MTS9000A Telecom Power User Manual Russia Veon MTS9304A-HD10A1 MTS93

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 112

MTS9000A Telecom Power (Russia, Veon,

MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)

User Manual

Issue 01

Date 2020-01-17

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://www.huawei.com

Email: support@huawei.com

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. i


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual About This Document

About This Document

Purpose
This document describes the product features, components, and maintenance methods.
Figures provided in this document are for reference only.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 Maintenance engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided, could
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to personal injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. ii


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual About This Document

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue 01 (2020-01-17)
This is the first official release.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. iii


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual Contents

Contents

About This Document .................................................................................................................... ii


1 Safety Precautions ......................................................................................................................... 1
1.1 General Safety .............................................................................................................................................................. 1
1.2 Personnel Requirements ............................................................................................................................................... 5
1.3 Electrical Safety ............................................................................................................................................................ 5
1.4 Installation Environment Requirements ....................................................................................................................... 7
1.5 Mechanical Safety ........................................................................................................................................................ 8
1.6 Battery Safety ............................................................................................................................................................. 11

2 Product Overview ....................................................................................................................... 15


2.1 Introduction to the MTS ............................................................................................................................................. 15
2.2 Cabinet Description .................................................................................................................................................... 16
2.2.1 MTS9304A-HD10A1 (H2 power cabinet) .............................................................................................................. 16
2.2.2 MTS9304A-AX10A1 (A2 power cabinet) .............................................................................................................. 18
2.2.3 MTS9514A-GX1401 (A3 power cabinet) ............................................................................................................... 20
2.2.4 MTS9300A-HX10A2 (H1 equipment cabinet) ........................................................................................................ 22
2.2.5 MTS9300A-AX10A1 (A1 equipment cabinet) ........................................................................................................ 24
2.2.6 MTS9300A-XA10A4 (A battery cabinet) ................................................................................................................ 26
2.2.7 DEU04D-H120A3 (DEU equipment cabinet) ......................................................................................................... 28

3 Components ................................................................................................................................. 31
3.1 Power Distribution Unit .............................................................................................................................................. 31
3.1.1 Power Subrack ......................................................................................................................................................... 31
3.1.2 AC Power Distribution Box (ACDB) ...................................................................................................................... 32
3.1.3 Intelligent Power Distribution Unit ......................................................................................................................... 35
3.1.4 Battery Power Distribution Box............................................................................................................................... 38
3.2 PSU (DPU40D-N06A3) ............................................................................................................................................. 39
3.3 Lithium Battery (DBU20B-N12A3) ........................................................................................................................... 43
3.4 Rectifier ...................................................................................................................................................................... 45
3.5 SMU02C ..................................................................................................................................................................... 47
3.6 User Interface Module UIM05B1 ............................................................................................................................... 51
3.7 PC300D ...................................................................................................................................................................... 52
3.8 DC Air Conditioner PC1000D-1 ................................................................................................................................. 53

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. iv


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual Contents

3.9 AH1500H .................................................................................................................................................................... 55


3.10 AC Heater HAU03A ................................................................................................................................................. 56
3.11 DC Heater HAU02D ................................................................................................................................................. 57
3.12 TCUC........................................................................................................................................................................ 58
3.13 Sensors ...................................................................................................................................................................... 59
3.13.1 Digital Temperature and Humidity Sensor ............................................................................................................ 59
3.13.2 Smoke Sensor ........................................................................................................................................................ 61
3.13.3 Water Sensor .......................................................................................................................................................... 61
3.13.4 Door Status Sensor................................................................................................................................................. 62
3.13.5 Battery Temperature Sensor ................................................................................................................................... 63

4 Maintenance ................................................................................................................................. 64
4.1 Routine Maintenance .................................................................................................................................................. 64
4.1.1 Cabinet ..................................................................................................................................................................... 64
4.1.2 AC and DC Power Distribution ............................................................................................................................... 65
4.1.3 Rectifier ................................................................................................................................................................... 66
4.1.4 SMU......................................................................................................................................................................... 67
4.1.5 Parameters on the SMU ........................................................................................................................................... 68
4.1.6 Cables ...................................................................................................................................................................... 69
4.2 Identifying Component Faults .................................................................................................................................... 69
4.2.1 Identifying Rectifier Faults ...................................................................................................................................... 69
4.2.2 Identifying SSU Faults............................................................................................................................................. 70
4.2.3 Identifying Circuit Breaker Faults ........................................................................................................................... 70
4.2.4 Locating AC Input Module Faults ........................................................................................................................... 70
4.2.5 Identifying SMU Faults ........................................................................................................................................... 70
4.3 Replacing Components ............................................................................................................................................... 70
4.3.1 Replacing a Rectifier ............................................................................................................................................... 71
4.3.2 Replacing a Circuit Breaker ..................................................................................................................................... 72
4.3.3 Replacing an AC Input Module ............................................................................................................................... 73
4.3.4 Replacing an SMU02C ............................................................................................................................................ 74
4.3.5 Replacing a UIM05B1 ............................................................................................................................................. 75
4.3.6 Replacing a DMU02C1 ........................................................................................................................................... 76
4.3.7 Replacing an AC Heater .......................................................................................................................................... 77
4.3.8 Replacing a DC Heater ............................................................................................................................................ 78
4.3.9 Replacing a TCUC Control Board ........................................................................................................................... 79
4.3.10 Replacing a Heat Exchanger Fan ........................................................................................................................... 82
4.3.11 Replacing an External Circulation Fan (DEU cabinet) .......................................................................................... 84
4.3.12 Replacing an Internal Circulation Fan (DEU cabinet) ........................................................................................... 86
4.3.13 Replacing a Heat Exchanger Core (DEU cabinet) ................................................................................................. 88
4.3.14 Replacing a Digital Temperature and Humidity Sensor ......................................................................................... 90
4.3.15 Replacing a Smoke Sensor .................................................................................................................................... 90
4.3.16 Replacing a Water Sensor ...................................................................................................................................... 92

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. v


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual Contents

4.3.17 Replacing a Door Status Sensor ............................................................................................................................. 92


4.3.18 Replacing a Battery Temperature Sensor ............................................................................................................... 93

A Technical Specifications ........................................................................................................... 95


A.1 Environmental Specifications .................................................................................................................................... 95
A.2 Electrical Specifications............................................................................................................................................. 96
A.3 EMC Specifications ................................................................................................................................................... 97

B Electrical Conceptual Diagrams .............................................................................................. 99


C Associations Between UIM Dry Contacts and Alarms ..................................................... 100
D Acronyms and Abbreviations................................................................................................ 104

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. vi


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

1 Safety Precautions

1.1 General Safety


Statement
Before installing, operating, and maintaining the equipment, read this document and observe
all the safety instructions on the equipment and in this document.
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document
do not cover all the safety instructions. They are only supplements to the safety instructions.
Huawei will not be liable for any consequence caused by the violation of general safety
requirements or design, production, and usage safety standards.
Ensure that the equipment is used in environments that meet its design specifications.
Otherwise, the equipment may become faulty, and the resulting equipment malfunction,
component damage, personal injuries, or property damage are not covered under the warranty.
Follow local laws and regulations when installing, operating, or maintaining the equipment.
The safety instructions in this document are only supplements to local laws and regulations.
Huawei will not be liable for any consequences of the following circumstances:
 Operation beyond the conditions specified in this document
 Installation or use in environments which are not specified in relevant international or
national standards
 Unauthorized modifications to the product or software code or removal of the product
 Failure to follow the operation instructions and safety precautions on the product and in
this document
 Equipment damage due to force majeure, such as earthquakes, fire, and storms
 Damage caused during transportation by the customer
 Storage conditions that do not meet the requirements specified in this document

General Requirements
 Before installing, operating, or maintaining the equipment, remove any conductive
objects such as watches or metal jewelry like bracelets, bangles, and rings to avoid
electric shock.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 1


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 When installing, operating, or maintaining the equipment, wear dedicated protective


gears such as insulation gloves, goggles, and safety clothing, helmet, and shoes, as
shown in the following figure.

 Use insulated tools or tools with insulated handles, as shown in the following figure.

 Follow the specified procedures for installation, operation, and maintenance.


 Ensure that bolts are tightened with a torque wrench and marked using red or blue color.
Installation personnel mark tightened bolts in blue. Quality inspection personnel confirm
if the bolts are tightened and then mark them in red. (The marks should cross the edges
of the bolts, as shown in the following figure.)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 2


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Before installing, operating, or maintaining a cabinet, clean up any water, ice, snow, or
other sundries on the top of the cabinet to prevent sundries from falling into the cabinet
when you open the cabinet door.
 Do not install, use, or operate outdoor equipment and cables (including but not limited to
moving equipment, operating equipment and cables, inserting connectors to or removing
connectors from signal ports connected to outdoor facilities, working at heights, and
performing outdoor installation) in harsh weather conditions such as lightning, rain,
snow, and level 6 or stronger wind.
 Before handling a conductor surface or terminal, measure the contact point voltage and
ensure that there is no risk of electric shock.
 Ensure that all slots are installed with boards or filler panels. Avoid hazards caused by
hazardous voltages or energy on boards. Ensure that the air channel is normal, control
electromagnetic interference, and prevent dust and other sundries on the backplane,
baseplate, and boards.
 After installing the equipment, remove idle packing materials such as cartons, foam,
plastics, and cable ties from the equipment area.
 In the case of a fire, immediately leave the building or the equipment area, and turn on
the fire alarm bell or make an emergency call. Do not enter the building on fire in any
case.
 Do not stop using protective devices. Pay attention to the warnings, cautions, and related
precautionary measures in this document and on the equipment. Promptly replace
warning labels that have worn out.
 Keep irrelevant people away from the equipment. Only operators are allowed to access
the equipment.
 All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the
unused cable holes with the caps delivered with the cabinet. The following figure shows
the criteria for correct sealing with firestop putty.

 Do not use water, alcohol, oil, or other solvents to clean electrical components inside and
outside a cabinet.

Personal Safety
 If there is a probability of personal injury or equipment damage during operations on the
equipment, immediately stop the operations, report the case to the supervisor, and take
feasible protective measures.
 To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
 Do not power on the equipment before it is installed or confirmed by professionals.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 3


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

Symbol Conventions
To ensure personal and equipment safety, observe all the safety instructions marked on the
equipment when installing, operating, and maintaining the equipment.

Symbol Description
Indicates a part exposed to high voltage. This symbol warns
operators that both direct and indirect contact with the power grid
is fatal. Such areas include hazardous voltage points or protective
power supply covers that may be removed during maintenance.
Warns users of overheating. This symbol is attached to a device
surface that may overheat and cause scalding. It warns users not to
touch the surface during operations or maintenance. Users should
wear heat insulation gloves before operations to prevent scalding.
Indicates protection earthing. This symbol is attached next to a
or protection ground terminal next to grounded equipment and an
external ground system. An equipment ground cable is connected
to an external ground bar through the protection ground terminal.
Indicates equipotential bonding. This symbol is found with
equipotential terminals inside equipment.

Indicates electrostatic discharge (ESD). This symbol is used in all


electrostatic sensitive areas. Before operating equipment in these
areas, wear ESD gloves or an ESD wrist strap.
Indicates that the equipment is safe to use at altitudes below 2000
m (6561.6 ft.).

Indicates that the equipment is not safe to use in tropical climates.

Indicates a fan assembly or moving part. This symbol is


silkscreened on or attached to the panel of a fan assembly,
or warning operators to keep away. Do not touch the blades when the
fan is rotating.

