CHARACTERISTICS

• Visible safe isolation gap


• Fault-free operations in extreme weather conditions
• Low wear and ageing reduction of all active components achieved thanks to the application of the highest
quality switching units, which have excellent mechanical and electrical properties according
to norm 62271-103
• Possibility to expand with other components e.g. current transformers, lightning arresters
• High switching current 100A without the need to switch off the whole linear sequence.

RN III 24/4-100A i RUN III 24/4-100A switch disconnector parameters


Rated voltage Ur 24(25)kV
Rated frequency – number of phases fr 50 Hz-3
Rated power frequency withstand voltage – in wet conditions and when it rains – 1 min. Ud
- To the ground and inter-phases 50kV
- Safe isolation break 60kV
Rated lightning impulse withstand voltage 1,2/50ms Up
- To the ground and inter-phases 125kV
- Safe isolation break 145kV
Rated continuous current Ir 400A
Rated short-time withstand current Ik 16kA (1s)
Rated peak current strength Ip 40kA
Rated short-circuit making current Ima 16kA
Rated short-circuit breaking current in a circuit with low inductance Iload 100A
Rated short-circuit breaking current in a ring network circuit Iloop 100A
Rated short-circuit breaking current of cable charging Icc 20A
Mechanical durability (the process defined as closing and opening) 5000
Operation temperature - 40°C + 60°C
Electricity class E3

Compliance with standards:

• PN-EN 62271-103:2011 – “High Voltage Switchgear and Control gear – Part 103: Disconnectors with rated
voltages above 1 kV and up to and including 52 kV”,
• PN-EN 62271-1:2009+A1:2011 - “High Voltage Switchgear and Control gear – Part 1: Common
specifications”,
• PN-EN 62271-102:2005; PN-EN 62271-102 :2005/A1:2011 - “High Voltage Switchgear and Control
gear – Part 102: High voltage altering current disconnectors and grounding switches”,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN 61140:2005/A1 - Protection against electric shock. Common aspects for installation and equipment.
Switch disconnectors have a certificate of conformity from the accredited body: the Institute of
Electrical Engineering in Warsaw.

www.zpue.com 25
VIEW, DIMENSIONS AND CONSTRUCTION

6 7
1000 450

4 8
10
11

700
3 2

800
5
9

380 1

710 1700

1 - switch disconnector frame (beam) 7 - air interrupter 100A


2 - bushing insulator 8 - connecting cable
3 - main contacts of the switch disconnector 9 - drive lever of the switch disconnector
4 - flicker movable contacts 10 - connection terminal
5 - movable support 11 - oscillating element with a terminal strip
6 - element for the interrupter installation

LOAD BREAK INTERRUPTER VIEW 100A

Load break interrupter view – switch disconnector closed Load break interrupter view – switch disconnector opened

26 www.zpue.com
MV overhead connectors
6 / Connectors with limited connection capability 25 A
in frame and modular version

frame version

Modular version frame version Modular version

CONSTRUCTION

Connectors are three-pole appliances with one drive. Each pole is equipped with two supporting insulators –
fixed or movable. Connectors can be equipped with porcelain, composite insulators with cycloaliphatic resin or
silicone in an HTV rubber cover. Handles with main contacts are installed to the insulators. The main contacts are
made from tinning coated, profiled copper flat bars. The construction of the contacts allows their self-guidance,
and provides a large contact surface and clamping force.
Appliances, as standard, are equipped with current terminals, which allow the installation of isolated or naked
aluminum electricity cables with a cross-section of 16-95 mm2 (a special design allows connecting cables with
a cross-section of 120 mm2). This information must be provided while placing an order or request. Additionally,
appliances with earthing switches are equipped with a flexible contact, which takes over the effects of bending on
a movable appliance pole.
Connectors in the modular structure can be expanded with additional elements such as: lightning arresters,
additional support insulators. They can be installed in the horizontal or vertical position.

www.zpue.com 27
CHARACTERISTICS

• Visible safe isolation gap,


• Fault-free operations in extreme weather conditions,
• Low wear and ageing reduction of all active components achieved thanks to the application of the highest
quality switching units, which have excellent mechanical and electrical properties according to the latest
norms PN-EN.

CONNECTORS WITH LIMITED CONNECTION CAPABILITY 25 A IN A FRAME VERSION

Connector parameters RN III 24(36)/4; RUN III 24(36)/4; ON III 24(36)/4; OUN III 24(36)/4

Connector type RUN (RN) RUN (RN) OUN (ON) OUN (ON)

Rated voltage Ur 24(25)kV 36kV 24(25)kV 36kV


Rated frequency – number of phases fr 50 Hz-3 50 Hz-3 50 Hz-3 50 Hz-3
Rated power frequency withstand voltage –
in wet conditions and when it rains – 1 min. Ud
- To the ground and inter-phases 50kV 70kV 50kV 70kV
- Safe isolation break 60kV 80kV 60kV 80kV
Rated lightning impulse withstand voltage 1,2/50ms Up
- To the ground and inter-phases 125kV 170kV 125kV 170kV
- Safe isolation break 145kV 195kV 145kV 195kV
Rated continuous current Ir 400A 400A 400A 400A
(800A*) (800A*) (800A*) (800A*)
Rated short-time withstand current Ik 16kA (1s) 16kA (1s) 16kA (1s) 16kA (1s)
Rated peak current strength Ip 40kA 40kA 40kA 40kA
Rated short-circuit making current Ima 16kA 16kA 16kA 16kA
Rated short-circuit breaking current in a circuit with low inductance Iload 25A 25A ----- -----
Rated short-circuit breaking current in a ring network circuit Iloop 25A 25A ----- -----
Rated short-circuit breaking current of cable charging Icc 20A 10A ----- -----
Mechanical durability (the process defined as closing and opening) 5000 5000 2000 2000
Operation temperature - 40°C - 40°C - 40°C - 40°C
+ 50°C + 50°C + 50°C + 50°C
Electricity class E3 E3 ----- -----

* Parameters were given to the connector with fixed poles

28 www.zpue.com
Compliance with standards:

• PN-EN 62271-103:2011 – “High Voltage Switchgear and Control gear – Part 103: Disconnectors with rated
voltages above 1 kV and up to and including 52 kV”,
• PN-EN 62271-1:2009+A1:2011 - “High Voltage Switchgear and Control gear – Part 1: Common
specifications”,
• PN-EN 62271-102:2005; PN-EN 62271-102 :2005/A1:2011 - “High Voltage Switchgear and Control
gear – Part 102: High voltage altering current disconnectors and earthing switches”,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN 61140:2005/A1 - Protection against electric shock. Common aspects for installation and equipment.

Switch disconnectors and disconnectors have a certificate of conformity from the accredited body:
the Institute of Electrical Engineering in Warsaw.

