Service Setup Manual: Svmim-M3
Service Setup Manual: Svmim-M3
Service Setup Manual: Svmim-M3
Ver.4.0
Jul. 28th 2018
SVMIM-M3
1
Main menu
Service setup screen can be accessed from a web browser using
“IPaddress/service”. First to find the IP address of the SVM, run the “FindSVM.exe”
program provided.
“FindSVM.exe” program screen should appear. The SVM should show up in the
screen. Take note of the IP address.
“FindSVM.exe” program screen
In the example shown above, the service setup screen can be accessed from a web
browser using “192.168.1.98/service”.
From the SVM Service setup screen, below functions can be set.
Service setup screen for SVMPC1 Service setup screen for SVMPC2
SVMIM-M3
3
Network setting
SVM controller has to set network parameter(IP address, netmask, default gateway
and DNS server) and both wired and wireless connection is available.
SVMIM-M3
4
Wifi setting
(1) Set SSID and PIN code
In case of WiFi connection is selected, click “WiFi Setup(SSID)” to set SSID and
PIN code for WiFi connection on WiFi setting screen. If PIN code is not set for the
WiFi network, then PIN code entry should be empty. Then click “Set” and setup is
finished when “OK” dialog is appeared.
SVMIM-M3
5
Timezone setting
Click “Timezone setup” on the service menu screen to open setup screen, and
select your timezone in the list.
After selecting the timezone, please click “Set” button to store this setting and
restart SVM controller.
SVMIM-M3
6
Alert mail setting
Please prepare mail server information below to send e-mail.
SMTP server address
SMTP server port number Example: In the case of Gmail
SMTP server user name SMTP server address: smtp.gmail.com
SMTP server user password SMTP server port number: 587
Note 1: When Gmail server is used, “Allow less secure apps” should set to “ON”.
Otherwise SVM controller cannot send mail to Gamil server.
Note 2: Confirm the SVM controller is connecting to internet connectable network
and set network parameter to access to the internet.
First, click “Alert mail setup” on the service setup screen to open alert mail setup
screen.
SVMIM-M3
7
(2) Set parameters to send alert mail
Set below parameter on the screen. And then click “Set” button. It will appear “OK”
dialog when the setting is succeeded. After that, please reboot SVM controller.
SVMIM-M3
8
Device connection setting
Device connection setting has to be done during installation process.
DTA116A51
Click “Controller Connection Setup” on the service setup screen, then device
connection setting screen will be appeared.
Under “USB port connection devices”, click on “Add” next to DTA116A51. The
Device ID should be “1” and the USB port should be “USB1”.
Smart Meter
If smart meter is required, click on “Add” next to Smart Meter. Connect the Smart
Meter USB connection to USB2 if there is only one DTA116A51 connection, or to
USB3 if there are two DTA116A51 connections.
Click on the “Meter Type” column to select the model of the smart meter being
used.
Please click on “Save” button on the bottom of the screen to save all edited settings
and reboot the SVM controller to run with the setting.
SVMIM-M3
9
Click “Controller Connection Setup” on the service setup screen, then device
connection setting screen will be appeared.
Under “LAN connection devices”, click on “Add” next to the device type you are
connecting to.
The Device ID should be “1”. If more than one of each device connection is
connected, each device connection will need a unique Device ID.
Click on the “IP Address” controller and key in the IP address of the device.
The port number is already set with the default port number for each device type.
Click and change the port number only if the controller’s ports are not using the
default settings.
*Note: Default port number for iTM is 8081, iTC is 80, WAGO and D-Mobile is 502.
Please click on “Save” button on the bottom of the screen to save all edited settings
and reboot the SVM controller to run with the setting.
SVMIM-M3
10
In case iTM is connected to SVM, port number, user name and password have to
set for iTM. In case iTC is connected to SVM, port number has to set for iTC. Please
refer below in deatil.
IP address
Port Number
User Name
Password
Note: Please ensure username “svm” and password “svm” is set up in iTM.
Port Number
SVMIM-M3
11
Management Point attribute setting
Sometimes, SVM controller receives incorrect information of management point,
especially in case of iTC, all indoor unit information is incorrect. At that time,
SVM application shows wrong information. To solve this issue, this function can be
used.
To use this function, click “Point Setup” on the service setup screen. Then please
set management point attribute for each management point by following below
instruction.
Click icon then the color will Drag & Drop each line to change
change to gray. This means it will the order of management point.
delete this management point.
SVMIM-M3
12
USB converter model check
This function use to check if a USB converter can use for SVM controller.
Currently, SVM controller can use USB converter which uses PL2303 chip set.
Unfortunately, we have 2 types of USB converter using PL2303 chip set and
CH340 chip set in the market and both are the same look.
SVMIM-M3
13
Optional function setting
Click “Optional Function Setup” on the service menu screen to open setup screen
and select the optional functions.
After selecting the optional functions, please click “Set” button to store this setting.
SVMIM-M3
14
Site Information Setup for MSM
Click “Site Information Setup for MSM” on the service menu screen to open setup
screen to setup local site information for MSM.
After keying in the local site information, please click “Save” button to save.
SVMIM-M3
15
Visual Screen Editor
Visual Screen Editor is a tool to make visualized monitoring screen. To open this
tool, click “Visual Screen Editor” in the Service Menu.
SVMPC1 has 2 types of monitoring screen, Top screen and Section screen. The
Top screen displays screen buttons that access to the Section screens. The
Section screen displays management point cell/icon. These screens can be
modified by specifying background image and changing the location of screen
buttons and management point icon on this tool.
Visual Screen editor for Top Screen
SVMIM-M3
16
Switching To Visual Screen
Under standard mode, screen buttons and management point cells are displayed
in a fixed title pattern on monitoring screen. This monitoring screen is called
“Standard mode”. It is necessary to change to “Visual mode” to make visualized
screen. To change to Visual mode is just switch to “Visual” in Screen Type. When
the Screen Type is changed to Visual, Background Image selection button will be
appeared.
For Top screen
Click
SVMIM-M3
17
Relocating the screen buttons and management points
At first, all the screen buttons and management point icons will be aligned
together at the top left corner. All buttons and icons should be moved to required
point. It just can be done by drag & drop by mouse.
Tips : Drag & drop with Shift Key to allow easy aligning of buttons and icons.
Save Data
Save Data button saves all screen layout data to SVMPC1. Don’t forget to save data
before leaving this tool. Otherwise all layout data will be missing.