Indicates that users should refer to the instruction. This symbol is


used when the usage of a device port cannot be clearly described.
or For example, this symbol can be used in but not limited to the
following scenarios:
1. For a multi-power device, use it near the power supply to
replace the multi-power supply identifier. The symbol indicates
that the device has multiple power inputs. Therefore, when
powering off the device, you must disconnect all power inputs.
2. If there are multiple output ports, use the symbol near the
or
output ports. Connect cables according to the rated power
output and configuration parameter information in the
instruction.
3. If there are multiple slots, use the symbol near the slot

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 4


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

Symbol Description
information. For details, see the description of slot information,
restrictions on boards, and usage conditions in the instruction.

1.2 Personnel Requirements


 Personnel who plan to install or maintain Huawei equipment must receive thorough
training, understand all necessary safety precautions, and be able to correctly perform all
operations.
 Only qualified professionals or trained personnel are allowed to install, operate, and
maintain the equipment.
 Only qualified professionals are allowed to remove safety facilities and inspect the
equipment.
 Personnel who will operate the equipment, including operators, trained personnel, and
professionals, should possess the local national required qualifications in special
operations such as high-voltage operations, working at heights, and operations of special
equipment.

 Professionals: personnel who are trained or experienced in equipment operations and are clear of the
sources and degree of various potential hazards in equipment installation, operation, and
maintenance
 Trained personnel: personnel who are technically trained, have required experience, are aware of
possible hazards on themselves in certain operations, and are able to take protective measures to
minimize the hazards on themselves and other people
 Operators: operation personnel who may come in contact with the equipment, except trained
personnel and professionals

1.3 Electrical Safety


Grounding
 The protective ground of the equipment should be reliably connected to the ground
screw on the metal enclosure (grounding resistance ≤ 0.1 ohm).
 For the equipment that needs to be grounded, install the ground cable first when
installing the equipment and remove the ground cable last when removing the
equipment.
 Do not damage the ground conductor.
 Do not operate the equipment in the absence of a properly installed ground conductor.
 For the equipment that uses a three-pin socket, ensure that the ground terminal in the
socket is connected to the protection ground.

AC and DC Power

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 5


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 The power system is energized by power sources with hazardous voltage. Direct or
indirect contact (through damp objects) with the power sources may result in electric
shock.
 Non-standard and improper operations may result in fire or electric shock.
 Do not connect or disconnect power cables with power on. Transient contact between the
core of the power cable and the conductor will generate electric arcs or sparks, which may
cause fire or personal injury.
 If the power supply to the equipment is permanently connected, install an easily
accessible disconnector at the exterior of the device.
 Before making electrical connections, switch off the disconnector on the upstream device
to cut off the power supply if people may contact energized components.
 If a "high electricity leakage" tag is attached on the equipment, ground the protective
ground terminal on the equipment enclosure before connecting the AC power supply;
otherwise, electric shock as a result of electricity leakage may occur.
 Before installing or removing a power cable, turn off the power switch.
 Before connecting a power cable, check that the label on the power cable is correct.
 Before connecting the power supply, ensure that cable connections are correct.
 If the equipment has multiple inputs, disconnect all the inputs before operating the
equipment.

Cabling
 When routing cables, ensure that a distance of at least 30 mm exists between the cables
and heat-generating components or areas. This prevents damage to the insulation layer of
the cables.
 Do not route cables behind the air intake and exhaust vents of the equipment.
 Ensure that cables meet the VW-1 flame spread rating requirements.
 Bind cables of the same type together. When routing cables of different types, ensure that
they are at least 30 mm away from each other.
 Ensure that all cables are securely bound. Route and bind cables so that they appear neat
and tidy and their cable sheaths are intact.
 If an AC input power cable is connected to the cabinet from the top, bend the cable in a
U shape outside the cabinet and then route it into the cabinet.
 Ensure that the bending radius of each cable is at least five times the diameter of the
cable.
 When routing power cables, ensure that there is no coiling or twisting. Do not join or
weld power cables. If necessary, use a longer cable.

ESD
 When installing, operating, and maintaining the equipment, comply with the ESD
protection regulations and wear the ESD clothing, gloves, and wrist strap.
 When holding a board, hold its edge without touching any components. Do not touch the
components with your bare hands.
 Package boards with ESD packaging materials before storing or transporting them.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 6


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

1.4 Installation Environment Requirements


 To prevent fire due to high temperature, ensure that the ventilation vents or heat
dissipation system are not blocked when the equipment is running.
 Ensure that there are no acid, alkaline, or other corrosive gases in the installation place.
 Do not place the equipment near heat sources or exposed fire sources, such as electric
heaters, microwave ovens, roasters, water heaters, furnace fire, candles, or other places
where high temperature may occur. Otherwise, the enclosure will melt or the equipment
will heat up, which can cause a fire.
 Install the equipment in an area far away from liquids. Do not install it under areas prone
to condensation, such as under water pipes and air exhaust vents, or areas prone to water
leakage, such as air conditioner vents, ventilation vents, or feeder windows of the
equipment room. Ensure that no liquid enters the equipment to prevent faults or short
circuits.
 Before installing the equipment into a cabinet, ensure that the cabinet is secured and will
not tilt or fall down due to loss of balance, which can cause personal injury or equipment
damage.
 Do not expose the equipment to flammable or explosive gas or smoke. Do not perform
any operation on the equipment in such environments.

Installation at Heights
Working at heights refers to operations that are performed at least 2 meters above the ground.
Do not at heights in any of the following situations:
 Rainwater remains on steel pipes or other risky conditions exist. After the preceding
conditions no longer exist, the safety director and relevant technical personnel need to
check the involved equipment. Operators can begin working only after obtaining
consent.
 When working at heights, comply with local relevant laws and regulations.
 Only trained and qualified personnel are allowed to work at heights.
 Before working at heights, check the climbing tools and safety gears such as safety
helmets, safety belts, ladders, springboards, scaffolding, and lifting equipment. If they do
not meet the requirements, take corrective measures or disallow working at heights.
 Wear personal protective equipment such as the safety helmet and safety belt or waist
rope and fasten it to a solid structure. Do not mount it on an insecure moveable object or
metal object with sharp edges. Make sure that the hooks will not slide off.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 7


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Set a restricted area and eye-catching signs for working at heights to warn away irrelevant
personnel.
 Carry the operation machinery and tools properly to prevent them from falling off and
causing injuries.
 Personnel involving working at heights are not allowed to throw objects from the height to
the ground, or vice versa. Objects should be transported by tough slings, hanging baskets,
highline trolleys, or cranes.
 Do not perform operations on the upper and lower layers at the same time. If unavoidable,
install a dedicated protective shelter between the upper and lower layers or take other
protective measures. Do not pile up tools or materials on the upper layer.
 Ensure that guard rails and warning signs are set at the edges and openings of the area
involving working at heights to prevent falls.
 Do not pile up scaffolding, springboards, or other sundries on the ground under the area
involving working at heights. Do not allow people to stay or pass under the area involving
working at heights.
 Inspect the scaffolding, springboards, and workbenches used for working at heights in
advance to ensure that their structures are solid and not overloaded.
 Dismantle the scaffolding from top down after finishing the job. Do not dismantle the
upper and lower layers at the same time. When removing a part, ensure that other parts
will not collapse.
 Do not loiter when working at heights. Do not sleep at heights.
 Any violations must be promptly pointed out by the site manager or safety supervisor
and the involved personnel should be prompted for correction. Personnel who fail to stop
violations will be forbidden from working.
 Operators who violate the safety regulations are responsible for accidents caused. The
supervisor has to bear the responsibility accordingly.

1.5 Mechanical Safety


Hoisting Devices

Do not walk under hoisted objects.


 Only trained and qualified personnel should perform hoisting operations.
 Check that hoisting tools are available and in good condition.
 Before hoisting objects, ensure that hoisting tools are firmly secured onto a load-bearing
object or wall.
 Ensure that the angle formed by two hoisting cables is no more than 90 degrees, as
shown in the following figure.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 8


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Do not drag steel ropes and hoisting tools or bump hoisted objects against hard objects
during hoisting.

Using Ladders
 Use wooden or fiberglass ladders when you need to perform live working at heights.
 When a step ladder is used, ensure that the pull ropes are secured and the ladder is held
firm.
 Before using a ladder, check that it is intact and confirm its load bearing capacity. Do not
overload it.
 Ensure that the wider end of the ladder is at the bottom, or protective measures have
been taken at the bottom to prevent the ladder from sliding.
 Ensure that the ladder is securely positioned. The recommended angle for a ladder
against the floor is 75 degrees, as shown in the following figure. An angle rule can be
used to measure the angle.

When climbing a ladder, take the following precautions to reduce risks and ensure safety:

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 9


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Keep your body steady.


 Do not climb higher than the fourth rung of the ladder from the top.
 To climb onto a roof, ensure that the ladder top is at least one meter higher than the roof
line, as shown in the following figure.

 Ensure that your body's center of gravity does not shift outside the legs of the ladder.

Drilling Holes
When drilling holes into a wall or floor, observe the following safety precautions:

Do not drill holes into the equipment. Doing so may affect the electromagnetic shielding of
the equipment and damage components or cables inside. Metal shavings from drilling may
short-circuit boards inside the equipment.
 Wear goggles and protective gloves when drilling holes.
 When drilling holes, protect the equipment from shavings. After drilling, clean up any
shavings that have accumulated inside or outside the equipment.

Moving Heavy Objects


 Be cautious to avoid injury when moving heavy objects.

 When moving the equipment by hand, wear protective gloves to prevent injuries.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 10


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Move or lift the equipment by holding its handles or lower edges. Do not hold the
handles of modules (such as power supply units, fans, and boards) that are installed in
the equipment because they cannot support the weight of the equipment.

1.6 Battery Safety


If no battery is involved, skip this section.
Before installing, operating, or maintaining batteries, read the battery manufacturer's
instructions. The safety precautions specified in this document are highly important
precautions that require special attention. For additional safety precautions, see the
instructions provided by the battery manufacturer.

Basic Requirements
Before operating batteries, carefully read the safety precautions for battery handling and
master the correct battery connection methods.

 Do not expose batteries at high temperatures or around heat-generating devices, such as


sunlight, fire sources, transformers, and heaters. Excessive heat exposure may cause the
batteries to explode.
 Do not burn batteries. Otherwise, the batteries may explode.
 To avoid leakage, overheating, fire, or explosions, do not disassemble, alter, or damage
batteries, for example, insert sundries into batteries or immerse batteries in water or other
liquids.
 When replacing a battery, use a battery of the same model or type. Improper replacement
may cause the battery to explode.
 Do not connect a metal conductor to the battery poles or touch the battery terminals.
Otherwise, the battery may be short-circuited and heat up, which can cause injuries such as
burning.

To ensure safety during battery installation, operation, and maintenance, pay attention to the
following:
 Do not wear conductive articles such as watches, bracelets, bangles, and rings.
 Wear goggles, rubber gloves, and protective clothing to prevent skin contact with
electrolyte in the case of electrolyte overflow. If a battery leaks, protect the skin or eyes
from the leaking liquid. If the skin or eyes come in contact with the leaking liquid, wash
it immediately with clean water and go to the hospital for medical treatment.
 Use dedicated insulated tools.
 Move batteries in the required direction. Do not place a battery upside down or tilt it.
 Keep the battery loop disconnected during installation and maintenance.
 Do not drop, squeeze, or puncture a battery. Protect batteries from external high pressure
to prevent internal short circuits and overheating.
 Dispose of waste batteries in accordance with local laws and regulations. Do not dispose
of batteries as household waste. If a battery is disposed of improperly, it may explode.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 11


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Do not use a damaged battery.


 To prevent injuries or explosion, do not allow children or pets to swallow or bite a
battery.
 If batteries experience discoloration, deformation, abnormal heating, or other
abnormalities during working, charging, or storage, stop using the batteries and replace
them with new ones.
 Batteries can work properly with the allowed charge and discharge parameters when the
temperature is within the specified range. If the temperature is outside the specified
range, the battery charge and discharge performance and safety are affected.

