PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-1F-1 MOUNTING LOCATION :
AREA/EQPT.SERVED : RAW MATERIAL MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Outdoor lighting 3 380 0.80 1.00 1.25 3 1.52 1.90 ELCB 16
2 Lighting 1 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
3 Lighting 2 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
4 Lighting 3 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 Lighting 4 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
6 Lighting 5 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
7 Lighting 6 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
8 Lighting 7 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
9 Exit & EM 1 230 0.10 0.13 1.25 2 0.54 0.68 MCB 16
10 Rec-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
11 Rec-2 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
12 Rec-3 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
13 Rec-4 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
14 Rec-5 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
15 Air shower -1 1 230 2.50 3.13 1.25 2 13.59 16.98 MCB 20
16 Air shower -2 1 230 2.50 3.13 1.25 2 13.59 16.98 MCB 20
17 Air Curtain-1~2 1 230 0.50 0.63 1.25 2 2.72 3.40 MCB 16
18 EF-11-1 3 380 3.70 4.63 DOL 1.25 3 7.03 8.78 MCB 16
19 EF-GENERATOR 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 MCB 16
20 EF-POWER RECIVE 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 MCB 16
21 EF-BLOWER 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 MCB 16
19 Spare 1 230 0.25 0.31 1.25 2 1.36 1.70 MCB 16
20 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
21 Space 1 230 1.25 2 0.00 0.00 MCB 16
22 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 24.20 30.25 0.00 0.00 0.00 0.00 1.25 3 43.66 54.58 MCCB 63 63
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-1F-2 MOUNTING LOCATION :
AREA/EQPT.SERVED : ELECTRICAL ROOM MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Lighting-1 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
2 Lighting-2 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
3 Lighting-3 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
4 Lighting-4 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 Lighting-5 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
6 Lighting-6 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
7 Lighting-7 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
8 Exit & EM 1 230 0.10 0.13 1.25 2 0.54 0.68 MCB 16
9 Rec-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
10 Rec-2 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
11 Rec-3 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
12 Rec-4 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
13 Rec-5 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
14 Air shower -3 1 230 2.50 3.13 1.25 2 13.59 16.98 MCB 20
15 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
16 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
17 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
18 Space 1 230 1.25 2 0.00 0.00 MCB 16
19 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 16.20 20.25 0.00 0.00 0.00 0.00 1.25 3 29.23 36.54 MCB 30 30
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-1F-3 MOUNTING LOCATION :
AREA/EQPT.SERVED : PRODUCTION STOCK ROOM MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Lighting-1 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
2 Lighting-2 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
3 Lighting-3 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
4 Lighting-4 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 Lighting-5 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
6 Lighting-6 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
7 Lighting-7 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
8 Lighting-8 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
9 Lighting-9 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
10 Lighting-10 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
11 Lighting-11 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
12 Lighting-12 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
13 Exit & EM 1 230 0.10 0.13 1.25 2 0.54 0.68 MCB 16
14 Rec-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
15 Rec-2 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
