Professional Documents
Culture Documents
Etp820S - Electrical Protection 425: S E D E E
Etp820S - Electrical Protection 425: S E D E E
Etp820S - Electrical Protection 425: S E D E E
na
SCHOOL OF ENGINEERING DEPARTMENT OF ELECTRICAL ENGINEERING http://www.polytechnic.edu.na/EEE
The portion of a power system shown by the one-line diagram of Figure Q1.1, with generating sources back
of all three ends, has conventional primary and back-up relaying. The numbered boxes indicate the locations
of the circuit-breakers (CBs).
In each of the cases listed in Table Q1.1, a short-circuit has occurred and certain circuit-breakers have tripped
as stated.
Assume that the tripping of these circuit-breakers was correct under the circumstances.
Where was the short-circuit? Was there any failure of the protective relaying, including breakers and if so,
what failed? Assume only one failure at a time.
Draw a sketch showing the overlapping of primary protective zones and indicate the exact locations of the
various faults in Table Q1.1.
NB: Name the bus-bus as BB1, BB2, etc., the lines as L1, L2, etc. and the protective zones as Zone 1, Zone 2,
etc., from left to right.
Figure Q1.1.
Table Q1.1
Case CBs Tripped Location of Fault What Failed? Main Protection (CBs) Back-up Protection (CBs)
a 4, 5, 8
b 3, 7, 8
c 3, 4, 5, 6
d 1, 4, 5, 6
e 4, 5, 7, 8
f 4, 5, 6
Solutions:
1
The network divided into zones of protection:
Table Q1.1
Case CBs Tripped Location of Fault What Failed? Main Protection (CBs) Back-up Protection (CBs)
2
(a) Define the following: (1) Auto-recloser and (2) Single-shot reclosing (6 marks)
Answers:
(1) An auto-recloser is a circuit breaker equipped with a mechanism that can automatically close the breaker
after it has been opened due to a fault. (3.0 marks)
(2) Single-shot reclosing is an operation sequence providing only one reclosing operation, lockout of the
circuit occurring on subsequent tripping. (3.0 marks)
(b) Figure Q2.1 shows a typical single-shot automatic reclosing (auto-reclose) scheme. It shows a successful
re-closure in the event of a transient fault. Complete the diagram by naming the ‘times’ indicated by the
encircled numbers and define ‘times’ 1, 3 and 5. (11 marks)
Figure Q2.1.
Answers:
The ‘times’:
(1) Protection operating time.
(2) Circuit-breaker operating time.
(3) Circuit-breaker dead time.
(4) Auto-reclose relay operating time.
(5) Auto-reclose relay dead time.
(5.0 marks)
Definitions:
(1) Protection operating time: The time from the inception of the fault to the closing of the tripping contacts.
Where a separate auxiliary tripping relay is employed, its operating time is included. (2.0 marks)
(3) Circuit-breaker dead time: The interval between interruption in all circuit-breaker poles on the opening
stroke and the making of the contacts and hence re-establishment of the circuit on the reclosing stroke.
(2.0 marks)
(5) Auto-reclose relay reclaim time: The time required, after one or more counting operations, for the
counting mechanism to return to the starting position. (2.0 marks)
3
(c) The arrangement shown in Figure Q2.2 consists
basically of two transformer feeders, EHV Line 1
and EHV Line 2, interconnected by a single circuit-
breaker, 120.
Answers:
(1) A transient fault on Line 2 causes tripping of circuit-breakers 120 and B2 followed by re-closure of CB 120.
If the re-closure is successful, Transformer T2 is re-energised and circuit breaker B2 Re-closes after a short
time delay. (4.0 marks)
(2) If the line fault is persistent, 120 trips again, after the first attempt at re-closure followed by the automatic
opening of the motorised line isolator 203.
Circuit-breaker 120 re-closes again, followed by the re-closer of circuit-breaker B1, so that both transformers
T1 and T2 are then supplied from Line 1. (4.0 marks)
AUTO-CLOSE SCHEMES
4
Auto-close schemes are employed to close,
automatically, circuit-breakers that are
normally open when the supply network is
healthy.
