Medium Voltage Product

BDG 072Ax
Indoor current transformers

Highest voltage for equipment [kV] 0,72


Power frequency test voltage, 1 min. [kV] 3

Rated primary current [A] 2000 – 57000


Rated short-time thermal current [kA] 130(3s) - 210 (3s)
Rated dynamic current [kA] 360-575
Reconnectable secondary

Description Technical data


The indoor current transformer type BDG without primary The transformers are designed and manufactured in
conductor designed for installation in generators circuit-bre- conformity with the following standards:
akers systems. t IEC 60044-1: Instrument transformers - Part 1: Current
The BDG current transformers have the possibility of transformers
reconnection on secondary side tCSN EN 60044-1: Instrument transformers - Part 1:
The maximum number of secondary windings is 3 with Current transformers
maximum 12 secondary terminals without possibility of direct tGOST 7746-2001: Current transformers
grounding thus the connection of each secondary to ground
requires separate leads (not part of delivery). There are more The transformer can be installed by authorized person only
details on BDG current transformer installation in separate and need to comply with instructions for installation, use
manual available upon request. and maintenance.
The secondary windings are designed for metering or Standardized insulation level of BDG transformers
protection purposes. One terminal of each used secondary Standard insulation level: 0.72 / 3 / - kV
winding and one terminal of not used winding have to be Code designation -BDG current transformers
earthed during the transformer operation (not used short-cir-
cuited also). The terminals allow M4 connection. The BDG 072A1 – multi core design body up to 18000A
transformer can be mounted in any position and it is fixed by BDG 072A2 – multi core design body up to 23000A
four M16 bolts. BDG 072A3 – multi core design body up to 57000A

BDG 072 A x
Voltage dimension
0.72 kV 1… inner diameter 870mm
2… inner diameter 940mm
3… inner diameter 1260mm
Technical data

Types BDG 072 A1 BDG 072 A2 BDG 072 A3


rated voltage Up to 0,72 Up to 0,72 Up to 0,72
rated primary current max. [A] 18000 23000 57000
rated primary current min. [A] 2000 3000 4000
Rated frequency [Hz] 50/60 50/60 50/60
rated secondary current [A] 1 or 5 1 or 5 1 or 5
rated burden max. (per core) [VA] 200 200 200
rated acc. Class best IEC 0.1 0.1 0.1
rated acc. Class best ANSI 0.3 0.3 0.3
number of cores per frame max. 3 3 3
protection class IEC 5P or 10P 5P or 10P 5P or 10P
ambient temperature categories [ºC] -45...+80 -45...+80 -45...+80
temperature for transport [ºC] -50...+80 -50...+80 -50...+80
Power frequency withstand voltage [kV] 3 3 3
Ith rated short-time current [kA/3s] 130 130 210
Idyn dynamic withstand current [kA] 360 360 575

Marking of current transformer outlets

Examples of secondary terminal marking:


Dimensions

BDG 072A1

Drawing no. Polarity

1VL4600822R0101 P1-P2
1VL4600822R0102 P2-P1

weight of the transformer depend on number of cores and their parameters 20 - 60kg
Dimensions

BDG 072A2

Drawing no. Polarity

1VL4600823R0101 P1-P2
1VL4600823R0102 P2-P1

weight of the transformer depend on number of cores and their parameters 30 - 70kg
Dimensions

BDG 072A3

Drawing no. Polarity

1VL4600824R0101 P1-P2
1VL4600824R0102 P2-P1

weight of the transformer depend on number of cores and their parameters 45 - 90kg
ABB s.r.o.
PPMV Brno

1VLC000502 - Rev.4, en 2012. 12. 13


Division of Instrument Transform ers The data and ilustrations in this catalogue are not
binding. We reserve the right to make changes of the
Videnska 117
content, in the course of technical development of the
619 00 Brno, Czech Republic product.
E-mail: info.ejf@cz.abb.com
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
www.abb.com