VIEW, DIMENSIONS AND CONSTRUCTION OF THE MODULAR CONNECTORS

1000 450

6 11

10
810
910

3 2
5
9

7
8

380 1

710 1700

* Dimensions relating to the connectors 36 kV

1 - switch disconnector frame (beam) 7 - earthing switch contact


2 - bushing insulator 8 - earthing switch supporting structure
3 - switch disconnector main contacts 9 - drive lever of the switch disconnector
4 - flicker movable contacts/ snap action movable contacts 10 - connection terminal
5 - movable support 11 - oscillating element with a terminal strip
6 - snap action contact

www.zpue.com 29
VIEW, DIMENSIONS AND CONSTRUCTION OF THE FRAME CONNECTORS

435 (465*) 435 (465*) 105


4

11
6
10
740 (960*)

7 2
3
1
9 8
5

1000 (1130*) 1080 (1140*)

* Dimensions relating to the connectors 36 kV

1 - switch disconnector frame (beam) 7 - earthing switch contact


2 - bushing insulator 8 - earthing switch supporting structure
3 - switch disconnector main contacts 9 - drive lever of the switch disconnector
4 - flicker movable contacts/ snap action movable contacts 10 - connection terminal
5 - movable support 11 - oscillating element with a terminal strip
6 - snap action contact

CONNECTORS WITH LIMITED CAPABILITY RATED CONTINUOUS CURRENT 800 A

The Connector structure refers to well-known power industry solutions, which have been in use for many years
now. A modified contact system allows the transmission and switching capability to be increased. The application
of silicone drive insulators eliminates the risk of damage to this element. The main shaft interlock prevents faulty
switching operations and considerably improves the handling safety of the appliance. Connectors can be equipped
with porcelain, composite insulators with cycloaliphatic resin or silicone in an HTV rubber cover. Contact elements
applied from our production units guarantees the proper electrical and mechanical operation of the appliance.
Appliances are designed to power lines with considerable cable cross-sections up to 240 mm2, overhead
switchgear busbar bridges and stations 110 kV/15 – 24 – 36 kV and for cable trays. Standard hand drives
manufactured by ZPUE S.A. are used to control the connectors.

VIEW, DIMENSIONS AND CONSTRUCTION OF THE CONNECTORS 800 A

435 (465*) 435 (465*) 115 6


4
3
10

5 7
2

9 11

1100 (1160*) 1020 (1080*)

30 www.zpue.com
1

1020 (1080*)
8

1 - switch disconnector frame (beam)


2 - bushing insulator
3 - main contacts of the switch disconnector
4 - flicker movable contacts
5 - movable support
6 - element for the interrupter installation
7 - air interrupter 100A
8 - connecting cable
9 - drive lever of the switch disconnector
10 - connection terminal
11 - oscillating element with a terminal strip

www.zpue.com 31
CONNECTORS WITH LIMITED CONNECTION CAPABILITY 25 A
IN FRAME AND MODULAR VERSION

- - -
V – operates in a vertical position 24 kV*
H – operates in a horizontal position *

(b) – white porcelain insulator without


markings – brown porcelain insulator

K – cycloaliphatic resin composite


S – composite in a silicone rubber cover
P – porcelain

Without designation – frame


W – modular
N – with a fixed pole

i – with the bushing insulator *


o – with the lightning arrester

Breaking capacity current 100 A with a break interrupter

Rated current 4 - 400 A


8 - 800 A **

Rated voltage 24 kV
36 kV

Disconnector type (three-pole)

Overhead

U – with the grounding switch


no designation - without the earthing switch
R – switch disconnector with limited connection capability
O - disconnector
RUN III 24/4 P
Stands for an overhead, three-pole switch disconnector with the earthing switch for the rated voltage 24 kV and
rated continuous current 400 A.

ON III 24/4 P
Stands for an overhead, three-pole disconnector for the rated voltage 24 kV and rated continuous current 400 A.

RUN III 24/4 o W-S-V


Stands for an overhead, three-pole switch disconnector with the earthing switch 24 kV/400 A with an arrester,
modular composite insulators in a silicone rubber cover designed for vertical installation

OUN III 24/8 N-S


Overhead, three-pole disconnector with the earthing switch 24 kV/800 A with a fixed pole, composite insulators in
a silicone rubber cover

OUN III 36/8 N-S


Overhead, three-phase disconnector with the earthing switch 36 kV/800 A with a fixed pole, composite insulators
in a silicone rubber cover

* refers to the modular connectors


** refers to the fixed pole

32 www.zpue.com
CONNECTORS DESIGN VARIANTS

Frame connectors

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Disconnector P (51,5 kg) P (53,5 kg)


S (41,3 kg) Disconnector with S (43,3 kg)
ON III 24/4 P(S)(K) the earthing switch
K (47,5 kg) K (49,5 kg)
OUN III 24/4 P(S)(K)

P (51,7 kg) P (53,7 kg)


Switch disconnector Switch disconnector
S (41,5 kg) S (43,5 kg)
RN III 24/4 P(S)(K) with the earthing switch
K (47,7 kg) K (49,7 kg)
RUN III 24/4 P(S)(K)

P (68,7 kg) Disconnector with P. (73,3 kg)


Disconnector
S (53,3 kg) the earthing switch S (55,3 kg)
ON III 36/4 P(S)(K)
K (59,5 kg) OUN III 36/4 P(S)(K) K (64,1 kg)

P (69,0 kg) P (73,7 kg)


Switch disconnector Switch disconnector
S (53,8 kg) S (55,7 kg)
RN III 36/4 P(S)(K) with the earthing switch
K (59,8 kg) K (64,5 kg)
RUN III 36/4 P(S)(K)

P (80,2 kg) P (90,2 kg)


Disconnector Switch disconnector
S (70,0 kg) S (78,0 kg)
ON III 24/8 N-P(S)(K) with the earthing switch
K (74,5 kg) K (82,5 kg)
OUN III 24/8 N-P(S)(K)

P (100 kg) Switch disconnector P (108 kg)


Switch disconnector
S (85,0 kg) with the earthing switch S (93,0 kg)
RN III 36/8 N-P(S)(K)
K (92,0 kg) RUN III 36/8 N-P(S)(K) K (98,5 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change of the device's
weight and dimensions.

www.zpue.com 33
CONNECTORS DESIGN VARIANTS

Modular connectors in a basic version (horizontal)

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Disconnector Disconnector with


ON III 24/4 the earthing switch
W-S(K)(P)-H OUN III 24/4
W-S(K)(P)-H

P (59,5 kg) P (61,5 kg)


S (49,3 kg) S (51,5 kg)
K (57,5 kg) K (58,5 kg)

Switch Switch disconnector


disconnector with the
RN III 24/4 earthing switch
W-S(K)(P)-H RUN III 24/4
W-S(K)(P)-H

P (61,5 kg) P (63,5 kg)


S (51,5 kg) S (53,5 kg)
K (59,5 kg) K (60,0 kg)

Modular connectors in a basic version (vertical)

Disconnector Disconnector with


ON III 24/4 the earthing switch
W-S(K)(P)-V OUN III 24/4
W-S(K)(P)-V

P (59,5 kg) P (61,5 kg)


S (49,3 kg) S (51,5 kg)
K (57,5 kg) K (58,5 kg)

Switch Switch disconnector


disconnector with the
RN III 24/4 earthing switch
W-S(K)(P)-V RUN III 24/4
W-S(K)(P)-V

P (61,5 kg) P (63,5 kg)


S (51,5 kg) S (53,5 kg)
K (59,5 kg) K (60,0 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.