Solution:
The starting circuits for breaker CB4 monitor the operation of transformer protection on any of the
transformers T1, T2 and T3 together with the tripping of an associated circuit-breaker CB1-CB3. … (2.0)
In the event of a fault, the auto-close circuit is initiated and circuit-breaker CB4 closes, after a short time
delay, to switch in the stand-by transformer. … (2.0)
Some schemes employ an auto-tripping relay, so that when the faulty transformer is returned to service, the
stand-by is automatically disconnected. … (2.0)
Solution:
The bus section breaker should be auto-closed in the event of the loss of one transformer, to spread the load
over the remaining transformers. … (2.0)
Starting and auto-trip circuits are employed as in the stand-by scheme. … (2.0)
The auto-close relay used in practice is a variant of one of the standard auto-reclose relays.
(a) Briefly explain the working principle of operation of a circuit-breaker. (12 marks)
Answer:
5
The main parts of a circuit-breaker, in as far as its
operation is concerned, are the trip coil, the
latching mechanism, the main contacts, the
opening spring and the auxiliary contacts. See
Figure Q4.1. … (2.0)
Operation:
(iv) The trip coil is de-energised by the opening of the circuit-breaker auxiliary contacts that are in series with
the coil. … (1.0)
(b) Draw a schematic diagram showing the complete three-phase connections of a protective relay/circuit-
breaker scheme with the associated components. Assume voltage-current relays. Show on a separate
diagram (Figure (b)) the circuit-breaker tripping coil circuit. NB: Your schematic should include the contacts,
coils, switches, etc… (10 marks)
6
Figure Q4.2. Complete three-phase connections of a protective relay/circuit- breaker scheme with the
associated components
(10.0 marks)
7
(ii) If the circuit-breaker has tripped, in the event of a fault in the power circuit, a red bulb must be lit. The
red bulb should stay on, for as long as it has not been re-set, long after the circuit-breaker has tripped.
(iii) In the event that the circuit breaker fails to trip during a fault condition, an alarm must sound and it can
only be cancelled manually.
Solution:
(i) With a healthy power circuit, the circuit-breaker is in circuit and its two auxiliary pairs of contacts, 52a and
52b, are closed. Relay A is energised and it closes its pair of contacts which in turn energises relay D. Relay D
closes its NO contacts in the ‘green bulb, CB-energised’ indicator circuit and opens its NC contacts in the ‘red
bulb CB-tripped’ indicator circuit.
(ii) With a fault in the power circuit, the protection relay operates and PR closes, energising the CB trip coil
which in turn trips the CB. Relay B gets energised and it provides the holding contact for PR when the
protection relay resets. Relay A is shorted releasing its contacts open which in turn de-energises relay D. The
pair of contacts in the ‘green bulb circuit’ opens, turning the green bulb off. Relay D’s NC contacts close to
complete the ‘red bulb circuit’ turning on the ‘CB-tripped’ indicator red bulb. Relay C also gets energised but
before its NO time-delayed pair of contacts could close to sound the alarm and before its time-delayed pair
of NC contacts could open, the CB auxiliary pairs of contacts 52a and 52b open to de-energise both relays B
and D. Though relay A is re-energised, relay D stays de-energised through 52b. Closing the CB will revert the
circuits to the status of section (i).
(iii) In the event of a fault and the failure of the CB to trip, relay C succeeds in having its time-delayed pair of
contacts closed, sounding the alarm. At the same time its time-delayed pair of NC contacts in the ‘red bulb
CB-trip’ indicator circuit are opened to prevent the red bulb from being lit. The alarm will sound indefinitely if
the CB status does not change until it is cancelled.
Allocation of marks: each pair of contacts carries 1.0 mark + the correct positioning of the relays/trip-coil,
another 1.0 mark = 10.0 marks in total.
8
Figure Q5.1. Trip-circuit supervisory circuit.