16 Rec-3 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
17 Rec-4 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
18 Rec-5 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
19 Air curtain 1-4 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
20 LP-GH 3 400 6.00 5.80 1.25 3 8.37 10.46 MCB 16
20 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
21 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
22 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
23 Space 1 230 1.25 2 0.00 0.00 MCB 16
24 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 24.70 29.18 0.00 0.00 0.00 0.00 1.25 3 42.11 52.64 MCCB 63 63
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-GH MOUNTING LOCATION :
AREA/EQPT.SERVED : GH MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Outdoor lighting 3 380 0.80 0.80 1.25 3 1.22 1.52 ELCB 16
2 Lighting GH 1 230 0.80 0.30 1.25 2 1.30 1.63 MCB 16
3 Lighting GH FL 1 230 0.80 0.20 1.25 2 0.87 1.09 MCB 16
4 Rec-1 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 DP-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
6 IU AC GH 1 230 1.80 2.25 1.25 2 9.78 12.23 MCB 16
6 Spare 1 230 0.00 0.00 1.25 2 0.00 0.00 MCB 16
7 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 6.00 5.80 0.00 0.00 0.00 0.00 1.25 3 8.37 10.46 MCB 16 30
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-2F MOUNTING LOCATION :
AREA/EQPT.SERVED : 2FL MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Lighting 2 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
2 Lighting 2 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
3 Lighting 2 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
4 Lighting 2 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 Lighting 3 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
6 Lighting 3 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
7 Lighting 3 FL 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
8 Exit & EM 1 230 0.10 0.13 1.25 2 0.54 0.68 MCB 16
9 Rec-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
10 Rec-2 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
11 Rec-3 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
12 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
13 Spare 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
14 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 10.70 13.38 0.00 0.00 0.00 0.00 1.25 3 19.31 24.13 MCB 25 30
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : LP-GH MOUNTING LOCATION :
AREA/EQPT.SERVED : GH MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 Outdoor lighting 3 380 0.80 0.80 1.25 3 1.22 1.52 ELCB 16
2 Lighting RM 1 230 0.80 0.30 1.25 2 1.30 1.63 MCB 16
3 Lighting RM 1 230 0.80 0.20 1.25 2 0.87 1.09 MCB 16
4 Lighting BLOWER 1 230 0.80 0.20 1.25 2 0.87 1.09 MCB 16
4 Rec-1 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
5 DP-1 1 230 1.00 1.25 1.25 2 5.43 6.79 MCB 16
6 EF-101-1 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 MCB 16
7 EF-101-2 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 MCB 16
8 Spare 1 230 0.00 0.00 1.25 2 0.00 0.00 MCB 16
9 Spare 1 230 0.00 0.00 1.25 2 0.00 0.00 MCB 16
8 Space 1 230 1.25 2 0.00 0.00 MCB 16
9 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 6.50 5.63 0.00 0.00 0.00 0.00 1.25 3 8.12 10.15 MCB 16 30
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-FAN-1 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 AIR INTAKE UNIT SF-3 3 380 55.00 68.75 1.25 3 104.45 130.57 ELCB 150
2 CENTRIFUGAL FAN 12-2 3 380 45.00 56.25 DELTA-WYE 1.25 3 85.46 106.83 ELCB 125
3 CENTRIFUGAL FAN 11-1 3 380 15.00 18.75 DELTA-WYE 1.25 3 28.49 35.61 ELCB 40
4 CENTRIFUGAL FAN 11-2 3 380 15.00 18.75 DELTA-WYE 1.25 3 28.49 35.61 ELCB 40
5 CENTRIFUGAL FAN 12-1 3 380 15.00 18.75 DELTA-WYE 1.25 3 28.49 35.61 ELCB 40
6 CENTRIFUGAL FAN EX-1 3 380 15.00 18.75 DELTA-WYE 1.25 3 28.49 35.61 ELCB 40
7 CENTRIFUGAL FAN 12-1 3 380 4.00 5.00 DOL 1.25 3 7.60 9.50 ELCB 16
8 AXIAL FAN 12-1 3 380 2.20 2.75 DOL 1.25 3 4.18 5.22 ELCB 16
9 CENTRIFUGAL FAN RF-1 3 380 15.00 18.75 DELTA-WYE 1.25 3 28.49 35.61 ELCB 40
10 WALL FAN 37 3 380 0.75 0.94 DOL 1.25 3 1.42 1.78 ELCB 16
11 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
12 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
13 Space 1 230 1.25 2 0.00 0.00 ELCB 16
14 Space 1 230 1.25 2 0.00 0.00 ELCB 16