34 www.zpue.com
CONNECTORS DESIGN VARIANTS

Modular connectors with the construction for lightning arresters installation (horizontal)

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Disconnector Disconnector with


ON III 24/4 the earthing switch
o W-S(K)(P)-H OUN III 24/4
o W-S(K)(P)-H

P (65,5 kg) P (67,5 kg)


S (55,3 kg) S (57,3 kg)
K (63,5 kg) K (65,5 kg)

Switch Switch disconnector


disconnector with the earthing switch
RN III 24/4 RUN III 24/4
o W-S(K)(P)-H o W-S(K)(P)-H

P (67,5 kg) P (69,5 kg)


S (57,3 kg) S (59,3 kg)
K (65,5 kg) K (67,5 kg)

Modular connectors with the construction for support insulators installation (horizontal)

Disconnector Disconnector with


ON III 24/4 the earthing switch
and W-S(K)(P)-H OUN III 24/4
and W-S(K)(P)-H

P (65,5 kg) P (67,5 kg)


S (55,3 kg) S (57,3 kg)
K (63,5 kg) K (65,5 kg)

Switch disconnector Switch disconnector


RN III 24/4 with the earthing switch
and W-S(K)(P)-H RUN III 24/4
i W-S(K)(P)-H

P (67,5 kg) P (69,5 kg)


S (57,3 kg) S (59,3 kg)
K (65,5 kg) K (67,5 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result
in a change of the device's weight and dimensions.

www.zpue.com 35
CONNECTORS DESIGN VARIANTS

Modular connectors with the construction for lightning arresters installation (vertical)

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Disconnector Disconnector
ON III 24/4 with the
o W-S(K)(P)-V earthing switch
OUN III 24/4
o W-S(K)(P)-V

P (65,5 kg) P (67,5 kg)


S (55,3 kg) S (57,3 kg)
K (63,5 kg) K (65,5 kg)

Switch disconnector Switch disconnector


RN III 24/4 with the
o W-S(K)(P)-V earthing switch
RUN III 24/4
o W-S(K)(P)-V

P (67,5 kg) P (69,5 kg)


S (57,3 kg) S (59,3 kg)
K (65,5 kg) K (67,5 kg)

Modular connectors with the construction for support insulators installation (vertical)

Disconnector Disconnector with


ON III 24/4 the earthing switch
and W-S(K)(P)-V OUN III 24/4
i W-S(K)(P)-V

P (65,5 kg) P (67,5 kg)


S (55,3 kg) S (57,3 kg)
K (63,5 kg) K (65,5 kg)

Switch Switch disconnector


disconnector with the
RN III 24/4 earthing switch
i W-S(K)(P)-V RUN III 24/4
i W-S(K)(P)-V

P (67,5 kg) P (69,5 kg)


S (57,3 kg) S (59,3 kg)
K (65,5 kg) K (67,5 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result
in a change of the device's weight and dimensions.

36 www.zpue.com
CONNECTORS DESIGN VARIANTS

Modular connectors with air interrupters 100 A (horizontal)

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Switch disconnector Switch disconnector


RN III 24/4-100A with the
W-S(K)(P)-H earthing switch
RUN III 24/4-100A
W-S(K)(P)-H

P (63,5 kg) P (65,5 kg)


S (53,3 kg) S (55,5 kg)
K (61,5 kg) K (62,0 kg)

Modular connectors with the construction for lightning arresters installation (horizontal)

Switch disconnector Switch disconnector


RN III 24/4-100A with the
o W-S(K)(P)-H earthing switch
RUN III 24/4-100A
o W-S(K)(P)-H

P (69,5 kg) P (71,5 kg)


S (59,5 kg) S (61,3 kg)
K (67,5 kg) K (69,5 kg)

Modular connectors with air interrupters 100 A (vertical)

Switch disconnector Switch disconnector


RN III 24/4-100A with the
W-S(K)(P)-V earthing switch
RUN III 24/4-100A
W-S(K)(P)-V

P (63,5 kg) P (65,5 kg)


S (53,3 kg) S (55,5 kg)
K (61,5 kg) K (62,0 kg)

Modular connectors with the construction for lightning arresters installation (vertical)

Switch disconnector Switch disconnector


RN III 24/4-100A with the
o W-S(K)(P)-V earthing switch
RUN III 24/4-100A
o W-S(K)(P)-V

P (69,5 kg) P (71,5 kg)


S (59,5 kg) S (61,3 kg)
K (67,5 kg) K (69,5 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.

www.zpue.com 37
CONNECTORS DESIGN VARIANTS

Modular connectors for 36 kV in a Basic version (horizontal)

Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight

Disconnector Disconnector
ON III 36/4 with the
W-S(K)(P)-H earthing switch
OUN III 36/4
W-S(K)(P)-H

P (64,0 kg) P (66,5 kg)


S (54,3 kg) S (56,5 kg)
K (62,5 kg) K (63,5 kg)

Switch disconnector Switch disconnector


RN III 36/4 with the
W-S(K)(P)-H earthing switch
RUN III 36/4
W-S(K)(P)-H

P (66,5 kg) P (68,5 kg)


S (56,5 kg) S (58,5 kg)
K (64,5 kg) K (65,0 kg)

Modular connectors for 36 kV with the construction for lightning arresters installation (horizontal)

Disconnector Disconnector
ON III 36/4 with the
o W-S(K)(P)-H earthing switch
OUN III 36/4
o W-S(K)(P)-H

P.(73,5 kg) P (76,5 kg)


S (64,8 kg) S (67,3 kg)
K (72,5, kg) K (75,0 kg)

Switch disconnector Switch disconnector


RN III 36/4 with the
o W-S(K)(P)-H earthing switch
RUN III 36/4
o W-S(K)(P)-H

P (77,5 kg) P (79,5 kg)


S (66,0 kg) S (68,5 kg)
K (75,0 kg) K (77,5 kg)

Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.

38 www.zpue.com
MV overhead connectors
7 / Overhead rail switch disconnector RNK-1

CONSTRUCTION

Switch disconnector RNK-1 is designed for continuous and short-circuit current conduction, as well as to
perform switching operations in a current range which does not exceed the rated continuous current of the switch
disconnector.
A switch disconnector is a single-pole appliance, which is composed of a fixed base, movable base, hydro-
cycloaliphatic resin insulators, current busbars, electric arc extinguishing guide bars.
The main contacts of the switch disconnector are made from profiled electrolytic copper flat bars coated with silver
plating. Construction elements are made from St3SY steel and protected against corrosion by hot dip galvanizing.
All movable elements are made from stainless steel.
A switch disconnector can be equipped with a busbar connection.
In open/closed position, the switch disconnector makes a visible and safe isolation gap.

Detailed information on the switch disconnector is presented on www.zpue.com and in the technical
documentation.

Compliance with standards:


The overhead cable switch disconnector RNK-1 complies with the requirements of the PN-EN 50123 norm.

Technical parameters of the switch disconnector


Rated voltage Ur 3,6kV

Rated continuous current Ir 4000A

Rated continuous current 4000A

Rated making current 4000A

Short-circuit current 50kA

Short-circuit current 0,2s

Operation temperature -25 up to +40°C

Mechanical class of the switch disconnector M2

Electrical class of the switch disconnector Minimum 15 switches of the rated current

www.zpue.com 39
MV overhead connectors
8 / Motor drive for remote controlling in Smart
Grid systems

CONSTRUCTION

Motor drive type NSP-7/SO-2 and NSP-8 produced by ZPUE are adapted to manipulating by RN and RPN with
rotary movement, instead of used manual drives which functionality is significantly higher than another solutions
applied in energy production. Motor drive casings are made from powder painted aluminium (there i salso
possibility to order casing from stainless steel), drive type NSP-7/SO-2 (requires another controller mounted in
different cabinet).
Drive type NSP-8 can be equipped in any telemechanic controller produced by Mikronika, Apator-Elkomtech,
charger for battery, battery, earth fault indicator.
All drives produced by ZPUE are compatibile with all dispatechers systems: Wind-ex; Syndis; NetMan-Radius;
SEN-CZAT.

Motor drives T1 and T2 are dedicated only for disconnectors type THO- description in subsection
„Disconnectors: sectionalizers” THO in closed casings for Smart Grid, parameters in table below.

Compliance with standards:

• PN-EN 61439-1:2011 - Low-voltage switchgear and controlgear assemblies - Part 1: General rules;
• PN-EN 60529:2003 - Degrees of protection provided by enclosures (IP code);
• PN-EN 60439-5:2008 - Low-voltage switchgear and controlgear assemblies - Part 1: General rules
concerning sets for energy distribution in public networks
• PN-EN ISO 1461:2011 - Hot Dip Galvanized Coatings on Fabricated iron and steel articles
• PN-EN ISO 12944-2:2001P - Corrosion protection of steel structures by protective paint systems - Part 2:
environments classification
• PN-EN 60529: 2003 - Degrees of protection provided by enclosures (Code IP) and connected standards
• PN-EN 62262:2003 - Degrees Of Protection Provided By Enclosures For Electrical Equipment Against
External Mechanical Impacts (IK Code)
• PN-EN 61140:2005/A1:2008 - Protection against electric shock - Common aspects for installation and
equipment
• PN-EN ISO 12944-2:2001P - Paints and Varnishes - Corrosion protection of steel structures through the use
of painting methods – Part 2: environment classification.

