Republic of the Philippines

GENERAL SANTOS CITY WATER DISTRICT

PUMP TEST DATA

Nature of Test : Laboratory Field

PUMP STATION NO. : LOCATION :

PUMP DATA ELECTRIC MOTOR DATA POWER USED :


Type Model Type Model
No. of Stage RPM Rated HP RPM
Rated Cap. Head Volt Ampere A
Make Serial No. Phase w/ S.F. A
Weight : kg. Hz.
REQUIRED Safety Factor Genset Total Running Time:
Min. Pump Efficiency (%) Make Motor Resistance :
Capacity Serial No.
TDH
RPM

Discharge Pumping Water Head Discharge Capacity


Voltage ( V ) Current ( A )
RPM Pressure Level Loss TDH inc. Volume Time
GPM
psi ft m ft ft (liter) (sec.) V1 V2 V3 V I1 I2

General Data :
Test Conducted By:
SWL
Pump Setting Orifice Dia.
Well Casing Dia. Test Pipe Dia.
Suction Pipe Dia.
Previous PWL :
PWL = Witnessed By:
Date Installed :
Date Repaired :
Supplier :
Note:
T

Date Tested :

Date Last Tested:

POWER USED : TIME TESTED :

Socoteco II Start :

Generator Set Finish:

Genset Total Running Time:


Motor Resistance :
L1 = Megaohms
L2 = Megaohms
L3 = Megaohms

Current ( A ) Motor Water Break Pump Eff.


PF
Eff. HP HP %
I3 I

Remarks: Passed

Failed
Republic of the Philippines
GENERAL SANTOS CITY WATER DISTRICT
E. Fernandez St., Brgy. Lagao, General Santos City

PUMP TEST DATA

Nature of Test : Laboratory Field Date Tested : June 19 2019

PUMP STATION NO. : 14 LOCATION : PRK. PROMISE LAND, BRGY. MABUHAY. GSC Date Last Tested:

PUMP DATA ELECTRIC MOTOR DATA POWER USED : TIME TESTED :


Type Model Type Model 2396048521
No. of Stage RPM Rated HP 100 RPM 3525 X Socoteco II Start : 8:30 AM
Rated Cap. 256 m^3/h Head Volt 460 Ampere 142 A
Make GRUNDFOSS Serial No. Phase 3 w/ S.F. 1.15 A Generator Set Finish: 8:40 AM
Weight : kg. Hz. 60
REQUIRED Safety Factor 1.15 Genset Total Running Time: 799.3
Min. Pump Efficiency (%) Make FRANKLIN ELECTRIC Motor Resistance :
Capacity Serial No. L1 = Megaohms
TDH L2 = Megaohms
RPM L3 = Megaohms

Discharge Pumping Head Discharge Capacity


Voltage ( V ) Current ( A )
RPM Pressure Water Level Loss TDH inches Volume Motor PF Water Break Pump
psi ft m ft ft lps m³/hr GPM V1 V2 V3 V I1 I2 I3 I Eff. HP HP Eff. %
30 69.30 30.83 101.12 5 175.42 118.00 519 465 457 462 461.33 72 73 72 72.3 0.9 0.80 23.00 55.78 41.23

General Data :
Test Conducted By: Remarks: Passed
SWL 30.50 m
Pump Setting 60 m Orifice Dia. 6 in RANDY M. RODA JOELY L. CASINAS Failed
Well Casing Dia. 350/250 Test Pipe Dia. 8 in
Suction Pipe Dia. 6 in Witnessed By:
Previous PWL : 30.76 m
PWL = 30.33 m

//PEMD Pump_test_form2017