Main Breaker 3 400 181.95 227.44 0.00 0.00 0.00 0.00 1.25 3 328.28 410.35 MCCB 500 630
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-FAN-2 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 CENTRIFUGAL FAN 36-3 3 380 55.00 68.75 DELTA-WYE 1.25 3 104.45 130.57 ELCB 150
2 CENTRIFUGAL FAN EX-2 3 380 30.00 37.50 DELTA-WYE 1.25 3 56.98 71.22 ELCB 80
3 CENTRIFUGAL FAN EF-2 3 380 7.50 9.38 DOL 1.25 3 14.24 17.80 ELCB 20
4 AXIAL FAN 22-1 3 380 2.20 2.75 DOL 1.25 3 4.18 5.22 ELCB 16
5 AXIAL FAN 22-1 3 380 3.00 3.75 DOL 1.25 3 5.70 7.12 ELCB 16
6 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
7 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
8 Space 3 380 1.25 3 0.00 0.00 ELCB 16
9 Space 3 380 1.25 3 0.00 0.00 ELCB 16

Main Breaker 3 400 97.70 122.13 0.00 0.00 0.00 0.00 1.25 3 176.27 220.34 MCCB 225 250
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-FAN-3 MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 EF-12-1 3 380 5.50 6.88 DOL 1.25 3 10.45 13.06 ELCB 16
2 EF-B1-1 3 380 4.00 5.00 DOL 1.25 3 7.60 9.50 ELCB 16
3 EF-B1-2 3 380 7.50 9.38 DOL 1.25 3 14.24 17.80 ELCB 20
4 EF-12-1 3 380 4.00 5.00 DOL 1.25 3 7.60 9.50 ELCB 16
5 AIR SHOWER-4 1 220 2.50 3.13 1.25 2 14.20 17.76 MCB 20
6 AIR SHOWER-5 1 220 2.50 3.13 1.25 2 14.20 17.76 MCB 20
7 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 20
8 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 20
7 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
8 Spare 3 380 0.00 0.00 1.25 3 0.00 0.00 ELCB 16
9 Space 1 230 1.25 2 0.00 0.00 ELCB 16
10 Space 1 230 1.25 2 0.00 0.00 ELCB 16

Main Breaker 3 400 42.00 52.50 0.00 0.00 0.00 0.00 1.25 3 75.78 94.72 MCCB 100 125
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-CH-1 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 WATER CHILLER CR-1-1 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
2 WATER CHILLER CR-1-2 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
3 WATER CHILLER CR-1-3 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
4 WATER CHILLER CR-1-4 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
5 WATER CHILLER CR-1-5 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
6 WATER CHILLER CR-1-6 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
7 WATER CHILLER CR-1-7 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
8 WATER CHILLER CR-1-8 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
9 CHILLER WATER PUMP CP-1 3 380 2.20 2.75 1.25 3 4.18 5.22 ELCB 16
10 AHU AC-1 3 380 48.60 60.75 1.25 3 92.30 115.38 ELCB 125
11 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
12 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
13 Space 3 380 1.25 3 0.00 0.00 ELCB 16
14 Space 3 380 1.25 3 0.00 0.00 ELCB 16

Main Breaker 3 400 431.60 539.50 0.00 0.00 0.00 0.00 1.25 3 778.70 973.38 ACB 1000 1000
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-CH-2 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 WATER CHILLER CR-2-1 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
2 WATER CHILLER CR-2-2 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
3 WATER CHILLER CR-2-3 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
4 WATER CHILLER CR-2-4 3 380 47.60 59.50 1.25 3 90.40 113.00 ELCB 125
5 CHILLER WATER PUMP CP-1 3 380 1.50 1.88 1.25 3 2.85 3.56 ELCB 16
6 AHU AC-1 3 380 32.60 40.75 1.25 3 61.91 77.39 ELCB 80
7 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
8 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
9 Space 3 380 1.25 3 0.00 0.00 ELCB 16
10 Space 3 380 1.25 3 0.00 0.00 ELCB 16

