WASTE SYSTEM COMPONENTS
10
WASTE SYSTEM COMPONENTS - BRANCHES
Common branches
11
WASTE SYSTEM COMPONENTS - BRANCHES
EN 12056 – 2 GRAVITY
DRAINAGE SYSTEMS
Types of system:
SYSTEM I
12
WASTE SYSTEM COMPONENTS - BRANCHES
EN 12056 – 2 GRAVITY
DRAINAGE SYSTEMS
Types of system:
SYSTEM II
13
WASTE SYSTEM COMPONENTS - BRANCHES
EN 12056 – 2 GRAVITY
DRAINAGE SYSTEMS
Types of system:
SYSTEM III
14
WASTE SYSTEM COMPONENTS - BRANCHES
EN 12056 – 2 GRAVITY
DRAINAGE SYSTEMS
Types of system:
SYSTEM IV
15
WASTE SYSTEM COMPONENTS - BRANCHES
NOT VENTILATED VENTILATED COMMON
COMMON BRANCHES BRANCHES
H
H
L L
16
WASTE SYSTEM COMPONENTS - STACKS
Ventilation pipe
Waste stack
17
WASTE SYSTEM COMPONENTS - STACKS
18
VERTICAL STACKS – TYPE OF CONNECTION
SQUARED BRANCH ANGLE BRANCH
19
VERTICAL STACKS – TYPE OF CONNECTION
SQUARED BRANCH ANGLE BRANCH
20
VERTICAL STACKS – TYPE OF CONNECTION
21
VERTICAL STACKS – TYPE OF VENTILATION
PRIMARY VENTILATION
• Suggested up to max 5
floors
22
VERTICAL STACKS – TYPE OF VENTILATION
PARALLEL VENTILATION
• Suggested to buildings
higher than 3 floors
23
VERTICAL STACKS – TYPE OF VENTILATION
SECONDARY VENTILATION
• Solution suggested for
systems with a high value of
contemporaneity and height
• Allow having common
branches with a length up to
10 meters
24
VERTICAL STACKS – FLOW RATE
Primary
100 - 4,0 5,2
ventilation
25
VERTICAL STACKS – FLOW RATE
26
VERTICAL STACKS – FLOW RATE
Primary
100 - 4,0 5,2
ventilation
Parallel or
secondary 100 50 5,6 7,3
ventilation
27
VENTILATION BRANCH FITTING
28
VENTILATION BRANCH FITTING
29
VENTILATION BRANCH FITTING
30
VENTILATION BRANCH FITTING
Mixing chamber
31
VENTILATION BRANCH FITTING
Internal
baffle
32
VENTILATION BRANCH FITTING - ADVANTAGES
Max flow rate Qmax [l/s]
SQUARED ANGLE BRANCH, SWEPT
Waste BRANCH BRANCH, BALL BRANCH
Type of Ventilation
stack
ventilation stack DN
DN
Primary
100 - 4,0 5,2
ventilation
Parallel or
secondary 100 50 5,6 7,3
ventilation
Ventilation
branch 100 - 13,0
fitting
33
VENTILATION BRANCH FITTING - ADVANTAGES
Number of typical apartments
SQUARED ANGLE BRANCH, SWEPT
Waste BRANCH BRANCH, BALL BRANCH
Type of Ventilation
stack
ventilation stack DN
DN
Primary
100 - 9 16
ventilation
Parallel or
secondary 100 50 18 31
ventilation
Ventilation
branch 100 - 100
fitting
* Typical apartments composed by: Sink, Dishwasher, Bathtub, washbasin, washing machine, WC
34
VENTILATION BRANCH FITTING - ADVANTAGES
• Less structural
interferences
• Great design
flexibility
35
VENTILATION BRANCH FITTING - ADVANTAGES
• Less structural
interferences
• Great design
flexibility
• Less pipes quantity
• Time and cost
savings
36
VENTILATION BRANCH FITTING - ADVANTAGES