Battery Installation
Before installing batteries, observe the following safety precautions:
 Install batteries in a dry and cool environment with good ventilation, which is away from
high temperature and flammable materials, and take precautions against fire.
 Place and secure batteries horizontally.
 Note the polarities when installing batteries. Do not short-circuit the positive and
negative poles of the same battery or battery string. Otherwise, the battery may be
short-circuited.
 When installing a battery string, retain at least one breakpoint to prevent a loop being
formed. After checking that the installation is correct, close the breakpoints to finish the
installation.
 During the installation, insulate the terminals of cables connecting batteries. Ensure that
the terminals do not come into contact with metal components such as the cabinet.
 Secure battery cables or copper bars by tightening bolts to the required torque. Loose
connections will result in excessive voltage drop or cause batteries to burn out in the case
of excessive current.
 Check battery connections periodically, ensuring that all bolts are securely tightened.

Battery Short Circuit

Battery short circuits can generate high instantaneous current and release a great amount of
energy, which may cause equipment damage or personal injury.
 If permitted, disconnect the batteries in use before performing any other operations.
 To avoid battery short-circuit, do not maintain batteries with power on.

Flammable Gas

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 12


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 Do not use unsealed lead-acid batteries.


 To prevent fire or corrosion, ensure that flammable gas (such as hydrogen) is properly
exhausted for lead-acid batteries.

Lead-acid batteries emit flammable gas when used. Ensure that batteries are kept in a
well-ventilated area and take preventive measures against fire.

Battery Leakage

Battery overheating causes deformation, damage, and electrolyte spillage.

If the battery temperature exceeds 60°C, check for and promptly handle any leakage.
Electrolyte overflow may damage the equipment. It will corrode metal parts and boards, and
ultimately damage the boards.

When the electrolyte overflows, absorb and neutralize the electrolyte immediately. When
moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte may
hurt human bodies.

If the electrolyte overflows, follow the instructions of the battery manufacturer or neutralize
the electrolyte by using sodium bicarbonate (NaHCO3) or sodium carbonate (Na2CO3).

Lithium Battery
The safety precautions for lithium batteries are similar to those for lead-acid batteries except
that you also need to note the precautions described in this section.

There is a risk of explosion if a battery is replaced with an incorrect model.


 A battery can be replaced only with a battery of the same or similar model recommended
by the manufacturer.
 When handling a lithium battery, do not place it upside down, tilt it, or bump it with
other objects.
 Keep the lithium battery loop disconnected during installation and maintenance.
 When the ambient temperature is lower than the lower limit of the operating temperature
(charge is forbidden at 0°C), do not charge the battery. Otherwise, a short circuit would
occur inside the battery.
 Do not throw a lithium battery in fire.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 13


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 1 Safety Precautions

 When maintenance is complete, return the waste lithium battery to the maintenance
office.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 14


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2 Product Overview

2.1 Introduction to the MTS


The multiple telecommunication system (MTS) is a solution that provides an outdoor
operating environment, security management, and monitoring network for wireless telecom
sites. It integrates the outdoor cabinet, temperature control unit, telecom power supply,
monitoring unit, network management system, AC and DC power distribution units, and surge
protective devices. It also provides sufficient space for housing customer equipment. The
MTS provides a series of highly efficient, intelligent, and integrated site solutions.
The MTS has the following features:
 Highly efficient site
− Battery hibernation
− Temperature control and energy saving
− High-density heat exchange
 Intelligent site
− IP and in-band networking
− Intelligent temperature control management
 Integrated site
− Modular power distribution

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 15


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2 Cabinet Description


2.2.1 MTS9304A-HD10A1 (H2 power cabinet)
Figure 2-1 Appearance

Table 2-1 Cabinet description

Item Description
External dimensions 1000 mm x 650 mm x 650 mm (including the 100 mm high base,
(H x W x D) excluding the protruding part of the door)
Cabinet weight ≤ 90 kg (excluding rectifiers and batteries)
Temperature control  Equipment compartment: heat exchanger (1500 W), AC heater
mode (500 W)
 Battery compartment: direct ventilation, AC heater (500 W)
Cable routing mode Routed in and out from the bottom
IP rating  Equipment compartment: IP55
 Battery compartment: IP45
Installation mode Installed on a floor or mounted on a pole
Power subrack 400 A
Application Class C
environment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 16


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

 Class B environments refer to indoor environments in which the ambient temperature and humidity
are not controlled and outdoor environments (with simple shielding measures such as awning
installation) where the humidity can reach 100%.
 Class C environments refer to marine environments or outdoor land environments (with simple
shading measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km
away from salt water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such
as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources,
such as chemical, rubber, and galvanization industries, or 1 km away from light pollution sources,
such as packing houses, tanneries, and boiler rooms.
 Class D environments refer to areas within 500 m away from the seashore.

Figure 2-2 Interior

(1) Smoke (2) AC power distribution (3) Door status sensor


sensor box (ACDB)
(4) Ground bar (5) Space for customer (6) Digital temperature and humidity
equipment sensor (Digital T/H sensor)
(7) AC heater (8) Battery power (9) Internal circulation fan
distribution box
(10) Power (11) Intelligent power (12) External circulation fan
subrack distribution unit
(13) Space for (14) Water sensor
batteries

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 17


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.2 MTS9304A-AX10A1 (A2 power cabinet)


Figure 2-3 Appearance

Table 2-2 Cabinet description

Item Description
External dimensions 1000 mm x 650 mm x 650 mm (including the 100 mm high base,
(H x W x D) excluding the protruding part of the door)
Cabinet weight ≤ 190 kg (excluding rectifiers and batteries)
Temperature control Air conditioner PC1000D-1 and two AC heaters
mode
Cable routing mode Routed in and out from the bottom
IP rating IP55
Installation mode Installed on a floor or mounted on a pole
Power subrack 400 A
Application Class C
environment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 18


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-4 Interior

(1) Smoke sensor (2) Battery power (3) Door status sensor
distribution box
(4) ACDB (5) Ground bar (6) Digital temperature and humidity
sensor (Digital T/H sensor)
(7) AC heater (8) Power subrack (9) DC air conditioner PC1000D-1
(10) Intelligent power (11) Space for (12) Water sensor
distribution unit customer equipment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 19


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.3 MTS9514A-GX1401 (A3 power cabinet)


Figure 2-5 Appearance

Table 2-3 Cabinet description

Item Description
External dimensions 1410 mm x 815 mm x 735 mm (including the 150 mm high base,
(H x W x D) excluding the protruding part of the door)
Cabinet weight ≤ 170 kg (excluding rectifiers and batteries)
Temperature control Air conditioner AH1500H and two AC heaters
mode
Cable routing mode Routed in and out from the bottom
IP rating IP55
Installation mode Installed on a floor
Power subrack 400 A
Application Class C
environment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 20


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-6 Interior

(1) Air conditioner AH1500H (2) ACDB (3) Digital T/H


sensor
(4) Ground bar (5) AC heater (6) Smoke sensor
(7) Door status sensor (8) Battery power distribution (9) Power subrack
box
(10) Intelligent power distribution (11) Space for customer (12) Water sensor
unit equipment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 21


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.4 MTS9300A-HX10A2 (H1 equipment cabinet)


Figure 2-7 Appearance

Table 2-4 Cabinet specifications

Item Specifications
External dimensions (H x 1000 mm x 650 mm x 650 mm (including the 100 mm high
W x D) base, excluding the protruding part of the door)
Weight ≤ 65 kg
Temperature control mode heat exchanger (1500 W) and two AC heaters
Cabling mode Routed in and out from the bottom
IP rating IP55
Installation mode Installed on a floor or mounted on a pole
Application environment Class C

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 22


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-8 Interior

(1) Smoke sensor (2) Door status sensor (3) ACDB


(4) Ground bar (5) AC heater (6) Digital T/H sensor
(7) Space for customer equipment (8) Internal circulation fan (9) TCUC
(10) External circulation fan (11) Water sensor

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 23


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.5 MTS9300A-AX10A1 (A1 equipment cabinet)


Figure 2-9 Appearance

Table 2-5 Cabinet specifications

Item Specifications
External dimensions (H x 1000 mm x 650 mm x 650 mm (including the 100 mm high
W x D) base, excluding the protruding part of the door)
Weight ≤ 160 kg
Temperature control mode Air conditioner PC1000D-1 and two AC heaters
Cabling mode Routed in and out from the bottom
IP rating IP55
Installation mode Installed on a floor or mounted on a pole
Application environment Class C

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 24


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-10 Interior

(1) Smoke sensor (2) Door status sensor (3) ACDB


(4) Ground bar (5) AC heater (6) Digital T/H
sensor
(7) Air conditioner (8) Space for customer (9) Water sensor
PC1000D-1 equipment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 25


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.6 MTS9300A-XA10A4 (A battery cabinet)


Figure 2-11 Appearance

Table 2-6 Cabinet specifications

Item Specifications
External dimensions (H x 1000 mm x 650 mm x 650 mm (including the 100 mm high
W x D) base, excluding the protruding part of the door)
Weight ≤ 65 kg (excluding batteries)
Temperature control mode Air conditioner PC300D and an AC heater
Cabling mode Routed in and out from the bottom
IP rating IP55
Installation mode Installed on a floor or mounted on a pole
Application environment Class C

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 26


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-12 Interior

(1) Smoke sensor (2) Door status sensor (3) Space for batteries
(4) Digital T/H sensor (5) AC heater (6) Ground bar
(7) Air conditioner PC300D (8) Water sensor

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 27


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

2.2.7 DEU04D-H120A3 (DEU equipment cabinet)


Figure 2-13 Appearance

Table 2-7 Cabinet description

Item Description
External dimensions 660 mm x 340 mm x 540 mm
(H x W x D)
Weight ≤ 32 kg
Cooling mode Heat exchanger: 1400 W
Cabling mode Routed in and out from the bottom
IP rating IP55
Installation mode Pole-mounted or wall-mounted
Space for customer 4U
equipment

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 28


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-14 Internal structure

(1) DC output circuit (2) Space for customer (3) RTN+ output
breakers equipment terminals
(4) DC hearter HAU02D (5) Door status sensor (6) Cable bags
(7) TCUC (8) DC SPD (9) DC input terminals
(10) Ground bar

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 29


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 2 Product Overview

Figure 2-15 Side view of a cabinet

(1) Internal circulation fan (2) Heat exchanger core (3) External circulation fan

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 30


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3 Components

3.1 Power Distribution Unit


3.1.1 Power Subrack
Figure 3-1 ETP48400-C3B1 appearance

(1) AC input module (2) Space for rectifiers (3) UIM05B1


(4) Reserved slot for communications (5) Battery wiring (6) BLVD power
expansion module ports distribution
(7) SMU02C (8) LLVD power
distribution

Table 3-1 ETP48400-C3B1 specifications

Item Specifications

AC input system 220/380 V AC three-phase four-wire, compatible with 220 V


AC single-phase
DC power distribution  LLVD: six 32 A circuit breakers (Default disconnection
voltage: 44.0 V)
 BLVD: six 16 A circuit breakers (Default disconnection
voltage: 43.2 V)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 31


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Item Specifications
Surge protection  AC surge protection: nominal surge discharge current: 30
kA (8/20 µs)
 DC surge protection: 10 kA (8/20 µs) in differential mode,
20 kA (8/20 µs) in common mode
 Signal surge protection:
Outside the cabinet: 3 kA in differential mode, 5 kA in
common mode (8/20 μs)
Inside the cabinet: 0.5 kV in differential mode, 1 kV in
common mode (8/20 μs)

3.1.2 AC Power Distribution Box (ACDB)


ACDB (H2 power cabinet)