Types of motor drives:

drive type T-1* T-2 NSP-7/SO2 NSP-8 with telemechanic


power suplly voltage 24V DC 24V DC 24V DC 230V AC/ 24V DC
Power of the motor 200W* 160W 330W 400W
Current for start up 6,5A 6,8A 9A 20A
Average time (*) switch on 4-6/
of switch on/ switch off <2s switch off 0,1s <2s <2s

Weigth of drive 23kg 29kg 38,6kg 65kg

* Note
motor drive T1 in new design available for sale from 1.01.2017.

40 www.zpue.com
Motor drive NSP-7/SO2

View from the SO-2 side View from the drive side

1 240
11 12
10 4 3
8
5

390
14

49
6
13 7
6 9
CLOSE
15
OPEN

1 - main shaft 10 - housing door


2 - control cam 11 - door opening indication
3 - limit circuit breaker 12 - drive casing
4 - gearmotor 13 - control panel SO-2
5 - crank 14 - terminal strip with signals conduction
6 - manual drive mechanical interlock 15 - control operation mode
7 - manual drive slot interlock
8 - manual drive slot

OPERATING PRINCIPLE

NSP-7/SO-2 is an electric drive 24V DC equipped with a control panel SO-2.


The drive has a motor for 24 V DC voltage, single-step spur gear and electric control system SO-2.
Switch disconnector maneuvering is performed when the main shaft drive is rotated to a 180° angle. The drive's
construction allows it to be handled from the ground level. The drive has a mechanical operation interlock, which
protects against closing the drive during network operations.

A mechanical interlock allows permanent locking of the switch disconnector in the “OPEN” or “CLOSE” position.
In order to lock the drive, the manual drive slot interlock (7) should be opened. Next insert the hand drive
mechanical interlock (6) in such a way as to fit the interlock lugs with the cut out of the manual drive slot (8), then
close the casing door (10).

www.zpue.com 41
OPERATING PRINCIPLE

Opening of the manual driver slot interlocks causes simultaneous switching off of the drive power supply
thanks to the limit switch activation.
Pulling out the mechanical interlock (6) from the manual drive slot (8) and closing the manual drive slot
interlock (7) causes the release of the lock.
The switch disconnector can be maneuvered remotely or electrically from the control panel SO-2.
On the control cubicle panel are buttons:

“CLOSE” - send an impulse to close switch disconnector;


“OPEN” – send an impulse to open switch disconnector;
The control operation mode (15) is used to choose the way in which to control the switch disconnector:
1. REMOTE –remote control of the connector (radio control)
0. SWITCHED OFF – controlling deactivated
2. connector manoeuvring using buttons on the SO-2 control panel

Detailed information related to the drive is included in the DTR documentation.

Motor drive NSP-8 with telemechanics unit

1 22 21
4 26 7 18 10 24
25
9 12
13

8 11
805

29 27
28
15
19
20
14
550 0 2 3
35 17 16
5

1 - main shaft of the drive 15 - main overcurrent protection with the earthing switch disconnector
2 - espagnolette key to open panels Tytan (2A)
3 - manual drive crank 16 - short circuit indicator SZN-1 (option related to the controller type)
4 - drive casing 17 - temperature regulator
5 - door opening interlock 18 - espagnolette lock to open panels
6 - terminal to ground the drive casing 19 - batteries
7 - control panel SO-2 20 - heater
8 - place for installation of the mechanical interlock 21 - gearmotor
padlock 22 - limit switches of the drive shaft position indication
9 - manual drive slot 23 - optical indicator of the shaft position (by the main shaft 1)
10 - local control buttons (Close / Open) 24 - electrical diagram
11 - control operation mode (Remote/ Deactivated/ 25 - rating plate
Local) 26 - drive power supply circuit breaker 24 V DC
12 - manual drive lever interlock 27 - Plant/PLC controller (depending on the manufacturer)
13 - manual drive interlock lever 28 - place for radio installation
14 - assembly board with the apparatus 29 - lock with the padlock option

42 www.zpue.com
OPERATING PRINCIPLE

Drive NSP-8 is mounted in aluminium casing powder pointed with thermic insulation (can be also made from
stainless steel on special request), in additional it has lock type Master Key with possibility of closing by padlock.
Drive construction enable operation of the drive from ground level. Drive is mounted to the pole that connection
between main shaft of NSP drive and crank of disconnector drive is possible. Bands whoch connect dosconnectros
and drive NSP-8 are delivered with drive set. The drive is equipped with motor and single- step gear and electrical
control system. Disconnector manipulation is making by main drive shaft 180° rotation.
For proper operation, NSP-8 drive requires external power supply 230V with own needs transformer, mounted on
pole station. What's more electrical drive is equipped with controlu unit from Mikronka, Elkomtech, Instytut
Gdańsk. In additiona it can be equipped with earth falut indicator for example SZN-1, SZK-030/B or different type
with exact dimensions. The scheme of connection drive NSP-8, controller and part of mounting plate is shown in
drive Manual. Before making connections, by remote control or control from control box panel, please refer to
manual drive service, specifically with possibility of mechanical interlock of drive, which is decribes in details in
manual.
Disconnector manipulation can be make remotely or electrically from control panel SO-2.
On control panel SO-2 we have buttons (10):
CLOSE- provide impulse for closing the disconnector;
DISCONNECT- providing impulse for opening the disconnector;
Choice of disconnector contro lis realized by control choice switch (11):
1. REMOTE- control by radio
0. SWITCHED OFF- control disabled without possibility of remote or local control
2. LOCAL- manipulation by buttons (10) on control panel SO-2

Detail information you can find in manual.

Control cabinets series SO for remote supervision of the connectors in Smart Grid networks.

Cabinets „SO” are dedicated for complex service of remote control switches produced by ZPUE. Cabinet casing
is made from aluminium s powder pointed sheet. In cabinet casing the special drainage and protected by pollution
system is used.
Casing doors have lock type Master Key with possibility of use padlock and interlock which prevents from
accidential closing. Cabinets can be equipped with service socket 230V AC, internal lighting, heater 30W and
extracting ventilator.
In the bottom of the cabinet the metal glands fi 36 and fi 29 are mounted. By these glands the control wires fron
disconnector drive, antennas wire and power from own needs transformer or different supplying sources are
leading on (glands are fitting individually dirong production process).
In cabinets we have mounted poles controllers type Ex-mBEL; SO-52v-21-xxx; USP-120/x and another
available on the market, also communication module which integrating following functions: measuring, protective,
control with motor drives, telemechanic, automated technology, multichanels disturbance recorder as well as for
collecting and processing information about network parameters and occuring events and providing proper
communication wiyh SCADA system.
Detailed functional description of controllers and communication modules you can find in separated documents
which can be shared by ZPUE S.A. on client request.