37
VENTILATION BRANCH FITTING - ADVANTAGES
• Up to 20 m for
ventilated branches
38
VENTILATION BRANCH FITTING - ADVANTAGES
• Realization of a
circumventilation
(Pressure Relief Loop)
at the bottom of the
stack
2m
2m
39
EXAMPLE OF CALCULATION
AND CASE STUDY
CASE STUDY
42
CASE STUDY
43
CASE STUDY
44
CASE STUDY
45
CASE STUDY
BUILDING DATA:
• n° 62 residential floors
• n° 8 commercial floors
• 550 m²/net surface
• 75.000 m² total
• 379 apartment
46
SIZING OF THE VERICAL STACK
CALCULATION OF THE FLOW RATE
According to EN 12056-2
= · ∑
With:
K contemporaneity factor
DU drainage unit
TYPE OF of every sanitary
BUILDING FACTOR
fixture use
Intermittent (as(Residential,
per tableoffices)
values) 0,5
Frequent use (Hospital, Hotels) 0,7
Very frequent use (Public toilet)
FIXTURE DU [l/s]1,0
Special use (Laboratory)
Washbasin 0,5 1,2
Shower 0,6
Bath tub 0,8
WC 9l 2,5
Sink 0,8
47
SIZING OF THE VERICAL STACK
Black Water
FIXTURE DU [l/s]
WC [1] 2,5
WC [2] 2,5
TOTAL DU 5,0
Grey Water
FIXTURE DU [l/s]
Washbasin [1] 0,5
Shower [1] 0,6
Bath tub[1] 0,8
Washbasin [2] 0,5
Shower [2] 0,6
Sink 0,8
TOTAL DU 3,8
48
SIZING OF THE VERICAL STACK
Black Water
FIXTURE DU [l/s]
WC [1] 2,5
WC [2] 2,5
TOTAL DU 5,0
Grey Water
FIXTURE DU [l/s]
Washbasin [1] 0,5
Shower [1] 0,6
Bath tub[1]
CALCULATION 0,8 RATE
OF THE FLOW CALCULATION OF THE FLOW RATE
Washbasin [2] = · ∑ 0,5 = · ∑
Shower [2] 0,6
Sink = 0,5 · 5 · 62 = 8,80
0,8l/s = 0,5 · 3,8 · 62 = 7,67 l/s
TOTAL DU 3,8
49
SIZING OF THE VERICAL STACK
75 50 2,00
90 63 2,60
110 75 5,60
125 90 7,60
160 110 12,40
200 125 21,00
SYSTEM LAYOUT
51
SYSTEM LAYOUT
52
SYSTEM LAYOUT – STACK DOUBLING
SIZING OF THE VERICAL STACK
75 50 2,00
90 63 2,60
110 75 5,60
125 90 7,60
160 110 12,40
200 125 21,00
MATERIAL – SOLUTION 1
55
VENTILATION BRANCH FITTING
VALSIR PROPOSAL
VENTILATION BRANCH
FITTING
(VBF)
56
VENTILATION BRANCH FITTING
Max flow rate Qmax [l/s]
SQUARED ANGLE BRANCH, SWEPT
Waste BRANCH BRANCH, BALL BRANCH
Type of Ventilation
stack
ventilation stack DN
DN
Primary
100 - 4,0 5,2
ventilation
Parallel or
secondary 100 70 5,6 7,3
ventilation
Ventilation
branch 100 - 13,0
fitting
57
VENTILATION BRANCH FITTING
• Up to 8 meter for not
ventilated branches
58
VENTILATION BRANCH FITTING
• Realization of a
circumventilation
(Pressure Relief Loop)
at the bottom of the
stack
2m
2m
59
SIZING OF THE VERICAL STACK
60
SIZING OF THE VERICAL STACK
75 50 2,00
90 63 2,60
110 75 5,60
125 90 7,60
160 110 12,40
VBF 110 13,0 l/s
MATERIAL – SOLUTION 2
62
COMPARISON OF THE MATERIAL
STACKS
Solution 1 Solution 2 Comparison
Item Quantity Unit Quantity Unit % material
63
REDUCTION OF THE SHAFT
64