Figure 3-2 Appearance

(1) Maintenance socket and RCD (2) AC output circuit breakers and terminals

Table 3-2 Specifications

Item Specifications
AC output Two 1-pole 10 A circuit breakers, one maintenance socket, and one
10 A protection circuit breaker

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 32


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

ACDB (A2 power cabinet)

Figure 3-3 Appearance

(1) Maintenance socket (2) AC output N terminals


(3) RCD (for maintenance socket) (4) AC output circuit breakers

Table 3-3 Specifications

Item Specifications
AC output Three 1-pole 10 A circuit breakers, one maintenance socket, and
one 10 A protection circuit breaker

ACDB (A3 power cabinet)

Figure 3-4 Appearance

(1) Maintenance socket and RCD (2) AC output circuit breakers and terminals

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 33


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-4 Specifications

Item Specifications
AC output Three 1-pole 10 A circuit breakers, one 1-pole 20 A circuit breaker,
one maintenance socket, and one 10 A protection circuit breaker

ACDB (H1 equipment cabinet)

Figure 3-5 Appearance

(1) AC input circuit breaker and terminal (2) AC SPD


(3) Maintenance socket and RCD (4) AC output circuit breakers and terminals

Table 3-5 Specifications


Item Specifications

AC input One 3-pole 63 A circuit breaker


AC output Two 1-pole 10 A circuit breaker, one maintenance socket, and one
10 A protection circuit breaker
Surge protection Nominal surge discharge current: 30 kA

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 34


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

ACDB (A1 equipment cabinet)

Figure 3-6 Appearance

(1) Maintenance socket and RCD (2) AC output circuit breakers and (3) AC
terminals SPD
(4) AC input circuit breakers and (5) PE bar
terminal

Table 3-6 Specifications

Item Specifications
AC input One 3-pole 63 A circuit breaker
AC output Three 1-pole 10 A circuit breaker, one maintenance socket, and one
10 A protection circuit breaker
Surge protection Nominal surge discharge current: 30 kA

3.1.3 Intelligent Power Distribution Unit


Figure 3-7 DCDB48-200-16B appearance

(1) Ground screw (2) LLVD power distribution (3) BLVD power distribution
(4) DMU02C1 (5) DC input ports

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 35


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Figure 3-8 DMU02C1 panel

(1) Run indicator (2) Alarm indicator (3) RS485 communications ports

Table 3-7 Indicator description

Name Color Status Description


Run indicator Green Off The DMU is faulty or has no DC input.
Blinking The communications is normal.
slowly (0.5 Hz)
Blinking fast (4 The communications fails.
Hz)
Alarm Red Off No alarm is generated.
indicator
Steady on An alarm is generated.

Table 3-8 Communication port description

Communications Port Communications Communications Protocol


Parameter

COM1/COM2 Baud rate: 9600 bit/s Modbus protocol

NOTE
All these ports are protected by a security mechanism.

Figure 3-9 Communication port pins

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 36


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-9 Pin definitions for the RS485 port

Pin Signal Description


1 TX+ Transmits data over RS485
2 TX-
4 RX+ Receives data over RS485
5 RX-
3, 6, 7, 8 NA –

Figure 3-10 DIP switch

 When multiple DCDB48-200-16Bs are cascaded, you need to set the address DIP switch for the
DMU02C1.
 If one DCDB48-200-16B is installed, you do not need to set the address DIP switch for the
DMU02C1.

Table 3-10 DCDB specifications

Item Specifications

Input voltage 40–60 V DC


Total input current Maximum: 200 A
DC power distribution  BLVD power distribution: two 1-pole 16 A, two
1-pole 20 A, and two 1-pole 32 A circuit breakers
(Default disconnection voltage: 43.2 V)
 LLVD power distribution: four 1-pole 32 A and six
1-pole 63 A circuit breakers (Default disconnection
voltage: 45.0 V)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 37


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Item Specifications
Dimensions (H x W x D) 43.6 mm x 482.6 mm x 255 mm
Weight ≤ 10 kg
Installation mode Installed in a 19-inch rack
Cabling mode Routed in and out from the front
Maintenance mode Maintained from the front

3.1.4 Battery Power Distribution Box


Figure 3-11 DCDB48-400-4C appearance

(1) Ground screw (2) Battery circuit breaker status (3) Battery circuit
detection ports breaker
(4) Space reserved for battery (5) DC input ports
power distribution

Table 3-11 DCDB48-400-4C specifications

Item Specifications
Input voltage 40–60 V DC
Total input current Maximum: 400 A
DC power distribution Four 1-pole 125 A circuit breakers
Dimensions (H x W x D) 43.6 mm x 482.6 mm x 180 mm
Weight ≤ 5 kg
Installation mode Installed in a 19-inch rack
Cabling mode Routed in and out from the front
Maintenance mode Maintained from the front

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 38


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.2 PSU (DPU40D-N06A3)


Functions
The PSU integrates power rectification, distribution, and monitoring. It converts AC or
HVDC power into stable 48 V DC power, generates fault alarms, and reports monitoring data
to the upstream network management system (NMS) in real time. The PSU supports
communication with monitoring device through the MBUS.

Appearance

Figure 3-12 PSU

(1) Running indicator (2) Alarm indicator

Indicators

Table 3-12 PSU indicator description

Indicator Color Status Description


Running Green Off The PSU has no power input (no AC input
indicator and no battery input)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 39


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Indicator Color Status Description


Steady on Start / Self-check / Load (instantaneous status
during startup or upgrade)
Blinking at long The PSU communicating with the host
intervals (0.5 Hz) properly
Blinking at short The PSU is not communicating with the host
intervals (4 Hz) properly
Alarm Red Off The PSU is proper
indicator
Steady on Rectifier Fault/Address Conflict/SMU Fault
Blinking at long Rectifier Protection/Rectifier Shutdown/
intervals (0.5 Hz) Communication Failure/Rectifier Power
Failure/Parallel Fail/AC Overvoltage/AC
Undervoltage

Ports

Figure 3-13 PSU ports

(1) Power input port (2) Load output port 1 (3) Load output port 2
(4) Load output port 3 (5) Battery output port (6) COM_DIN port
(7) COM_ALM port (8) Ground screw

Power Ports

Table 3-13 Power port description

Port Fuse Specifications Function

PWR 1 × 16 A quick-connector(excluding AC or DC input; connects to


the fuse) the power supply.

LOAD1, LOAD2, 3 × 40 A quick-connector(with DC output; connect to loads.


LOAD3 replaceable fuses)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 40


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Port Fuse Specifications Function


BAT 1 × 40 A quick-connector(excluding Battery port; connects to the
the fuse) lithium battery.

Communications Ports

Table 3-14 Communications port description


Communications Communications Communications Function
Port Parameter Protocol

COM_DIN - CAN2.0 Communicates with


a lithium battery or a
cascaded PSU.
COM_ALM Baud rate: 9600 YDN protocol or Communicates with
bit/s, 19200 bit/s, master/slave upstream monitoring
115200 bit/s, protocol/ModBUS equipment.
auto-negotiation protocol
- CAN2.0 Communicates with
a cascaded PSU.

Figure 3-14 COM_DIN port pins

Table 3-15 COM_DIN port pin definitions

Pin Signal Name Description

1-2 NC NC
3 DI1+ Dry contact input 1
4 DI1-
5 NC NC
6 DI2+ Dry contact input 2
7 DI2-
8 CANH CAN data transmission and reception H

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 41


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Pin Signal Name Description


9 CANL CAN data transmission and reception L

Figure 3-15 COM_ALM port pins

Table 3-16 COM_ALM port pin definitions

Pin Signal Name Description


1 ALM1+ Associated with the AC failure alarm; OC door
output; AC Undervoltage Protection; AC
2 ALM1- Overvoltage Protection
3 ALM2+ A PSU is faulty
4 ALM2-
5 ALM3+ A Lithium battery is faulty
6 ALM3-
7 RS485_TX+ Northbound transmits data over RS485 positive
8 RS485_TX- Northbound transmits data over RS485 negative
9 RS485_RX+ Northbound receives data over RS485 positive
10 RS485_RX- Northbound receives data over RS485 negative
11 ALM4+ A PSU or a lithium battery generates a
recoverable alarm
12 ALM4-
13 Reserved Reserved
14 CANH CAN data transmission and reception H
15 CANL CAN data transmission and reception L

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 42


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.3 Lithium Battery (DBU20B-N12A3)


Functions
The lithium battery supplies backup power to communications equipment when the PSU has
no power input, thereby ensuring reliable power supply for service operation.

Appearance

Figure 3-16 Lithium battery

(1) Run indicator (2) Alarm indicator

Indicators

Table 3-17 Lithium battery indicator description

Name Color Status Meaning


Run Green Off The lithium battery has no power input or is faulty
indicator
Steady on Board startup / self-check / loading / activation /
board power-on when no software is loaded

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 43


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Name Color Status Meaning


Blinking The lithium battery is communicating properly with
slowly (0.5 monitoring equipment
Hz)
Blinking fast The lithium battery fails to communicate with
(4 Hz) monitoring equipment
Alarm Red Off The lithium battery is proper
indicator
Steady on Board Hardware Fault/Heater Fault/Battery Cell N
Fault/Address Conflict
Blinking Discharge Overcurrent Protection/Charge
slowly (0.5 Overcurrent Protection/High Temperature
Hz) protection/Low Temperature Protection/Abnormal
Close/Charge Overcurrent Protection/Discharge
Overcurrent Protection

Ports

Figure 3-17 Lithium battery ports

(1) Ground screw (2) COM_IN/OUT port (3) Battery output port 1
(4) Battery output port 2

Power Ports

Table 3-18 Power port description

Port Fuse Specifications Function


BAT1, BAT2 2×80A quick-connector Battery output port.
(excluding the fuse)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 44


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Communications Ports

Table 3-19 Communications port description

Communications Communications Protocol Function


Port

COM_IN, COM_OUT CAN2.0 Communicates with a PSU or


with a cascaded lithium battery.

Figure 3-18 COM_IN/COM_OUT port pins

Table 3-20 COM_IN/OUT port pin definitions

Pin Signal Description


1, 2 NC NC
3 CAN_H CAN data transmission and
reception H
4-6 NC NC
7 CAN_L CAN data transmission and
reception L
8 GND Protective ground

3.4 Rectifier
A rectifier converts AC input power into stable DC power.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 45


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Figure 3-19 Rectifier

(1) Power indicator (2) Alarm indicator (3) Fault indicator


(4) Locking latch (5) Handle

Table 3-21 Rectifier indicator description

Indicator Color Status Description


Power indicator Green Steady The rectifier has an AC input.
on
Off The rectifier has no AC input.
The rectifier is faulty.
Blinking The rectifier is being queried.
at 0.5 Hz
Blinking The rectifier is loading an application
at 4 Hz program.
Alarm indicator Yellow Off No alarm is generated.
Steady  A warning is generated due to ambient
on overtemperature.
 The rectifier has generated a protection
shutdown alarm due to ambient
overtemperature or undertemperature.
AC input overvoltage or undervoltage
protection has been triggered.
The rectifier is in hibernation state.
Blinking The communication between the rectifier and
at 0.5 Hz the external device is interrupted.
Fault indicator Red Off The rectifier is normal.
Steady The rectifier locks out due to output

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 46


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Indicator Color Status Description


on overvoltage.
The rectifier has no output due to an internal
fault.

3.5 SMU02C
Figure 3-20 SMU02C appearance

(1) SD card slot (2) Run indicator (3) Minor alarm indicator
(4) Major alarm (5) Buttons (6) USB ports (protected by a security
indicator mechanism)
(7) RS485/RS232 port (8) Fast Ethernet (FE) (9) CAN communications port
port
(10) LCD

Indicators

Table 3-22 Indicator description

Name Color Status Description


Run indicator Green Off The SMU is faulty or has no DC input.
Blinking The SMU is running properly and
slowly (0.5 Hz) communicating with the host properly.
Blinking fast (4 The SMU is running properly but fails to
Hz) communicate with the host properly.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 47


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Name Color Status Description


Minor alarm Yellow Off No minor or warning alarm is generated.
indicator
Steady on A minor or warning alarm is generated.
Major alarm Red Off No critical or major alarm is generated.
indicator
Steady on A critical or major alarm is generated.