Control cabinets SO parameters

Rated voltage of the altering current power supply 230VAC


Rated voltage of the internal systems power supply 24/12VDC
Degree of protection IP54*
Ambient temperature range -40°C +60°C
Possibility to install transmission modules GPRS/TETRA/NET-MAN/TRUNKING
Unladen mass 35-50kg*
* Self-weight influenced by the equipment variant and the number of operated connectors.

www.zpue.com 43
Compliance with standards:

• PN-EN 62271-1 - High Voltage Switchgear and Control gear – Part 1: Common specifications,
• PN-EN 61439-1:2011 - Low Voltage Switchgear and Control gear – Part 1: General specifications,
• PN-EN 60529:2003 - Degrees of protection provided by enclosures (IP code),
• PN-EN 60439-5:2008 – Low Voltage Switchgear and Control gear – Part 5: Particular
requirements for assemblies for power distribution in public networks,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN ISO 12944-2:2001P – Paints and Varnishes - Corrosion protection of steel structures
through the use of painting methods – Part 2: environment classification,
• PN-EN 60529: 2003 - Degrees of protection provided by enclosures (IP code) and related
standards,
• PN-EN 62262:2003 - Degrees of protection against mechanical damages provided by the
enclosures of the electrical devices (IK code),
• PN-EN 61140:2005/A1:2008 - Protection against electric shock - Common aspects for
installation and equipment,
• PN-EN ISO 12944-2:2001P - Paints and Varnishes - Corrosion protection of steel structures
through the use of painting methods – Part 2: environment classification.

Flow chart of the control cabinet “SO”

Drive control
Capacitive system
voltage
dividers Drive control
system SO-2
(option related
to the THO switch
disconnector)

Communication
with the supervision
Communication
centres for the
Plant/PLC controller
modem Smart Grid networks
with the function of
the short-circuit indication

Ex-mBEL_Bx
or
SO-52v-21-AUT Local switches,
3xU
indication
and control system

Current
transformers 3xI

THO-24 switch
disconnector with
current transformers
and voltage dividers
Power
supply
AKU

Power supply internal power system


230 VAC from
the MV/LV transformer

Control cabinet SO1-THO-T1 Control cabinet SO-5-THO-T2 Control cabinet SO1/2-THO-T1


with the SO-54SR-3xx controller with the Ex-mBEL_xx controller with the SO-52v-21-AUT controller

44 www.zpue.com
MV overhead connectors
9 / Fuse bases

CONSTRUCTION

Fuse bases are composed of the base main frame, MV bushing insulators and a fuse link.

PBNV-24, PBNV-30 overhead bases are designed for fixing WBGNp-17,5 and 24, OWBG-36 fuse links up to 25
A, as well as for connection with secured circuit in overhead switchgears, in particular in pole transformer
substations up to 400 kVA.

PBNW-24 overhead fuse bases are designed for installation of pipe type fuses HH 24/....A, VVC/HH 24/....A up
to 63 A, and to connect with a secured circuit in overhead switchgears, in particular in pole transformer substations
with a transformer more than 400 kVA.

Compliance with standards:


Fuse bases comply with the latest PN-EN standards and have a certificate of conformity from the accredited
body: the Institute of Electrical Engineering in Warsaw.

www.zpue.com 45
Technical parameters of the fuse bases

Rated voltage Ur 24kV 36kV


Isolation lightning impulse test voltage
- Underground and inter-pole 125kV 170kV
- Inter-terminal 145kV 195kV
Rated isolation altering test voltage
- Underground and inter-pole 50kV 70kV
- Inter-terminal 60kV 80kV
Rated frequency 50 Hz
Rated continuous current of the base 250A
(depending on the value of the used link)
Rated continuous currents of the fuse links PBNV-24 (from 2 up to 25A)
PBNW-24 (from 0,5 up to 80A)
Rated interrupting current 6,3kA
Link type Up to PBNV-24 WBGNp-17,5; 24, OWBG-36
Up to PBNW-24 HH 24......A; VVC/HH24......A
Bushing insulator type CH-4-125; ISWN CH-4-170

DESIGNATION

PBNV-24 PBNVo-24/D w I
2 2

3
6
3 6
3 3

1
1

7
5 5

4
4

1 – Bushing insulator 1 – Bushing insulator


2 – fuse link WBGN 2 – fuse link WBGN
3 – current terminal 3 – current terminal
4 – earthing terminal 4 – earthing terminal
5 – assembly element of the base 5 – assembly element of the base
6 – main contacts of the base 6 – main contacts of the base
7 – lightning arrester

PBNW-24
3 2

6 1 – Bushing insulator
2 – fuse link HH
1 3 – current terminal
4 – earthing terminal
5 – assembly element of the base
6 – main contacts of the base

5 4

46 www.zpue.com
MV overhead connectors
10 / Concrete poles and construction of the overhead power lines

SCOPE AND APPLICATION

Prefabricated functional spun concrete or wooden poles are delivered with previously installed constructions,
elements of the overhead connectors' drives, elements for lightning arresters installation, constructions for cable
terminations, required groundings, warning plates, etc.
Connectors should be self assembled on the poles in the construction site in order to avoid damage to the
elements during transfer and transport. Steel constructions are protected against corrosion by hot dip galvanizing
according to the PN-EN ISO 1461 norm. All connecting elements used in the construction assembly, such as bolts
and nuts, are protected against corrosion by hot dip galvanizing. The application of galvanizing for anti-corrosion
protection has been eliminated because of its insufficient durability. Prefabricated concrete poles are made
according to individual projects developed by ZPUE S.A and overhead power line albums adopted by the Polish
Society of Transmission and Distribution of Electricity.

Implementation of the ZKP system in accordance with the EN 1090 norm

In accordance with Regulation (UE) 305/2011 of the European Parliament and of the Council of 9 March 2011
(Construction Products Regulation – CPR), ZPUE is pleased to inform our customers that the Factory Production
Control System was introduced, fulfilling the requirements of the PN-EN 1090 norm within the range of production
of low, medium and high voltage power constructions, and transformer stations.
ZPUE was also examined and found to be a company which performs welding works in “steel supporting
constructions”.
To confirm the implementation, ZPUE has gained certificates from the notified and accredited body TUV
NORD.