Main Breaker 3 400 224.50 280.63 0.00 0.00 0.00 0.00 1.25 3 405.05 506.31 MCCB 600 630
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-AC-1 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : OUTDOOR MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 OU AC TRANS-1 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
2 OU AC 11-1-1 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
3 OU AC 11-1-2 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
4 OU AC 11-1-3 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
5 IU AC TR ROOM -1 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
6 IU AC TR ROOM -2 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
7 IU AC TR ROOM -3 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
8 IU AC 11-1 -1 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
9 IU AC 11-1 -2 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
10 IU AC 11-1 -3 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
11 IU AC 11-1 -4 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
12 IU AC 11-1 -5 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
13 IU AC 11-1 -6 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
14 IU AC 11-1 -7 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
15 IU AC 11-1 -8 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
16 IU AC 11-1 -9 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
17 IU AC 11-1 -10 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
18 IU AC 11-1 -11 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
19 IU AC 12-1 -1 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
20 IU AC 12-1 -2 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
21 IU AC 12-1 -3 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
22 IU AC 12-1 -4 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
23 IU AC 12-1 -5 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
24 IU AC 12-1 -6 3 380 5.00 6.25 1.25 3 9.50 11.87 MCB 16
25 IU AC 12-1 -1 3 380 1.70 2.13 1.25 3 3.23 4.04 MCB 16
26 OU AC 2FL 80 1 380 4.50 5.63 1.25 2 14.80 18.50 ELCB 20
27 OU AC 2FL 80 1 380 4.50 5.63 1.25 2 14.80 18.50 ELCB 20
28 OU AC 102 1 380 1.80 2.25 1.25 2 5.92 7.40 ELCB 16
29 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 16
30 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 16
31 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 16
32 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 16
33 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
34 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
35 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
36 Space 1 230 1.25 2 0.00 0.00 ELCB 16
37 Space 1 230 1.25 2 0.00 0.00 ELCB 16

Main Breaker 3 400 312.30 390.38 0.00 0.00 0.00 0.00 1.25 3 563.46 704.32 MCCB 800 800
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-AC-2 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : OUTDOOR MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 OU AC 12-3 3 380 12.50 15.63 1.25 3 23.74 29.67 ELCB 30
2 OU AC 12-3 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
3 OU AC 12-2-1 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
4 OU AC 12-2-2 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
5 OU AC 12-2-3 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
6 OU AC 12-2-4 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
7 IU AC 12-3-1 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
8 IU AC 12-3-2 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
9 IU AC 12-3-3 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
10 IU AC 12-3-4 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
11 IU AC 12-3-5 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
12 IU AC 12-3-6 3 380 2.70 3.38 1.25 3 5.13 6.41 MCB 16
13 IU AC 12-3-7 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
14 IU AC 12-3-8 1 230 1.70 2.13 1.25 2 9.24 11.55 MCB 16
15 IU AC 0.8KW 1 230 0.80 1.00 1.25 2 4.35 5.43 MCB 16
16 IU AC 1.1KW 1 230 1.10 1.38 1.25 2 5.98 7.47 MCB 16
17 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 40
18 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 40
19 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 30
19 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 30
20 Space 1 230 1.25 2 0.00 0.00 MCB 16
21 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 110.50 138.13 0.00 0.00 0.00 0.00 1.25 3 199.37 249.21 MCCB 250 250
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-AC-3 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : OUTDOOR MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 OU AC 3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
2 OU AC 3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
3 OU AC 3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
4 OU AC 5.7KW 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
5 OU AC 5.7KW 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
6 OU AC 5.7KW 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
7 OU AC 5.7KW 1 230 5.70 7.13 1.25 2 30.98 38.72 ELCB 40
8 OU AC 3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
9 OU AC 3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
10 OU AC NEW SPARE PART3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
11 OU AC NEW SPARE PART3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
12 OU AC NEW SPARE PART3.5KW 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
13 IU AC 22-1-1 3 380 4.00 5.00 1.25 3 7.60 9.50 MCB 16
14 IU AC 22-1-2 3 380 4.00 5.00 1.25 3 7.60 9.50 MCB 16
15 IU AC 22-1-3 3 380 4.00 5.00 1.25 3 7.60 9.50 MCB 16
16 IU AC 22-1-4 3 380 4.00 5.00 1.25 3 7.60 9.50 MCB 16
17 IU AC 22-2 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
18 IU AC 22-2 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
19 IU AC 22-2 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
20 IU AC 22-3 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
21 IU AC 22-3 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
22 IU AC 22-3 1.4KW 1 230 1.40 1.75 1.25 2 7.61 9.51 MCB 16
22 AIR SHOWER 4KW 1 230 4.00 5.00 1.25 2 21.74 27.17 MCB 30
23 AIR SHOWER 4KW 1 230 4.00 5.00 1.25 2 21.74 27.17 MCB 30
23 AIR SHOWER 4KW 1 230 4.00 5.00 1.25 2 21.74 27.17 MCB 30
23 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 20
24 SHUTTER DOOR 2KWX4 3 380 8.00 10.00 1.25 3 15.19 18.99 MCB 20
25 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 25
26 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 25
27 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
28 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 16
29 Space 1 230 1.25 2 0.00 0.00 MCB 16
30 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 103.20 129.00 0.00 0.00 0.00 0.00 1.25 3 186.20 232.74 MCCB 250 250
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-AC-4 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 OU AC 11-2 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
2 OU AC 11-2 1 230 3.50 4.38 1.25 2 19.02 23.78 ELCB 25
3 OU AC 11-1 3 380 31.00 38.75 1.25 3 58.87 73.59 ELCB 75
4 OU AC 12-1 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
5 OU AC 12-1 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
6 OU AC 3F-82 1 230 4.50 5.63 1.25 2 24.46 30.57 ELCB 32
7 OU AC 3F-82 1 230 4.50 5.63 1.25 2 24.46 30.57 ELCB 32
8 OU AC 3F-82 1 230 4.50 5.63 1.25 2 24.46 30.57 ELCB 32
9 OU AC 11-1 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
10 Spare 1 230 0.00 1.25 2 0.00 0.00 ELCB 30
11 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 30
12 Space 1 230 1.25 2 0.00 0.00 MCB 16
13 Space 1 230 1.25 2 0.00 0.00 MCB 16