Buttons

Table 3-23 Button description

Button Name Description


Up
Press and to scroll through the menus or to change
the value of a parameter.
Down

Cancel Returns to the previous menu without saving the settings.

Enter  Enters the main menu from the standby screen.


 Enters a submenu from the main menu.
 Saves menu settings on a submenu.

NOTE
 The LCD screen becomes dark if no button is pressed within 30 seconds.

 You need to log in again if no button is pressed within 1 minute.

 To increase or decrease a parameter value quickly, hold down or .

 To restart the SMU, hold down and for 10 seconds.

 To increase (or decrease) the LCD backlight, hold down and (or ) for 2
seconds.

SD Card Slot
SD card is used for storing the camera capture images, maximum support 32 G capacity.

USB Ports
You can quickly deploy a site, import and export configuration files, export running logs, and
upgrade software by inserting the USB flash drive that is specially used for site deployment
into the USB port.
After installing the specific WiFi module using the USB port, you can access the WebUI
locally, which facilitates operations.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 48


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Using WiFi modules provided by another vendor may cause data loss or function exception.
Consequences arising from this will not be borne by Huawei.

Communications Ports

Table 3-24 Communications port description


Communications Communications Parameter Communications Protocol
Port

FE 10/100M autonegotiation HTTPS, NetEco protocol,


SNMP, and TCP-Modbus
protocol
RS485/RS232 Baud rate: 1200 bit/s, 2400 bit/s, Master/slave protocol, YDN
4800 bit/s, 9600 bit/s, 14400 protocol, and Modbus protocol
bit/s, 19200 bit/s, 115200 bit/s
CAN Baud rate: 125 kbit/s CAN protocol

NOTE
All these ports are protected by a security mechanism.

Figure 3-21 Communication port pins

Table 3-25 Pin definitions for the FE port

Pin Signal Description


1 TX+ Transmits data over FE
2 TX-
3 RX+ Receives data over FE
6 RX-
4/5/7/8 NA -

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 49


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-26 Pin definitions for the RS485/RS232 port

Pin Signal Description


1 TX+ Transmits data over RS485
2 TX-
4 RX+ Receives data over RS485
5 RX-
3 RX232 Receives data over RS232
7 TX232 Transmits data over RS232
6 PGND Connects to the ground
8 NA –

Table 3-27 Description for the CAN port pins

Pin Signal Description


1 RX+ Receives data over RS485
2 RX-
3 NA -
4 TX+ Sends data over RS485
5 TX-
6 NA -
7 CANH CAN high level signal
8 CANL CAN low level signal

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 50


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.6 User Interface Module UIM05B1


Figure 3-22 Panel

(1) Dry contact and sensor (2) COM communications (3) Battery temperature sensor
ports port port
(4) Door status sensor port (5) Battery switch port (6) Cable hole for fan cables
(7) Handle

The battery switch is used only when the mains supply is unavailable.

Figure 3-23 Dry contacts

Figure 3-24 COM port pin definitions

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 51


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-28 COM port pin definitions

Pin Signal Description


1 RS485_RX+ RS485 data, positive
2 RS485_RX- RS485 data, negative
3 12 V Power supply
4 RS485_TX+ RS485 data, positive
5 RS485_TX- RS485 data, negative
6 GND Ground
7 Reserved –
8 GND Ground

3.7 PC300D
Figure 3-25 Appearance

(1) Wiring port (2) Fan

Table 3-29 Specifications

Item Specifications
Rated power (L35/L35) 120 W
Rated cooling capacity (L35/L35) 300 W

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 52


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Item Specifications
Heating capacity 300 W
Input voltage –48 V DC (–44 V DC to –57 V DC)
Operating temperature –40°C to +55°C
Storage temperature -40°C to +70°C
Alarm reporting Reports alarms over dry contacts. Normal: closed;
faulty: open
Altitude ≤ 4000 m
When the altitude ranges from 2000 m to 4000 m, the
operating temperature decreases by 1°C for each
additional 200 m.
Relative humidity 5%–95% RH
Noise GR487, acoustic pressure level: ≤ 65dB(A) at 1.5 m

3.8 DC Air Conditioner PC1000D-1


Figure 3-26 PC1000-1

(1) Communication port (2) Air return vent (3) DC Power Connector
(4) Air supply vent

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 53


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-30 PC1000D-1 specifications

Specification Value
Rated voltage –48 V DC
Circuit breaker capacity ≥ 11 A
Rated cooling capacity 1250 W
Rated cooling power 345 W
Ambient temperature range –15°C to +55°C
Fire-retardant performance Complies with UL94.
Certification Complies with CE and RoHS certification.
Surge protection Complies with IEC 61000-4-5.
Fan service life (L10/25°C for 70,000 hours
internal circulation fan, and
L10/40°C for external circulation
fan)
Dimensions (H x W x D) 783 mm x 479 mm x 200 mm
Weight 26 kg

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 54


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.9 AH1500H
Figure 3-27 Appearance

(1) Air return vent (2) Air supply vent (4) Display panel
(4) Wiring port

Table 3-31 Specifications

Item Specifications
Cooling capacity (L35/L35) 1500 W
Maximum power consumption 640 W (AC)/200 W (DC)
Typical power consumption 490 W (AC)/160 W (DC)
Heat exchanging capacity 70 W/K
Input voltage  220 V AC 50 Hz or 110 V AC 60 Hz
dual-live-wire
 –48 V DC
Operating temperature –40°C to +55°C
Storage temperature -40°C to +70°C
Alarm reporting Modbus, dry contact alarm (normal: closed; faulty:
open)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 55


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Item Specifications
Altitude < 4000 m
Relative humidity 5%–95% RH
Noise GR487, acoustic pressure level: ≤ 65dB(A) at 1.5 m

3.10 AC Heater HAU03A


A heater assembly unit (HAU) is adopted to ensure a proper operating temperature for the
equipment inside the cabinet.

Figure 3-28 Heater

(1) Indicator (2) Alarm dry contact (3) Control dry contact
(4) AC input port

Table 3-32 Indicator description

Silk Color Status Description


Screen

RUN Green Steady on The heater is powered on and


takes a self-test.
Off The heater is not powered on.
ALM Red Off No alarm is generated.
Steady on An alarm is generated and the
heater needs to be replaced.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 56


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Table 3-33 Heater specifications

Item Specifications
Input voltage 220 V AC single-phase or 110 V AC dual-live wire
Voltage frequency Rated frequency: 50 Hz/60 Hz
Operating –40°C to +65°C
temperature
Heater start and stop The heater starts when the temperature is 0°C and stops when the
temperature temperature is 15°C.
Operating humidity 5%–95% RH
Heating power > 500 W

3.11 DC Heater HAU02D


Figure 3-29 Appearance

(1) Power port (2) Grounding (3) Indicator

Table 3-34 Specifications

Item Specifications
Dimensions (H x W x D) 43.6 mm x 100 mm x 100 mm
Weight ≤ 1 kg
Operating voltage range 36–75 V DC
Rated operating voltage 48 V DC
Rated power 300 W

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 57


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Item Specifications
Operating temperature range –40°C to +65°C
Startup temperature 5±3°C
Shutdown temperature 15±3°C
Operating humidity range 5–95% RH
Altitude 0–4000 m.
When the altitude ranges from 2000 m to 4000 m, the
operating temperature decreases by 1°C for each
additional 200 m.

3.12 TCUC
The TCUC controls the running of the fans and refrigeration chip and monitors the TEC. It
reports alarms when faults occur.

Figure 3-30 TCUC

(1) Power input port (2) External circulation fan (3) Boolean value port
port (reserved)
(4) Door status sensor port (5) Indicator (6) E-label port (reserved)
(7) COM port (8) Communications port 1 (9) Communications port 2
(10) Temperature sensor (11) Temperature sensor port (12) Smoke sensor port
port 1 2

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 58


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

(13) Water sensor port (14) Internal circulation fan (15) TEC port
ports

Table 3-35 Indicator description

Silk Screen Color Status Description

RUN Green Steady on The board has a normal power supply, but no
program is running.
Blinking The system runs properly.
at 0.5 Hz
Blinking The serial port communication is interrupted, or
at 4 Hz the board is not registered.
Off The system is not powered on.
ALM Red Steady on The board has a normal power supply, but no
program is running.
Blinking An alarm is generated.
at 0.5 Hz
Off No alarm is generated.

3.13 Sensors
3.13.1 Digital Temperature and Humidity Sensor
A digital temperature and humidity sensor detects the indoor ambient temperature and
humidity in real time.

Figure 3-31 Appearance 1

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 59


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Figure 3-32 Appearance 2

DIP Switch
The following figures show the DIP switch on a digital temperature and humidity sensor. The
following table describes the DIP switch settings.

Figure 3-33 DIP switch 1

Figure 3-34 DIP switch 2

Table 3-36 DIP switch settings

Toggle Toggle Toggle Toggle Toggle Toggle Address of


Switch Switch Switch 3 Switch 4 Switch Switch Digital
1 2 5 6 Temperature and
Humidity Sensor

ON ON OFF OFF ON ON 51
OFF OFF ON OFF ON ON 52

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 60


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.13.2 Smoke Sensor


There are two types of smoke sensors with compatible mounting ports. Figure 3-35 and
Figure 3-36 show these two types of smoke sensors.

Figure 3-35 Smoke sensor 1

(1) Wiring port (2) Base (3) Indicator

Figure 3-36 Smoke sensor 2

(1) Wiring port (2) Base (3) Indicator

3.13.3 Water Sensor


A water sensor detects water based on the resistance change between both electrodes.
When the electrodes detect water, they are short-circuited and the SMU reports an alarm.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 61


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

Figure 3-37 Water sensor

Technical Specifications

Table 3-37 Water sensor specifications


Categor Item Specifications
y
Environ Operating temperature –40°C to +80°C
ment
Storage temperature –40°C to +80°C
Structure Dimensions (H x W x D)  Indoor version: 26 mm x 50 mm x 95 mm
 Outdoor version: 78.5 mm x 38.4 mm x
38.2 mm

3.13.4 Door Status Sensor


Figure 3-38 Door status sensor

(1) Switch (2) Magnet

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 62


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 3 Components

3.13.5 Battery Temperature Sensor


Figure 3-39 Battery temperature sensor

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 63


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

4 Maintenance

This section does not describe the maintenance of the PSU (DPU40D-N06A3) and lithium
battery (DBU20B-N12A3). For details about the maintenance of the DPU40D-N06A3 and
DBU20B-N12A3, see DPU40D-N06A3, DBU20B-N12A3, and DBU50B-N12A1 Distributed
Power System User Manual at http://support.huawei.com.

4.1 Routine Maintenance


Maintenance personnel perform routine maintenance periodically based on site requirements.
The recommended interval is six months. If any fault is detected, rectify it in a timely manner.
For details about the maintenance and troubleshooting of lithium batteries, see the
corresponding lithium battery manuals. For details about how to maintain and troubleshoot
AC / DC blade power supplies, see the blade manual.

Do not maintain devices on raining days; otherwise, water may enter and damage devices.

4.1.1 Cabinet
Table 4-1 Cabinet maintenance

No. Maintenance Item If... Then...


1 Check whether the The cabinet is scratched. Repaint the cabinet.
cabinet paint is flaking
off or there are scratches
on the cabinet surface.
2 Check whether the The environment quality Evaluate the risk and
cabinet is rusty or of the equipment room is improve the environment
corroded. poor. of the equipment room.
3 Check whether the The door lock is rusty or Replace the door lock.
cabinet door lock is has been tampered with.
damaged.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 64


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

No. Maintenance Item If... Then...