www.zpue.com 47
LIST OF DEVELOPMENTS AND ALBUMS WITH CONCRETE POLES
FOR OVERHEAD POWER LINES

• 15-30 kV Overhead power lines with AFL-6 (35-70) cables on E spun concrete poles. Energoprojekt Poznań 1993
P-22505 volume 1-10 LSN/E
• 15-30 kV Overhead power lines with AFL-6 (35-70) cables on EPV spun concrete poles. Energoprojekt Poznań
1992 P-22529 volume 1-7 LSN/V
• Medium voltage overhead power lines with AFL 35-70 cables on PTPIREE spun concrete poles,
• EL-project, Energolinia Poznań 1996 volume 1-8 LSN/P
• 15-20 kV Medium voltage overhead power lines with 70 (50) naked cables on spun concrete poles. Flat cable
line. PTPIREE, Energolinia Poznań 2000 volume 1-8 LSN 50/E
• Medium voltage overhead power lines with AFL 95-240 cables on spun concrete poles Energolinia Poznań 1998
EN-118 volume 1-2 LSN 240/E
• Medium voltage overhead power lines with PAS 50-120 cables on spun concrete poles. Flat and vertical cable
line. Energolinia Poznań 1998 EN-029 volume 1-6 LSN/PAS
• 15-20 kV Medium voltage overhead power lines with 35 (50), 70 (120) insulated cables on spun concrete poles.
Vertical and flat cable line El-project Poznań 1996 volume 1-16 LSNi
• Medium and low voltage overhead insulated lines on wooden and spun concrete poles – dual-voltage PTPIREE
power lines, Energolinia, Elprojekt Poznań 1996 volume 1-7 LSN/LNN
• Medium voltage overhead power lines with AFL 35-70 naked cables on wooden poles. Triangular cable line.
PTPIREE, Energolinia Poznań 2001 volume 1-3 LSNd
• 15-20 kV Medium voltage overhead power lines with semi-insulated cables with cross-sections 50-120mm2 in
flat configuration on PTPIRE spun concrete poles, Elprojekt, Energolinia Poznań 2003 volume 1-8 LSNi 50- 120
• 15-20 kV Medium voltage overhead power lines with AFL 120(70) cables on spun concrete poles El- project
• Poznań 1994 volume 1-4 LSN 120/E Actualisation PTPIREE, El-project Poznań 1998 volume 1-4 LSN 120/E
• Medium voltage overhead power lines on spun concrete poles. Metering points catalogue (accounting) AFL 35-
70 Energolinia Poznań1997 EN-067 volume 1-2 LSN/PR
• 15-20 kV Medium voltage overhead power lines on spun concrete poles. Metering points album. PTPIREE,
Energolinia Poznań 2008 LSN/PR
• 15-20 kV Medium voltage overhead power lines with 35 (50) and 70 mm2 naked cables on spun concrete poles
with radio controlled switch disconnectors. PTPIREE, Elprojekt, Energolinia Poznań 2000 volume 1-3 LSN-os
• 15-20 kV Medium voltage overhead power lines with naked cables in triangular configuration on PTPIREE spun
concrete poles, Energolinia Poznań 2002 volume 1-4 LSN 35(50)
• Medium voltage double track lines with AFL 120 (70) cables on PTPIREE spun concrete poles,
• El-project Poznań 1995 volume 1-3 LSN 2 x 120/E
• Medium voltage overhead double track lines with semi-insulated 2x70-120mm2 cables in vertical configuration
on PTPIREE spun concrete poles, Elprojekt Poznań 2004 volume 1-3 LSNi 2x70-120
• 15-20 kV Medium voltage overhead power lines with unisolated cables in flat configuration 70 and 50mm2 on
single spun concrete poles type E and EM Energolinia Poznań 2007 EN-340 volume 1-3 LSN 70(50)
• 15-30 kV Medium voltage overhead power lines on E, EPV, ŻN, BSW spun concrete poles. Catalogue of the poles
with THO (AFL 35 70)switch disconnectors Energolinia Poznań 1997 EN-097 volume 1 LSN/R
• 15-30 kV Medium voltage overhead power lines on ŻN, BSW concrete poles, E and EPV spun concrete poles, with
unisolated and insulated cables.
15-30 kV Medium voltage overhead power lines with AFL-6 120, 240mm2 cables in flat and triangular
configuration on spun concrete poles Energolinia Poznań EN-316 2010 volume 1-2 LSN 120, 240

48 www.zpue.com
In addition we kindly invite to use catalogues for overhead lines design.

Poles stations with RN and RPN Poles stations with THO disconn- Poles stations with disconnectors
disconnectors with radio control ectors with radio control and cables (TOM I, TOM II)

Catalogue MV overhead lines Catalogue MV overhead lines Overhead battery for conductor
with wires AFL-6 120, 240 mm with disconnectors and cables rail 3kV current PKP with wires
(TOM I) for line AFL-6 120, 240 mm 2x2xAFL-6 240mm + 1xAFL-6
(TOM II) 70mm on concrete poles.

www.zpue.pl 49
EXEMPLARY SOLUTIONS FOR CONCRETE POLES
WITH RADIO CONTROLLED CONNECTORS

Pole ROKe LSN 70(50) Pole ROPp-23(3r) LSN 70(50)


with switch disconnector THO with switch disconnector THO

~3,0 m
~1,6 m

~1,2 m
Pole Or LSN 70(50) Pole Oro LSN 70(50) with recloser THO-RC27
with recloser THO-RC27 and disconnector ON III 24/4 P

50 www.zpue.com
Pole Op-12g(2r) LSN 70(50) Pole RPKr LSN 70(50)
with switch disconnector THO i RN with switch disconnector RN-100A

Pole O-6gr LSN 35(50) Pole ROKp-22(3r) LSN 70(50)


with switch disconnector RPN with switch disconnector 3xRPN
~3,0 m

~3,0 m
~1,7 m

~1,7 m

www.zpue.com 51
EXEMPLARY SOLUTIONS FOR CONCRETE POLES
WITH MANUALLY CONTROLLED CONNECTORS

Pole Kp-21(2go) LSN 70(50) Pole Og(2o) LSN 70(35)

1,4

Pole Op-21(2go) LSN 70(50) Pole OMtg2r LSN 120-240

240 mm2 70 mm2

52 www.zpue.com
Pole Kb(2g0) LSNi 2x70(120) Pole Ko(2g) LSN 70(50)

Pole ROKg(2o) LSN 25(50) Pole ROKp-12go LSN 70(50)

www.zpue.com 53
MV overhead connectors
11 / Spun concrete poles and prefabricated fundaments

SPUN CONCRETE POLES

(The pre-stressed high strength type E and EM concrete poles offered by ZPUE are the highest quality
products, compliant with the standard PN-EN 12843:2008. Use of modern technology of concrete density by
centrifugation method allows us to achieve a high level of density and a smooth surface, which guarantees the
stability and bearing capacity of the spun concrete poles. Concrete compressive strength class minimum
C40/50(C50/60) according to PN-EN206-1:2003.)

CHARACTERISTICS

• Design working life 50 years without the need for maintenance,


• Low water absorption <3,5%, good frost resistance, exposure class XC4, XF2 according to the PN-EN 206-1
norm:
• 2003, confirmed by accredited research body,
• Esthetic design, scratch resistance of the smooth surface,
• Limiting of the amount of land made unavailable for agricultural use
• Possibility to increase the span length, fewer number of poles along 1km of lines,
• Easy foundation in the ground,
Application of one concrete pole instead of expanded spans.

APPLICATION

• Supports for overhead and overhead-cable MV and LV power lines, telecommunication lines, train and tram
lines,
• Various support constructions for general application.

CONCRETE POLES DESIGNATION

E M 12/15

Strength, bearing capacity (kN)


Concrete pole height (m)
Durability > 12 kN
Pre-stressed high strength
type E concrete poles

Legend
L – overall length of the concrete pole
dw – outside diameter of the apex
Dp – outside diameter of the base

54 www.zpue.com
TECHNICAL PARAMETERS OF THE CONCRETE POLE TYPE E
dw
Dimensions
Rupture Strength
Lp. Concrete Strength force Weight [m] [mm]
pole type [kN] [kg] color
[kN] indication

770 mm
L L1 L2 dp dw

170 mm
1 E 6,7/12 12 21,6 850 6,7 6,7 1,5 353 218 Yellow

2 E 7,5/12 12 21,6 980 7,5 6,7 1,5 330 218 Yellow


Blue
3 E 8,2/4,3 4,3 7,7 987 8,2 6,7 1,5 353 218
Black
4 E 8,2/6 6,0 10,8 990 8,2 6,6 1,6 341 218
5 E 8,2/10 10,0 18,0 1100 8,2 6,6 1,6 341 218 Red

6 E 8,2/12 12,0 21,6 1150 8,2 6,6 1,6 341 218 Yellow
Green
7 E 8,2/15 15,0 27,0 1150 8,2 6,6 1,6 341 218
8 E 9/2,5 2,5 4,5 775 9,0 7,4 1,6 308 173 White
Openings 26 for crossbar assembly

