DISTRIBUTION SOLUTIONS

TJO 7
Outdoor voltage transformers

The TJO 7 single-pole insulated


voltage transformers are cast in
outdoor epoxy resin and are
designed mainly for insulation
voltages up to 40.5 kV. Insulation
voltages different from the above
are to be the subject of an
agreement between the
manufacturer and the customer.
Alternative insulation voltages are
available to special order. Standard
transformers incorporate an
overvoltage factor of 1.9 Un/8 hrs.

Description The transformers are designed and manufactured


One outlet of the primary winding, including its ter- to conform with the requirements and recommen-
minal, is insulated from earth at the rated insulation dations of the following standards: IEC, EN, VDE,
value. The other outlet of the primary winding, to- ANSI, BS, GOST, ČSN and PN-EN.
gether with its terminal, is earthed during opera-
tion. Most transformers are equipped with two sec- —
Parameters
ondary windings, the first is either for measurement
20:√3; 22:√3; 27:√3;
or protection purposes, the other is for connection Rated primary voltages 1) [kV]
30:√3; 33:√3; 35:√3
into an open-delta configuration in a three-phase Rated secondary voltages 1) 2) [V] 100:√3; 110:√3
system. One terminal of each secondary winding Rated voltages for open-delta
[V] 100:3; 110:3
and one of the open-delta connected terminals connection 1)
must be earthed during the transformer operation. Rated frequency [Hz] 50; 60
The secondary windings are led out into a cast-type Highest voltage for equipment [kV] up to 40.5
secondary terminal board covered with a sealed Rated power-frequency withstand
[kV] up to 95
plastic cover. voltage (r.m.s.), 1 min.
Rated lightning impulse
[kV] up to 200
withstand voltage (peak)
The transformer body is fixed by four screws, the Max. rated burden/classes 50/0.2; 150/0.5;
[VA/cl]
bolted earthing clamp is located on the transformer – measurement winding 250/1
base plate. For ease of handling and assembly the Max. rated burden/classes
[VA/cl] up to 200/3P or 6P
– residual winding
transformer is supplied with four suspension lugs
Rated thermal limiting output [VA] 1000
fixed to the base plate.
1)
Other voltages can also be supplied on request.
2)
Accuracy classes 0.2; 0.5; 1 (measurement winding) or 3P; 6P
By special order, the transformer can also be sup- (protection winding).

plied with a primary winding designed for two dif-


ferent primary voltages (with reconectable second-
ary winding).

Dimension drawing
weight: 52-55 kg
creepage distance: 1120 mm

340 250
M12

(40)

90 680

M8
N

5
55

10 170
220
450

4xØ12,2
15
190

310 15


ABB Contact Center
tel.: +48 22 22 37 777
contact.center@pl.abb.com

ABB Sp. z o.o.


Branch in Przasnysz
59 Leszno St.
06-300 Przasnysz, Poland
Phone: +48 22 22 38 900
3405PL402-W3-en. Edition 11.2018

Fax: +48 22 22 38 950


— —
For additional information please contact We reserve the right to make technical We reserve all rights in this document and
your local ABB representative or visit web changes or modify the contents of this do- in the subject matter and illustrations con-
page. cument without prior notice. With regard tained therein. Any reproduction, disclo-
to purchase orders, the agreed particulars sure to third parties or utilization of its
shall prevail. ABB does not accept any re- contents – in whole or in parts – is forbid-
sponsibility whatsoever for potential er- den without prior written consent of ABB.
rors or possible lack of information in this © Copyright 2018 ABB All rights reserved
www.abb.com document.

You might also like