4 Check whether the front The front or rear of Remove the blockage or
and rear of rectifiers are rectifiers is blocked or clean up the dust.
blocked or dusty. dusty.
5 Whether there are traces Animals entered the 1. Clear the traces and
of animals such as cabinet. take precautions
insects, mice, and snakes during clearance to
inside the cabinet prevent secretions of
animals from entering
monitoring boards or
energized
components.
2. Seal the cable holes to
prevent animals from
entering the cabinet
again.

4.1.2 AC and DC Power Distribution


Table 4-2 AC and DC power distribution maintenance
No. Maintenance Item If... Then...

1 Check whether an  Red: The SPD is Replace the SPD if it is


indicator on the surge damaged due to a damaged.
protective device (SPD) is voltage surge or
red. lightning strike.
 Green: The SPD is
normal.
2 Check the SPD circuit  OFF: A voltage surge 1. Replace the circuit
breaker status. or lightning strike has breaker if it is
occurred. damaged, replace it
 ON: The SPD is 2. Turn on the circuit
normal. breaker if the SPD is
intact.
3 Check for AC input  AC input power 1. Replace AC input
undervoltage. cables have a large power cables with
voltage drop. shorter or thicker

cables.
AC input power
cables are in poor 2. Connect AC input
contact. power cables securely.

3. Provide the voltage
The mains voltage is
data to the power
too low.
supplier.
4 Check for AC input The mains voltage is too Provide the voltage data
overvoltage. high. to the power supplier.
5 Check whether the AC  AC input power 1. Check and rectify the
input voltage is cables are in poor cables.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 65


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

No. Maintenance Item If... Then...


open-phase. contact, 2. Provide the
short-circuited, or open-phase data to the
damaged. power supplier.
 The mains supply has
failed.
6 Check whether a DC  Load overcurrent Rectify any overcurrent
output circuit breaker is occurs. or short circuit. Turn on
OFF and a fuse is blown.  Load short-circuit the circuit breaker or
occurs. replace the fuse.

7 Check for DC busbar A rectifier is abnormal. Replace the abnormal


overvoltage. rectifier.
8 Check for DC busbar  The AC power 1. Resume the AC power
undervoltage. supply has failed. supply.
 The system is 2. Check the load status
overloaded. and rectify faults if
any.
 A rectifier is
3. Replace the abnormal
abnormal.
rectifier.
9 Check whether the  The DC busbar is 1. Check and secure
temperature of a DC loose or in poor cabinet busbar
busbar working at room contact. connections.
temperature exceeds  The system is 2. Check the load status
95°C. overloaded. and rectify faults if
any.

4.1.3 Rectifier
Table 4-3 Rectifier maintenance

No. Maintenance Item If... Then...


1 Check the green indicator Off: 1. Check the rectifier AC
status (normal: steady 
input.
There is no AC input.
on). 2. Replace the rectifier.
 The rectifier is faulty.
2 Check the yellow Steady on: 1. Check the ambient
indicator status (normal: 
temperature status,
Because the ambient
off). and clean the cabinet
temperature is high,
air channel.
the rectifier power is
limited. 2. Rectify faults in the
indoor temperature
 Because the ambient control system.
temperature exceeds
3. Check the AC input
the upper or lower
voltage.
threshold, the
rectifier shuts down 4. The rectifier is in
for protection. hibernation. No action

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 66


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

No. Maintenance Item If... Then...


 AC input is required.
over/undervoltage
protection is
triggered.
 The rectifier is in
hibernation.
Blinking: 1. Check that the rectifier

communications cable
The rectifier
is securely connected.
communication has
failed 2. Replace the rectifier.
 The rectifier is faulty.
3 Check the red indicator Steady on: 1. Check that the cabinet
status (normal: off). 
is not connected to an
The rectifier is
external DC power
latched off due to
source that has a
output overvoltage.
voltage of greater than
 The rectifier is faulty. 58.5 V DC.
2. Check that the rectifier
output voltage is
within 58.5 V DC.
3. Replace the rectifier.

4.1.4 SMU
Table 4-4 SMU maintenance

No. Maintenance Item If... Then...


1 Check the green indicator Off: 1. Check that the DC
status. 
input power cable is
There is no DC input.
securely connected.
 The SMU is faulty. 2. Check that the
communications cable
is securely connected.
3. Replace the SMU.
2 Check the red indicator Steady on: 1. Check related
status. 
components based on
A critical or major
alarms.
alarm is generated.
2. Replace the SMU.
 The SMU is faulty.
3 Check the LCD display  The LCD flat cable is 1. Check that the LCD
status. loose. flat cable is securely

connected.
The SMU is faulty.
2. Replace the SMU.
4 Check that the SMU can  The communications 1. Check that the
communicate with the cable is loose. communications cable
network management is securely connected.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 67


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

No. Maintenance Item If... Then...


system (NMS).  Networking 2. Check that networking
parameters are not parameter settings are
correctly set. correct.

4.1.5 Parameters on the SMU


Table 4-5 SMU parameter maintenance

No. Item Possible Cause Suggestion

1 Check whether the  Parameters are set Set battery parameters


displayed battery capacity incorrectly. again.
and number of battery  The number of
strings are the same as the batteries is changed,
actual data. or batteries are
replaced.
2 Check Charge Current N/A Change the value as
Limit Coefficient. The required. Otherwise,
value is typically retain 0.15C10.
0.15C10 and adjustable.
3 Check whether the  The battery 1. Replace the battery
displayed battery temperature sensor is temperature sensor.
temperature is the same faulty. 2. Replace the SMU.
as the actual temperature.  The SMU is faulty.
4 Check whether the  Battery current 1. Check that the current
displayed total load detection fault. monitoring cable is
current is the same as the 
securely connected.
The SMU is faulty.
actual current measured 2. Replace the SMU.
by a clamp meter.
5 Check whether the  The current 1. Check that the current
displayed battery charge monitoring cable is monitoring cable is
current is the same as the loose. securely connected.
actual current measured  The SMU is faulty. 2. Replace the SMU.
by a clamp meter.
6 Check whether the  The cabinet busbar 1. Check and secure the
difference between the and cables are loose cabinet busbar and
displayed DC output or in poor contact. cable connections.
voltage and the measured  The SMU is faulty. 2. Replace the SMU.
DC busbar voltage is less
than 0.5 V DC.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 68


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

4.1.6 Cables
Table 4-6 Cable maintenance

No. Maintenance Item If... Then...


1 Check whether signal Cables are not properly Bind signal cables and
cables and power cables installed. power cables separately.
are separately bound.
2 Check whether all cables Cables are not properly Bind cables properly.
are bound properly. installed.
3 Check whether the Cables are not properly Connect the cabinet
cabinet ground bar is installed. ground bar to the site or
securely connected to the equipment room ground
site or equipment room point.
ground point.
4 Check whether ground Cables corrode after Replace rusty cables.
cables are rusty. being used for a long
time.
5 Check whether the DC The DC RTN+ busbar is Connect the ground cable
RTN+ busbar is not properly grounded. to the DC RTN+ busbar
grounded. properly.
6 Check whether cables  Cables are too thin.  Replace the cables
have overheated and are  Cables are not with cables of the
deteriorating. properly routed. required thickness.
 Route the cables
properly.
7 Check whether cables are Cables are not properly Replace the cables and
misshapen by metal parts. installed. adjust the cable routing.
8 Check whether cables Cables are not properly Adjust the cable routing
pass behind the air installed. to prevent cable
exhaust vents of overheating.
rectifiers.
9 Check whether cable Cable insulation is Insulate the cables with
insulation is damaged. damaged. insulation tape.

4.2 Identifying Component Faults


4.2.1 Identifying Rectifier Faults
The following lists the rectifier faults
 The AC input and slot connector are normal, but the Fault indicator (red) is steady on or
all indicators are off.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 69


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

 The slot connector and SMU are normal, but the Alarm indicator (yellow) still blinks
after the rectifier is reinstalled.
 The AC input and SMU are normal, but the SMU cannot control the rectifier.

4.2.2 Identifying SSU Faults


If any of the following occurs, the SSU is faulty:
 The PV input and slot connector are normal, but the SSU indicator (red) is steady on or
all indicators are off.
 The slot connector and SMU are normal, but the yellow indicator still blinks after the
SSU is reseated.
 The PV input and SMU are normal, but the SMU cannot control the SSU.

4.2.3 Identifying Circuit Breaker Faults


If the load fuse is blown, it indicates that the circuit breaker trips. If the circuit breaker is
switched on and the downstream device is still not powered (the busbar has power), the circuit
breaker is faulty and needs to be replaced.

4.2.4 Locating AC Input Module Faults


The following lists the AC input module faults:
 The AC surge protector is faulty.
 Under normal AC power supply, if the rectifier has no output after the circuit breaker is
switched on (the upstream has power), the circuit breaker is faulty.

4.2.5 Identifying SMU Faults


The following lists the SMU faults:
 The DC output is normal but the green indicator on the SMU is off.
 The SMU breaks down or cannot be started. Its LCD has abnormal display or buttons
cannot be operated.
 With alarm reporting enabled, the SMU does not report alarms when the power system is
faulty.
 The SMU reports an alarm whereas the power system does not experience the fault.
 The SMU fails to communicate with the connected lower-level devices even though the
communications cables are correctly connected.
 Communication between the SMU and all rectifiers fails even though the rectifiers and
the communications cables are normal.
 The SMU cannot monitor AC or DC power distribution when communications cables are
intact and AC and DC power distribution is normal.
 Parameters cannot be set or running information cannot be viewed on the SMU.

4.3 Replacing Components

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 70


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

 Ensure that loads are supplied with power when replacing major components. For example,
keep the switches for primary loads in the ON position, and do not turn off the battery
switch and AC input switch at the same time.
 Seek the customer's prior consent if load disconnection is required.
 Rectifiers and the SMU are hot-swappable.

4.3.1 Replacing a Rectifier


Prerequisites
 You have obtained a pair of protective gloves and the cabinet door key.
 The new rectifier is intact.

Protect yourself from being burnt when moving the rectifier because the rectifier has a high
temperature.

Procedure
Step 1 Put on protective gloves.
Step 2 Push the locking latch at the right side of the panel towards the left.
Step 3 Gently draw the handle outwards, and then remove the rectifier from the subrack, as shown in
Figure 4-1.

Figure 4-1 Removing a rectifier

Step 4 Push the locking latch on the new rectifier towards the left, and pull out the handle.
Step 5 Place the new rectifier at the entry to the correct slot.
Step 6 Gently slide the converter into the slot along guide rails until it is engaged. Close the handle,
and push the locking latch towards the right to lock the handle, as shown in Figure 4-2.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 71


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-2 Installing a rectifier

Step 7 Take off protective gloves.


----End

Follow-up Procedure
Pack the removed component, and return it to Huawei local warehouse.

4.3.2 Replacing a Circuit Breaker


Prerequisites
 Tools are available.
 The new circuit breaker is intact.

 Power off the system before replacing a circuit breaker. Do not operate with power on.
 Power-off will disconnect the power supply to loads. Obtain prior consent from customers
before replacing a circuit breaker.

Procedure
Step 1 Switch off the circuit breaker to be replaced.
Step 2 Record the connection positions of cables, remove the cables, and insulate them.
Step 3 Remove the faulty circuit breaker.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 72


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-3 Removing a circuit breaker

Step 4 Install the new circuit breaker.


Step 5 Connect cables to the circuit breaker based on the recorded cable information.
Step 6 Switch on the circuit breaker.
----End

Follow-up Procedure
Pack the removed component and send it to the local Huawei warehouse.