9 E 9/4,3 4,3 7,7 845 9,0 7,4 1,6 308 173 Blue

10 E 9/6c 6,0 10,8 845 9,0 7,4 1,6 308 173 Black

11 E 9/6 6,0 10,8 1162 9,0 7,7 1,6 353 218 Black

12 E 9/10 10,0 18,0 1200 9,0 7,2 1,8 353 218 Red

13 E 9/12 12,0 21,6 1224 9,0 7,2 1,8 353 218 Yellow

14 E 9/15 15,0 27,0 1180 9,0 7,2 1,8 353 218 Green

15 E 10,5/2,5 2,5 4,5 988 10,5 8,7 1,8 330 173 White

16 E 10,5/4,3c 4,3 7,7 1048 10,5 8,5 2,0 330 173 Blue

17 E 10,5/4,3 4,3 7,7 1308 10,5 8,5 2,0 375 218 Blue

18 E 10,5/6 c 6,0 10,8 1048 10,5 8,5 2,0 330 173 Black

19 E 10,5/6 6,0 10,8 1308 10,5 8,5 2,0 375 218 Black

20 E 10,5/10 10,0 18,0 1476 10,5 8,3 2,2 375 218 Red

21 E 10,5/12 12,0 21,6 1568 10,5 8,3 2,2 375 218 Yellow

22 E 12/2,5 2,5 4,5 1156 12,0 10,0 2,0 353 173 White

23 E 12/4,3c 4,3 7,7 1298 12,0 9,8 2,2 353 173 Blue

24 E 12/4,3 4,3 7,7 1605 12,0 9,8 2,2 398 218


1

Blue

25 E 12/6c 6,0 10,8 1298 12,0 9,8 2,2 353 173 Black
26 E 12/6 6,0 10,8 1605 12,0 9,8 2,2 398 218 Black
Approximately L

27 E 12/10 10,0 18,0 1822 12,0 9,5 2,5 398 218 Red
L

28 E 12/12 12,0 21,6 1930 12,0 9,5 2,5 398 218 Yellow
29 E 12/15c 15,0 27,0 2090 12,0 9,5 2,5 398 218 Green

30 E 13,5/2,5 2,5 4,5 1668 13,5 11,3 2,2 375 173 White
Marking

31 E 13,5/4,3c 4,3 7,7 1168 13,5 11,1 2,4 375 173 Blue
place

32 E 13,5/4,3 4,3 7,7 1887 13,5 11,1 2,4 420 218 Blue

33 E 13,5/6 6,0 10,8 2047 13,5 11,0 2,5 420 218 Black
34 E 13,5/10 10,0 18,0 2230 13,5 10,8 2,7 420 218 Red
35 E 13,5/12 12,0 21,6 2394 13,5 10,8 2,7 420 218 Yellow
36 E 15/2,5 2,5 4,5 1690 15,0 12,5 2,5 398 173 White
500 mm.

37 E 15/4,3c 4,3 7,7 1913 15,0 12,3 2,7 398 173 Blue
38 E 15/4,3 4,3 7,7 2374 15,0 12,3 2,7 443 218 Blue
39 E 15/6 6,0 10,8 2379 15,0 12,2 2,8 443 218 Black
40 E 15/10 10,0 18,0 2657 15,0 12,0 3,0 443 218 Red
41 E 15/12 12,0 21,6 2809 15,0 12,0 3,0 443 218 Yellow

TECHNICAL
PARAMETRY PARAMETERS
TECHNICZNEOFŻERDZI
THE CONCRETE
typu E M POLE TYPE EM
40 ventilation or for

Dimensions
Rupture Rupture Strength
Lp. Concrete force force Weight [m] [mm] color
[kg]
3500 mm.

pole type [kN] [kg] indication


L L1 L2 Dp dw
1 EM 10,5/15 15,0 27,0 1875 10,5 8,3 2,2 420 263 Green

2 EM 10,5/17,5 17,5 31,5 1907 10,5 8,3 2,2 420 263 Orange
2

3 EM 10,5/20 20,0 36,0 1991 10,5 8,3 2,2 420 263 Brown
Cooperage
Approximately L

4 EM 10,5/25 25,0 45,0 2082 10,5 8,3 2,2 420 263 Purple

5 EM 12/15 15,0 27,0 2225 12,0 9,5 2,5 443 263 Green
Opening

6 EM 12/17,5 17,5 31,5 2383 12,0 9,5 2,5 443 263 Orange

7 EM 12/20 20,0 36,0 2492 12,0 9,5 2,5 443 263 Brown

8 EM 12/25 25,0 45,0 2518 12,0 9,5 2,5 443 263 Purple

9 EM 13,5/15 15,0 27,0 2841 13,5 10,8 2,7 465 263 Green

10 EM 13,5/17,5 17,5 31,5 2893 13,5 10,8 2,7 465 263 Orange

11 EM 13,5/20 20,0 36,0 3042 13,5 10,8 2,7 465 263 Brown

12 EM 13,5/25 25,0 45,0 3086 13,5 10,8 2,7 465 263 Purple

13 EM 15/15 15,0 27,0 3131 15,0 12,0 3,0 488 263 Green
Dp 14 EM 15/17,5 17,5 31,5 3131 15,0 12,0 3,0 488 263 Orange

15 EM 15/20 20,0 36,0 3225 15,0 12,0 3,0 488 263 Brown

16 EM 15/25 25,0 45,0 3225 15,0 12,0 3,0 488 263 Purple

www.zpue.com 55
SPUN CONCRETE POLES WITH EARTHING

The pre-stressed high strength type E and EMU concrete poles offered by ZPUE are the highest quality
products, compliant with the standard PN-EN 12843:2008. Use of modern technology of concrete density by the
centrifugation method allows us to achieve a high level of density and smooth surface, which guarantees stability
and bearing capacity of the spun concrete poles. Concrete compressive strength class minimum C40/50(C50/60)
according to PN-EN206-1:2003.

ADVANTAGES OF NETWOEK SOLUTIONS ON SPUN CONCRETE POLES

• Design working life 50 years without the need for maintenance,


• Low water absorption <3,5%, good frost resistance, exposure class XC4, XF2 according to PN-EN 206-1 norm:
2003, confirmed by accredited research body,
• Esthetic design, scratch resistance of the smooth surface,
• Limiting of the amount of land made unavailable for agricultural use
• Possibility to increase of the span length, fewer number of poles along 1km of lines,
• Easy foundation in the ground,
• Application of one concrete pole instead of expanded spans,
• Grounding terminal allows connection, for example: with a crossbar with inside grounding (which is not a load
transferring element),
• No need to place grounding steel tape on the surface of the pole

APPLICATION

• Supports for overhead and overhead-cable MV and LV power lines, telecommunication lines, train and tram
lines,
Various support constructions for general application.

CONCRETE POLE DESIGNATION

E M U 12/15

Strength, bearing capacity (kN)


Concrete pole height (m)
Ground terminal (optional)
Durability >12 kN
Pre-stressed high strength
type E concrete pole.

Legend
L - overall length of the concrete pole
dw - outside diameter of the apex
Dp - outside diameter of the base

56 www.zpue.com
dw TECHNICAL PARAMETERS OF THE CONCRETE POLE TYPE E AND EU
Dimensions
Lp. Rupture [m] [mm] Strength
Concrete Strength force Weight
pole type [kN] [kg] colour

770 mm
[kN] indication
L L1 L2 dp dw

170 mm
1 EU 6,7/12 12 21,6 850 6,7 6,7 1,5 353 218 Yellow

1300 mm
2 EU 7,5/12 12 21,6 980 7,5 6,7 1,5 330 218 Yellow
3 EU 8,2/4,3 4,3 7,7 987 8,2 6,7 1,5 353 218 Blue

4 EU 8,2/6 6,0 10,8 990 8,2 6,6 1,6 341 218 Black

5 EU 8,2/10 10,0 18,0 1100 8,2 6,6 1,6 341 218 Red

6 EU 8,2/12 12,0 21,6 1150 8,2 6,6 1,6 341 218 Yellow

7 EU 8,2/15 15,0 27,0 1150 8,2 6,6 1,6 341 218 Green
Openings 26 for crossbar assembly

8 EU 9/2,5 2,5 4,5 775 9,0 7,4 1,6 308 173 White
9 EU 9/4,3 4,3 7,7 845 9,0 7,4 1,6 308 173 Blue
10 EU 9/6c 6,0 10,8 845 9,0 7,4 1,6 308 173 Black
Ground terminal

