands. power.
37
Powerware 9X55 8-15 kVA, internal battery capacity
38
UPS selection guide
Load 250 VA 500 VA 750 VA 1000 VA 1500 VA 2000 VA 2500 VA 3000 VA
Powerware cabinet UPSs
Series 3, standby
3105 350 VA 8
3105 500 VA 8 3
Series 5, line-interactive
5110 500 VA 8 3
5110 700 VA 14 6 31
5110 1000 VA 35 15 10 5
5115 500 VA 15 5
5115 750 VA 35 13 6
5115 1000 VA 38 15 8 5
5115 1400 VA 55 28 14 8 52
5125 1000 VA 38 16 10 5
5125 1500 VA 56 32 22 13 6
5125 2200 VA 125 60 44 28 15 7
5125 1000 VA + 1 battery cabinet 190 100 70 50
5125 1500 VA + 1 battery cabinet 240 140 100 60 35
5125 2200 VA +1 battery cabinet 280 160 115 75 50 30
Series 9, double conversion
9120 700 VA 28 13 83
9120 700 VA + 1 battery cabinet 105 50 35
9120 700 VA +2 battery cabinet 200 100 65
9120 1000 VA 45 21 15 8
9120 1000 VA + 1 battery cabinet 160 85 55 37
9120 1000 VA +2 battery cabinet > 4 hours 160 110 68
9120 1500 VA 55 28 20 14 7
9120 1500 VA + 1 battery cabinet 230 115 80 55 33
9120 1500 VA +2 battery cabinet > 4 hours 220 150 100 60
9120 2000 VA 120 65 40 30 19 12
9120 2000 VA + 1 battery cabinet > 7 hours >4 hours 180 125 70 55
9120 2000 VA +2 battery cabinet > 10 hours >7 hours >4 hours 220 140 100
9120 3000 VA 120 65 40 30 19 14 10 8
9120 3000 VA + 1 battery cabinet > 7 hours >4 hours 180 125 70 55 45 30
9120 3000 VA +2 battery cabinet > 10 hours >7 hours >4 hours 220 140 100 80 65
Powerware rackmount UPSs
Series 5, line-interactive
5115 RM 500 VA 15 5
5115 RM 750 VA 35 13 6
5115 RM 1000 VA 38 15 8 5
5115 RM 1500 VA 55 28 14 8 5
5125 RM 1000 VA 36 19 13 7
5125 RM 1500 VA 36 19 13 7 5
5125 RM 3000 VA 110 45 30 20 15 11 6 5
5125 RM backup time can be extended to approx. 50 min. at full load by adding battery modules
Series 9, double conversion
9125 RM 1000 VA 35 15 9 5
9125 RM 1500 VA 60 40 25 16 8
9125 RM 2000 VA 60 40 25 16 8 5
9125 RM 3000 VA 80 45 30 21 13 9 7 5
9125 RM backup time can be extended to approx. 100 min. at full load by adding battery modules
39
EUROPE/MIDDLE EAST/ AMERICAS ASIA PACIFIC
AFRICA LOCATIONS
UNITED STATES AUSTRALIA
DENMARK World headquarters 119-127 Wicks Road
Østmarken 9 8609 Six Forks Road North Ryde
DK-2860 Søborg Raleigh, NC 27615 Sydney 2113 NSW
Tel. +45 3686 7910 Tel. +1 919 872 3020 Tel. +61-2-9878 5000
RUSSIA
Electrozavodskaya str. 33, building 4
107076 Moscow
Tel. +7 095 787 2890
SWEDEN
Sågvägen 2
S-184 25 Åkersberga
Tel. +46-8-598 940 00
UNITED KINGDOM
221 Dover Road
Slough SL1 4RF
Berkshire
Tel. +44-1753-608 700
40