4.3.3 Replacing an AC Input Module


Prerequisites
The required tools are available and the new AC input module is intact.

 Power off the AC input module before replacing it.


 Power-off will cause load devices to be shut down. Before replacing the AC input module,
obtain the customer's approval.

Procedure
Step 1 Switch off the circuit breaker on the AC input module.
Step 2 Record the installation positions of cables, remove the cables and insulate them.
Step 3 Remove the AC input module.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 73


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-4 Removing the AC input module

Step 4 Install the new AC input module.


Step 5 Install the AC input power cables based on the recorded information.
----End

Follow-up Procedure
Pack the removed parts and send it to the local Huawei warehouse.

4.3.4 Replacing an SMU02C


Prerequisites
 You have obtained the cabinet door key.
 The new SMU02C is intact.

Procedure
Step 1 Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.

Record the software version of the old SMU. If the old SMU is damaged and cannot be viewed, send the
barcodes of the old SMU and the cabinet to Huawei service personnel for query.

Step 2 Remove the communications cable from the SMU02C panel and record the cable information.
Step 3 Push the locking latch leftwards.
Step 4 Pull the handle outwards and remove the SMU02C.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 74


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-5 Removing the SMU02C

Step 5 Take off the SD card from the side of the SMU02C.

If no SD is installed, go to Step 7.

Step 6 Insert the SD card into the new SMU02C.


Step 7 Place the new SMU02C in the slot, push the locking latch leftwards, and pull out the handle.
Step 8 Gently push the SMU02C along guide rails until it is engaged. Close the handle, and push the
locking latch rightwards.

Figure 4-6 Installing the SMU02C

Step 9 Reset SMU02C parameters.

After replacing the old SMU with a new spare part, power on the new SMU and check its software
version. If the software version of the new SMU is earlier than that of the old SMU, upgrade the new
SMU software.

Step 10 Reconnect the communications cable to the SMU02C panel based on the recorded cable
information.
----End

Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.

4.3.5 Replacing a UIM05B1


Prerequisites
 The ESD wrist strap, ESD gloves, ESD box or bag, and toolbox are available.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 75


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

 The new UIM05B1 is intact.

Procedure
Step 1 Connect the ESD wrist strap ground cable, and wear the ESD wrist strap and ESD gloves.
Step 2 Record the connection positions of cables on the UIM05B1 panel and remove the cables.
Step 3 Loosen the screws on the UIM05B1 panel, pull the handle until it is engaged, and take out the
UIM05B1.

Figure 4-7 Removing the UIM05B1

Step 4 Install the new UIM05B1.


Step 5 Install the cables based on the recorded information.
----End

Follow-up Procedure
Pack the removed component and send it to the local Huawei warehouse.

4.3.6 Replacing a DMU02C1


Prerequisites
 The protective gloves and cabinet door key are available.
 The new DMU02C1 is intact.

Procedure
Step 1 Put on the protective gloves.
Step 2 Record the connection positions of cables on the DMU02C1 panel and remove the cables.
Step 3 Remove the old DMU02C1.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 76


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-8 Removing the old DMU02C1

Step 4 Record the DIP switch settings on the removed DMU02C1.


Step 5 Set the DIP switch on the new DMU02C1 based on the recorded settings.
Step 6 Install the new DMU02C1.

Figure 4-9 Installing the new DMU02C1

Step 7 Install the cables based on the recorded information.


Step 8 Remove the protective gloves.
----End

Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.

4.3.7 Replacing an AC Heater


Prerequisites
 Tools and the key to the cabinet door are available.
 The new heater is intact.

Before replacing the heater, ensure that its circuit breaker is OFF.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 77


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Procedure
Step 1 Wear the protective gloves.
Step 2 Switch off the heater circuit breaker on the ACDU.
Step 3 Record the cable connection positions on the heater and disconnect the cables.
Step 4 Remove the heater.
Step 5 Install a new heater.
Step 6 Connect the cables to the heater based on the recorded information.
Step 7 Switch on the heater circuit breaker on the ACDU.
Step 8 Remove the protective gloves.
----End

4.3.8 Replacing a DC Heater


Prerequisites
 The protective gloves, Phillips screwdriver, and key to the cabinet door are available.
 The new DC heater is intact.

Procedure
Step 1 Wear protective gloves.
Step 2 Remove the DC power cable from the heater.
Step 3 Remove the faulty heater.

There are three methods for installing a heater. Remove and install a heater based on site requirements.

Figure 4-10 Removing the faulty heater

Step 4 Install the new heater.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 78


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-11 Installing the new heater

Step 5 Install the DC heater power cable.


Step 6 Remove the protective gloves.
----End

4.3.9 Replacing a TCUC Control Board


Prerequisites
 An ESD wrist strap, protective gloves, ESD box or bag, and the cabinet door key are
available.
 The new TCUC control board is intact.

Context
You need only to disconnect the power supply to the TCUC, instead of the AC input to the
power system.

Procedure
Step 1 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD
gloves.
Step 2 Switch off the TCUC circuit breaker on the DC power distribution unit (PDU).
Step 3 Record the cable connection positions on the TCUC and disconnect the cables.
Step 4 Unscrew and remove the TCUC.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 79


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-12 Removing the TCUC installation component (H1 equipment cabinet)

Figure 4-13 Removing the TCUC

Figure 4-14 Removing the TCUC (DEU equipment cabinet)

Step 5 Remove the TCUC control board.


1. Record the positions of cables on the TCUC control board, and disconnect the cables.
2. Unscrew and remove the TCUC control board.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 80


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-15 Removing the TCUC control board

Step 6 Record the positions of jumper caps on the TCUC control board.

Figure 4-16 Jumper caps on the TCUC control board (H1 equipment cabinet)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 81


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-17 Jumper caps on the TCUC control board (DEU equipment cabinet)

Step 7 Install a new TCUC control board.


1. Set jumper caps for the new TCUC control board based on the recorded information.
2. Install a new TCUC control board in the TCUC.
3. Reconnect the removed cables to the TCUC control board based on the recorded
information.
Step 8 Install the TCUC.
Step 9 Reconnect the cables to the TCUC based on the recorded information.
Step 10 Switch on the TCUC circuit breaker on the DC PDU.
Step 11 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End

Follow-up Procedure
Pack the removed component and send it to the local Huawei warehouse.

4.3.10 Replacing a Heat Exchanger Fan


Prerequisites
 The key to the cabinet door and required tools are available.
 The new fan is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 82


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Step 2 Record the positions of signal cables on the UIM, and disconnect the cables.
Step 3 Unscrew and remove the UIM.

Figure 4-18 Removing the UIM05B1

Step 4 Disconnect the interconnection terminal from the fan power cable.
Step 5 Record the fan installation direction (the arrow mark on the fan), unscrew the fan, and remove
the fan cover and fan.

Replace the faulty fans as required.

Figure 4-19 Replacing a fan

Step 6 Place the new fan based on the recorded installation direction (arrow mark on the fan), place
the fan cover, and tighten the screws.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 83


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-20 Installing a fan

Step 7 Reconnect the interconnection terminal to the fan power cable.


Step 8 Insert the UIM into the correct slot, and tighten the screws.
Step 9 Reconnect the signal cables to the UIM based on the recorded information.
Step 10 Disconnect the ground cable for the ESD wrist strap, and take off the ESD wrist strap and
ESD gloves.
----End

4.3.11 Replacing an External Circulation Fan (DEU cabinet)


Prerequisites
 An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and maintenance
tool kit are available.
 The new fan is intact.

Context
You need only to disconnect the fan power cable, instead of the AC input to the system.

Procedure
Step 1 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD
gloves.
Step 2 Disconnect the power cable.
Step 3 Remove the external circulation fan.
1. Record the positions where cables are connected to the fan, and disconnect the cables.
2. Remove the external circulation fan using a screwdriver.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 84


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-21 Removing an external circulation fan

Step 4 Install a new external circulation fan.


1. Install the new external circulation fan in the cabinet using screws.
2. Connect the removed cables to the fan based on the recorded information.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 85


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-22 Installing a new external circulation fan

Step 5 Connect the power cable.


Step 6 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End

Follow-up Procedure
Send the removed fan for repair.

4.3.12 Replacing an Internal Circulation Fan (DEU cabinet)


Prerequisites
 An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and maintenance
tool kit are available.
 The new fan is intact.

Context
You need only to disconnect the fan power cable, instead of the AC input to the system.

Procedure
Step 1 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD
gloves.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 86


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Step 2 Disconnect the power cable.


Step 3 Remove the internal circulation fan.
1. Record the positions where cables are connected to the fan, and disconnect the cables.
2. Remove the internal circulation fan using a screwdriver.

Figure 4-23 Removing an internal circulation fan

Step 4 Install a new internal circulation fan.


1. Install the new internal circulation fan in the cabinet using screws.
2. Connect the removed cables to the fans based on the recorded information.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 87


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-24 Installing a new internal circulation fan

Step 5 Connect the power cable.


Step 6 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End

Follow-up Procedure
Send the removed fan for repair.

4.3.13 Replacing a Heat Exchanger Core (DEU cabinet)

Pay attention to the installation direction when replacing a heat exchanger core.

Prerequisites
 An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and maintenance
tool kit are available.
 The new Heat Exchanger Core is intact.

Context
You do not need to disconnect the AC input to the power system.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 88


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Procedure
Step 1 Remove the heat exchanger core and record the installation direction of it.

Figure 4-25 Removing a heat exchanger core

Step 2 Clean the heat exchanger core, or replace it with a new one.
Step 3 Install the heat exchanger core according to the recorded installation direction.

Figure 4-26 Installing a new heat exchanger core

----End

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 89


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

4.3.14 Replacing a Digital Temperature and Humidity Sensor


Prerequisites
 Tools and the key to the cabinet door are available.
 The new digital temperature and humidity sensor is intact.

Procedure
Step 1 Record cable information and installation positions.
Step 2 Record the DIP switch settings.
Step 3 Disconnect the cable from the communications port on the sensor.
Step 4 Remove the faulty sensor.

Figure 4-27 Removing a sensor

Step 5 Put the new sensor on the side of the cabinet.


Step 6 Connect cables based on the recorded cable information.
Step 7 Set the DIP switch based on the recorded DIP switch information.
----End

4.3.15 Replacing a Smoke Sensor


Prerequisites
 You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, the
cabinet door key, and tools.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 90


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

 The new smoke sensor is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2 Remove the smoke sensor.
1. Remove the connected cables from the smoke sensor.
2. Hold down the button on the smoke sensor and push the smoke sensor in the OPEN
direction.
3. Unscrew the smoke sensor base.

Figure 4-28 Removing the smoke sensor

Step 3 Install a new smoke sensor.


1. Properly place the smoke sensor base and tighten the screws for it.
2. Properly place the new smoke sensor and press and push it in the CLOSE direction.
3. Reconnect the removed cables to the smoke sensor.
Step 4 Disconnect the ground cable from the ESD wrist strap, and take off the ESD wrist strap and
ESD gloves.
----End

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 91


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Follow-up Procedure
Pack the removed component and send it to the local Huawei warehouse.

4.3.16 Replacing a Water Sensor


Prerequisites
 An ESD wrist strap, ESD gloves, ESD box or bag, door key, and required tools are
available.
 The new water sensor is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2 Disconnect the water sensor from the UIM.
Step 3 Unscrew and remove the water sensor from its support.
Step 4 Install the new water sensor on the support and place the support at the bottom of the cabinet
or on the equipment room floor.
Step 5 Connect the water sensor cable to the UIM.
Step 6 Disconnect the ground cable from the ESD wrist strap, and take off the ESD wrist strap and
ESD gloves.
----End

4.3.17 Replacing a Door Status Sensor


Prerequisites
 You have obtained the cabinet door key and tools.
 The new door status sensor is intact.