11 EU 9/6 6,0 10,8 1162 9,0 7,7 1,6 353 218 Black
12 EU 9/10 10,0 18,0 1200 9,0 7,2 1,8 353 218 Red

13 EU 9/12 12,0 21,6 1224 9,0 7,2 1,8 353 218 Yellow
(A)

14 EU 9/15 15,0 27,0 1180 9,0 7,2 1,8 353 218 Green

15 EU 10,5/2,5 2,5 4,5 988 10,5 8,7 1,8 330 173 White
16 EU 10,5/4,3c 4,3 7,7 1048 10,5 8,5 2,0 330 173 Blue

17 EU 10,5/4,3 4,3 7,7 1308 10,5 8,5 2,0 375 218 Blue

18 EU 10,5/6 c 6,0 10,8 1048 10,5 8,5 2,0 330 173 Black

19 EU 10,5/6 6,0 10,8 1308 10,5 8,5 2,0 375 218 Black

20 EU 10,5/10 10,0 18,0 1476 10,5 8,3 2,2 375 218 Red

21 EU 10,5/12 12,0 21,6 1568 10,5 8,3 2,2 375 218 Yellow
1

22 EU 12/2,5 2,5 4,5 1156 12,0 10,0 2,0 353 173 White
Approximately L

23 EU 12/4,3c 4,3 7,7 1298 12,0 9,8 2,2 353 173 Blue

24 EU 12/4,3 4,3 7,7 1605 12,0 9,8 2,2 398 218 Blue
L

25 EU 12/6c 6,0 10,8 1298 12,0 9,8 2,2 353 173 Black

26 EU 12/6 6,0 10,8 1605 12,0 9,8 2,2 398 218 Black
Marking
Ground terminal

27 EU 12/10 10,0 18,0 1822 12,0 9,5 2,5 398 218 Red
place

28 EU 12/12 12,0 21,6 1930 12,0 9,5 2,5 398 218 Yellow

29 EU 12/15c 15,0 27,0 2090 12,0 9,5 2,5 398 218 Green
(A)

30 EU 13,5/2,5 2,5 4,5 1668 13,5 11,3 2,2 375 173 White

31 EU 13,5/4,3c 4,3 7,7 1168 13,5 11,1 2,4 375 173 Blue

32 EU 13,5/4,3 4,3 7,7 1887 13,5 11,1 2,4 420 218 Blue
500 mm

33 EU 13,5/6 6,0 10,8 2047 13,5 11,0 2,5 420 218 Black

34 EU 13,5/10 10,0 18,0 2230 13,5 10,8 2,7 420 218 Red

35 EU 13,5/12 12,0 21,6 2394 13,5 10,8 2,7 420 218 Yellow

36 EU 15/2,5 2,5 4,5 1690 15,0 12,5 2,5 398 173 White

37 EU 15/4,3c 4,3 7,7 1913 15,0 12,3 2,7 398 173 Blue

38 EU 15/4,3 4,3 7,7 2374 15,0 12,3 2,7 443 218 Blue

39 EU 15/6 6,0 10,8 2379 15,0 12,2 2,8 443 218 Black
40 ventilation or for

40 EU 15/10 10,0 18,0 2657 15,0 12,0 3,0 443 218 Red

41 EU 15/12 12,0 21,6 2809 15,0 12,0 3,0 443 218 Yellow
3500 mm
3600 mm

TECHNICAL PARAMETERS OF THE CONCRETE POLE TYPE EM AND EMU


Approximately L2

Dimensions
Rupture Rupture Strength
Cooperage

Lp. Concrete force force Weight [m] [mm] colour


pole type [kg]
Opening

[kN] [kg] indication


L L1 L2 Dp dw
1 EMU 10,5/15 15,0 27,0 1875 10,5 8,3 2,2 420 263 Green

2 EMU 10,5/17,5 17,5 31,5 1907 10,5 8,3 2,2 420 263 Orange

3 EMU 10,5/20 20,0 36,0 1991 10,5 8,3 2,2 420 263 Brown

4 EMU 10,5/25 25,0 45,0 2082 10,5 8,3 2,2 420 263 Purple

5 EMU 12/15 15,0 27,0 2225 12,0 9,5 2,5 443 263 Green

Dp 6 EMU 12/17,5 17,5 31,5 2383 12,0 9,5 2,5 443 263 Orange

7 EMU 12/20 20,0 36,0 2492 12,0 9,5 2,5 443 263 Brown

8 EMU 12/25 25,0 45,0 2518 12,0 9,5 2,5 443 263 Purple
M10x25 9 EMU 13,5/15 15,0 27,0 2841 13,5 10,8 2,7 465 263 Green

10 EMU 13,5/17,5 17,5 31,5 2893 13,5 10,8 2,7 465 263 Orange
26

11 EMU 13,5/20 20,0 36,0 3042 13,5 10,8 2,7 465 263 Brown

263 Purple
12 EMU 13,5/25 25,0 45,0 3086 13,5 10,8 2,7 465
13 EMU 15/15 15,0 27,0 3131 15,0 12,0 3,0 488 263 Green
detail (A)
14 EMU 15/17,5 17,5 31,5 3131 15,0 12,0 3,0 488 263 Orange
earthing terminal
15 EMU 15/20 20,0 36,0 3225 15,0 12,0 3,0 488 263 Brown

16 EMU 15/25 25,0 45,0 3225 15,0 12,0 3,0 488 263 Purple

www.zpue.com 57
PREFABRICATED FOOTING ELEMENTS

Precast concrete is designed for concrete poles and transformer stations foundations in MV and LV overhead
networks. Concrete prefabricated footing and fundament elements are made from concrete class C 30/35. Footing
elements should be chosen based on PTPIREE albums and assessment of the ground parameters according to the
regulations defined in PN-81/B-03020 and PN-80/B-03322 norms.

List of footings and fundaments

Lp. Footing type Type Footing elements


Plate U - 85
1 Footing plates UP 1 - 7 Plate U - 130
Alloyed plate 0,3 x 0,3
Bracket OU-1, OU-2, OU-6/VE

Plate U - 85
Plate U - 130
2 Footing plates UP 11 - 18
Element ES-2
Alloyed plate 0,3 x 0,3
Block B - 60
Block B - 80
3 Footing blocks To the concrete pole Block B - 90
ŻN and BSW Block B - 150

SFP 111, 122, 133 Bottom plate PD


Plate PS 120
Prefabricated SFP 21/L, 22/L, 23/L Plate PS 160
4
fundaments SP 1, 2, 3 Plate PS 200
SP 11, 22, 33 Screw connections SFP 2 /L
Element EF
Plate P - 120
5 Prefabricated FP 11, 12, 13 Plate P - 160
fundaments FP 21, 22, 23 Plate P - 200
Assembly bolts

Element
Element Symbol of a weight
name the element [cm] Element sketch
[kg]

P - 120 120 675


FOOTING PLATE

P - 160 160 900

P - 200 200 1125

58 www.zpue.com
Element
Element Symbol of a weight Element sketch
name the element [cm] [kg]

PS - 120 120 400

PS - 160 160 530

PS - 200 200 660

U - 85 77
FOOTING BLOCKS

U - 130 156

Płyta
denna 510
PD

www.zpue.com 59
Element Symbol of Element sketch
weight the element
[kg]

B - 60 23

B - 80 38
FOOTING BLOCKS

B - 90 72

B - 150 120
FOOTING ELEMENTS

EF 1060

60 www.zpue.com
NOTE

www.zpue.com 61
NOTE

62 www.zpue.com