Main Breaker 3 400 213.50 266.88 0.00 0.00 0.00 0.00 1.25 3 385.20 481.50 MCCB 500 630
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads
PROJECT: X-PROJECT

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP


PANEL DESIGNATION : MP-AC-4 (OUTDOOR) MOUNTING LOCATION :
AREA/EQPT.SERVED : ROOF MOUNTING METHOD :
FEED FROM : FEED TYPE :

System RATING LOAD DISTRIBUTION, KVA Breaker Breaker


CKT. NO. LOAD DESCRIPTION Ø
Voltage KW KVA AN BN CN 3ø % Pole Full Load Rating TYPE AT AF
1 OU AC 12-3 3 380 54.00 67.50 1.25 3 102.56 128.19 ELCB 150
2 OU AC 22-1 3 380 26.30 32.88 1.25 3 49.95 62.44 ELCB 63
3 OU AC 22-1 3 380 26.30 32.88 1.25 3 49.95 62.44 ELCB 63
4 OU AC 22-2 3 380 18.20 22.75 1.25 3 34.57 43.21 ELCB 50
5 OU AC 22-3 3 380 18.20 22.75 1.25 3 34.57 43.21 ELCB 50
6 Spare 3 380 0.00 1.25 3 0.00 0.00 ELCB 30
7 Space 3 380 1.25 3 0.00 0.00 MCB 16
8 Space 3 380 1.25 3 0.00 0.00 MCB 16

Main Breaker 3 400 143.00 178.75 0.00 0.00 0.00 0.00 1.25 3 258.00 322.50 MCCB 350 400
Apply 1.25% for Lighting and Receptacle Loads
Apply 1.25% for Power & Motor Loads
Apply ____% for Fire Pump Loads