Professional Documents
Culture Documents
Inerting Docu
Inerting Docu
1. Purpose
The purpose of this document is to prevent the fire and explosions in process
centrifuging operations.
2. Scope
This is applicable all the basket type centrifuges used in manufacturing at all the CTO
sites
3. Responsibility
4. Guidelines
The centrifuge should be leak free and should be maintained to ensure that there are no
leakages through the lid and body gaskets
The maximum allowable leak rate is 100 m bar in 60 minutes
The centrifuge and the connected equipment should be inertised to a sufficient degree
therefore, oxygen is not permeating into the filtration system
The possibility of air leaking into the centrifuge through feed and vent line should be
prevented by suitable means
Provide separate inerting lines to the centrifuge bearing housing, basket, feed vessel
and receivers
Liquid seal with controllable liquid level in filtrate line to be provided
Filtrate discharge line should be sufficiently sized and sloped that accumulation and
vapor lock in the line is prevented. Discharge line diameter should be minimum 2xD
( D – diameter of feed pipe ). The slope to be min 100 mm in 1 mtr.
Nitrogen pressure required in side the basket is in the range of 10 to 15 mbar
Nitrogen pressure required in the bearing housing is in the range of 15 to 20 mbar
Pressure Relief to avoid excess pressure in the centrifuge to be provided
Sufficient level of automation to be provided to ensure the following
o Sufficient Nitrogen flow is maintained
o Sufficient Nitrogen pressure is maintained in the system
Page 1 of 5
CTO BEST PRACTICES Draft
Author: S.R.Pandian Supersedes Doc Date:
INERTING OF BASKET
Release Date: 25.09.08
CENTRIFUGES
Released By : Guideline No – CTO ENGG BP 001 ISSUE 1
Martin Ghosh
5. Interlocks
Power to the centrifuge should have an interlock with the set point of the nitrogen
inerting pressure in the centrifuge system
Nitrogen supply should be automatically cut off, on opening of the centrifuge lid
The centrifuge and the feed valve not to operate if the O2 level in the centrifuge is above
5%
6. Procedure
The following are the established procedure to operate any process centrifuge handling
flammable slurries.
6.1 Pre-flushing
Before starting the filtration operation in the centrifuge, the centrifuge is pre
flushed with N2 until the O2 sensor reads 5%. This is done by selecting the Pre-flush
mode in the PLC. The PID valve for Basket and for bearing housing open fully and
allow more N2 to flow into the system. The following points ensure that the pre-flushing
can be stopped and Blanketing can be selected in the PLC.
The PID valves’ opening percentage and the flow rate for pre-flushing are
selected depending upon the size and model of the centrifuge.
6.2 Blanketing
There should be some over pressure maintained in the centrifuge basket and in
the bearing housing of the centrifuge during the operation. Select Blanketing in the PLC
and ensure the following are maintained in the system,
Page 2 of 5
CTO BEST PRACTICES Draft
Author: S.R.Pandian Supersedes Doc Date:
INERTING OF BASKET
Release Date: 25.09.08
CENTRIFUGES
Released By : Guideline No – CTO ENGG BP 001 ISSUE 1
Martin Ghosh
The PID valve opening percentage and the flow rate for blanketing are selected
depending upon the size and model of the centrifuge.
6.3 Alarms
7. Oxygen Analyzer
The sensor of the O2 analyzer must be protected against direct contact with
liquid solvents or their mist. Frequent check is essential to purge the sensor of the O2
analyzer with ambient air to ensure that it reads correctly (calibration to 21% Vol.). This
frequency shall be validated on case to case basis. Defective sensor to be replaced and
necessary actions has to be initiated.
Page 3 of 5
CTO BEST PRACTICES Draft
Author: S.R.Pandian Supersedes Doc Date:
INERTING OF BASKET
Release Date: 25.09.08
CENTRIFUGES
Released By : Guideline No – CTO ENGG BP 001 ISSUE 1
Martin Ghosh
Page 4 of 5
CTO BEST PRACTICES Draft
Author: S.R.Pandian Supersedes Doc Date:
INERTING OF BASKET
Release Date: 25.09.08
CENTRIFUGES
Released By : Guideline No – CTO ENGG BP 001 ISSUE 1
Martin Ghosh
LEGENDS
All the control valves are in closed condition prior to start of the centrifuging operation.
The operator select the pre-flushing mode of inerting cycle in PLC before loading the
centrifuge. Valves CV1 and CV2 open and allow high flow of N2 into the system. The O2
sensor senses the presence of the O2 in the basket continuously and displays the same
in the HMI panel. The PS1 installed on the bearing housing N2 pipe measure the
pressure in the bearing housing and gives signal to close CV2 on the vent line and
ensure that the N2 pressure in the bearing housing is within the specified limit. PLC gives
a “centrifuge ready to load” display once the O2 % and the N2 pressure in the system
reaches with in the specified or “safe to operate” limits of the particular centrifuge. The
operator select the blanketing mode in the PLC now.
In the blanketing mode the PLC set the PID valves’ open position in the
minimum( predetermined % ) level and ensure a minimum flow of N2 is allowed to
maintain the required over pressure in the centrifuge basket and in the bearing housing.
CV2 will on/off depending upon the signal from PS1 to maintain the over pressure in the
system.
If the pressure in the system goes below the LOW LOW set point PS1 activate audio
visual alarm and simultaneously open CV1 to high flow levels to allow more N2 flow into
the system. If the pressure in th system reaches HIGH HIGH then CV2 open and release
pressure to vent and maintain the required pressure in the system.
CV2 installed on both the vent lines will go on and off to maintain the pressure in the
system. They remain close if the pressure in the system is within the specified limit. They
open if the pressure reaches HIGH HIGH set point. They will close once the pressure
drops down to HIGH set point.
Page 5 of 5