Procedure
Step 1 Open the cabinet door and remove the shell of the door status sensor.
Step 2 Record the positions where the alarm cables connect to the door status sensor, and unscrew
the alarm cables.
Step 3 Unscrew the door status sensor, as shown in Figure 4-29.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 92


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-29 Removing the door status sensor

Step 4 Remove the shell of the new door status sensor and remove the screws from the signal cables.
Step 5 Properly place a new door sensor at the installation position and tighten the screws.
Step 6 Place the alarm cables in sequence and secure the screws.
Step 7 Reinstall the shell of the door status sensor.
----End

Follow-up Procedure
Check that the door status alarm is cleared.

4.3.18 Replacing a Battery Temperature Sensor


Prerequisites
 An ESD wrist strap, ESD box or bag, cabinet door key, and required tools are available.
 The new battery temperature sensor is intact.

Procedure
Step 1 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD
gloves.
Step 2 Disconnect the battery temperature sensor cable from the UIM and record the port
information.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 93


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual 4 Maintenance

Figure 4-30 Disconnecting the battery temperature sensor cable

Step 3 Cut off the cable tie of the battery temperature sensor and remove the sensor.

Ensure that the detection probe of the battery temperature sensor is not in contact with a metal
surface.

Step 4 Properly place the new battery temperature sensor and bind it securely with a cable tie.
Step 5 Connect the battery temperature sensor cable to the UIM.
Step 6 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 94


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual A Technical Specifications

A Technical Specifications

The technical specifications described in this section apply only to power cabinets, equipment
cabinets, and battery cabinets. For details about the technical specifications of the PSU
(DPU40D-N06A3) and lithium battery (DBU20B-N12A3), see DPU40D-N06A3,
DBU20B-N12A3, and DBU50B-N12A1 Distributed Power System User Manual at
http://support.huawei.com.

A.1 Environmental Specifications


Table A-1 Environmental specifications

Item Specifications

Operating temperature –40°C to +45°C (1120 W/m2, without solar radiation)


Transportation –40°C to +70°C
temperature
Storage temperature –40°C to +70°C
Operating humidity 5%–95% RH
Storage humidity 5%–95% RH
Altitude 0–4000 m
When the altitude ranges from 2000 m to 4000 m, the
operating temperature decreases by 1°C for each additional
200 m.
Noise level Meets GR 487 standard; acoustic pressure level < 65 dBA at
1.5 m, 45°C
Other requirements  There is no conductive dust, corrosive gas, or explosion
hazard.
 Dust, corrosive substances, pests, molds, and other
indicators should be controlled in accordance with class
4.1 requirements in ETSI EN 300 019-1-4 (V2.2.1).

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 95


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual A Technical Specifications

A.2 Electrical Specifications


Table A-2 Electrical specifications

Item Specifications
AC input Input system and  220/380 V AC three-phase, four-wire
input voltage  220 V AC Single-Phase
Input frequency Frequency range: 45–66 Hz; nominal
frequency: 50 Hz/60 Hz
Power factor ≥ 0.99 (load ≥ 50%)
THD ≤ 5% (Vin = 208 V AC, 220 V AC, 230 V AC;
50%–100% load)
DC output Output voltage 43.2–57.6 V DC
range
Default output 53.5 V DC
voltage
Output power Output power = Output power of a single
rectifier x Number of rectifiers
Regulated voltage ≤ ±1%
precision
Ripple and noise ≤ 200 mVp-p
Psophometrically ≤ 2 mV
weighted noise
Unbalance of load ≤ ±5%
sharing
AC input AC input > 300 V AC
protection overvoltage
protection threshold
AC input When the voltage is restored to 290 V AC, the
overvoltage output restores.
recovery threshold
AC input < 85 V AC
undervoltage
protection threshold
AC input When the voltage is restored to 90 V AC, the
undervoltage output restores.
recovery threshold
DC output DC output –58.5 V DC to –60.5 V DC
protection overvoltage 1. If overvoltage occurs due to an internal
protection threshold fault, the rectifier locks out.
2. If the external voltage is greater than –63 V

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 96


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual A Technical Specifications

Item Specifications
for more than 500 ms, the rectifier locks
out.
AC surge Nominal surge discharge current: 30 kA (8/20 µs)
protection
DC surge 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common
protection mode
Safety design Complies with IEC 62368 and IEC 60950-22.
MTBF 200,000 hours (at 25°C)

A.3 EMC Specifications


Table A-3 EMC specifications

Item Specifications
Electromagnetic Conducted emission  AC power port: Class B
interference (EMI) (CE)  DC power port: Class A1
 Signal port: Class B
Reference standard: EN55032,
EN300386
Radiated interference Class B, reference standard: EN55032,
(RE) EN300386
Harmonic current Reference standard: EN61000-3-12
Voltage fluctuation Reference standard: EN61000-3-3,
and flicker EN61000-3-11
EMS Electrostatic  Contact discharge: 6 kV; air
discharge (ESD) discharge: 8 kV (criterion B)
 Contact discharge: 8 kV; air
discharge: 15 kV (criterion R)
Reference standard: EN61000-4-2
Electrical fast AC power port: ±2 kV; DC power
transient (EFT) port: ±2 kV; signal port: ±1 kV
Reference standard: EN61000-4-4
(criterion B)
Radiated 80 MHz-2.7 GHz; 10 V/m; 80% AM
susceptibility (RS) (1 KHz)
Reference standard: EN61000-4-3
(criterion A)
Conducted Power port: 10 V; signal port: 3 V
susceptibility (CS) Reference standard: EN61000-4-6

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 97


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual A Technical Specifications

Item Specifications
Surge susceptibility  AC power port: differential mode:
(Surge) 2 kV; common mode: 4 kV
 DC power port: differential mode:
1 kV; common mode: 2 kV
 Signal port: differential mode: 500
V; common mode: 1 kV
Reference standard: EN61000-4-5
(criterion B)
Voltage dip (DIP) Reference standard: EN61000-4-11

Note 1: This is a class A product. In residential areas, this product may cause radio
interference. Therefore, users may be required to take appropriate measures.

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 98


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual B Electrical Conceptual Diagrams

B Electrical Conceptual Diagrams

Figure B-1 Electrical conceptual diagram

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 99


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual C Associations Between UIM Dry Contacts and Alarms

C Associations Between UIM Dry Contacts


and Alarms

Table C-1 Associations between dry contacts and alarms (H2 power cabinet)

Port Type Silk Screen Associated Alarm


Dry contact input DIN1 Dry contact input 1
DIN1-DIN3 (closed: DIN2 Dry contact input 2
alarm; open: normal)
DIN4 (closed: normal; DIN3 Dry contact input 3
open: alarm)
DIN4 Heater alarm
Dry contact output ALM1 AC failure
Default setting (closed: Long-time AC failure (disabled by
alarm; open: normal). default)
The setting can be
modified. ALM2 Busbar overvoltage
Busbar ultra overvoltage
Busbar undervoltage
Busbar ultra undervoltage
Lithium battery discharge
ALM3 Single-rectifier fault – redundancy
(disabled by default)
Single-rectifier fault – non-redundancy
(disabled by default)
Multi-rectifier fault
All-rectifier communication failure
Rectifier fault
Rectifier protection
Communication failure
ALM4 AC SPD fault
AC SPD2 fault

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 100


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual C Associations Between UIM Dry Contacts and Alarms

Port Type Silk Screen Associated Alarm


ALM5 LLVD Load fuse blown
BLVD Load fuse blown
Battery fuse blown
ALM6 High battery temperature
Very high battery temperature
Low battery temperature
Very low battery temperature
High ambient temperature
Very high ambient temperature
Low ambient temperature
ALM7 Door status alarm
Smoke alarm
Water alarm
ALM8 Power cabinet temperature control:
Fan 1 fault, fan 2 fault, fan 3 fault,
Return Vent Overtemperature Alarm
When an external direct ventilation
battery cabinet or a heat exchanger
cabinet is used:
Air outlet overtemperature, air outlet
undertemperature, air inlet
overtemperature, air inlet
undertemperature, return air vent
overtemperature, return air vent
undertemperature, EXTFAN1 fault,
EXTFAN2 fault, INFAN1 fault,
INFAN2 fault, INFAN3 fault,
INFAN4 fault, TEC air conditioner
fault
Heater fault (from: DIN4)

Table C-2 Associations between dry contacts and alarms (A2 power cabinet, A3 power cabinet)

Port Type Silk Screen Associated Alarm


Dry contact input DIN1 Dry contact input 1
DIN1-DIN3 (closed: DIN2 Dry contact input 2
alarm; open: normal)
DIN4 (closed: normal; DIN3 Dry contact input 3
open: alarm)
DIN4 Heater alarm
Dry contact output ALM1 AC failure
Default setting (closed: Long-time AC failure (disabled by

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 101


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual C Associations Between UIM Dry Contacts and Alarms

Port Type Silk Screen Associated Alarm


alarm; open: normal). default)
The setting can be
modified. ALM2 Busbar overvoltage
Busbar ultra overvoltage
Busbar undervoltage
Busbar ultra undervoltage
Lithium battery discharge
ALM3 Single-rectifier fault – redundancy
(disabled by default)
Single-rectifier fault – non-redundancy
(disabled by default)
Multi-rectifier fault
All-rectifier communication failure
Rectifier fault
Rectifier protection
Communication failure
ALM4 AC SPD fault
AC SPD2 fault
ALM5 LLVD Load fuse blown
BLVD Load fuse blown
Battery fuse blown
ALM6 High battery temperature
Very high battery temperature
Low battery temperature
Very low battery temperature
High ambient temperature
Very high ambient temperature
Low ambient temperature
ALM7 Door status alarm
Smoke alarm
Water alarm
ALM8 Air Conditioner Fault Alarm:
High Air Conditioner Temperature,
Air Conditioner Internal Fan Fault, Air
Conditioner Outdoor Fan Fault, Air
Conditioner Compressor Fault, Air
Conditioner Evaporator Freezing,
Frequent High Air Conditioner
Pressure, Communication Failure,
Frequent Low Air Conditioner
Pressure, AC Power Failure,
Non-automatic Mode Alarm, AC

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 102


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual C Associations Between UIM Dry Contacts and Alarms

Port Type Silk Screen Associated Alarm


Overvoltage, AC Undervoltage, AC
Input Fault
When an external direct ventilation
battery cabinet or a heat exchanger
cabinet is used:
Air outlet overtemperature, air outlet
undertemperature, air inlet
overtemperature, air inlet
undertemperature, return air vent
overtemperature, return air vent
undertemperature, EXTFAN1 fault,
EXTFAN2 fault, INFAN1 fault,
INFAN2 fault, INFAN3 fault,
INFAN4 fault, TEC air conditioner
fault
Heater fault (from: DIN4)

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 103


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual D Acronyms and Abbreviations

D Acronyms and Abbreviations

A
ACDB Alternating current distribution box

B
BLVD Battery low voltage disconnection

D
DCDB Direct Current Distribution Box

E
EMC Electromagnetic compatibility
EMI Electromagnetic interference
EMS Electromagnetic susceptibility

H
HTTPS Hypertext Transfer Protocol Secure

L
LLVD Load low voltage disconnection

I
IEC International Electrotechnical Commission

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 104


MTS9000A Telecom Power (Russia, Veon,
MTS9304A-HD10A1, MTS9304A-AX10A1,
MTS9514A-GX1401)
User Manual D Acronyms and Abbreviations

M
MTBF Mean time between failures

P
PSU Power supply unit

R
RCD Residual current device

S
SMU Site monitoring unit
SNMP Simple Network Management Protocol
SPD Surge protection device

T
TCUC Temperature control unit C

U
UIM User interface module

Issue 01 (2020-01-17) Copyright © Huawei Technologies Co., Ltd. 105