MV and LV Overhead Connectors 2017
MV and LV Overhead Connectors 2017
• PN-EN 62271-103:2011 – “High Voltage Switchgear and Control gear – Part 103: Disconnectors with rated
voltages above 1 kV and up to and including 52 kV”,
• PN-EN 62271-1:2009+A1:2011 - “High Voltage Switchgear and Control gear – Part 1: Common
specifications”,
• PN-EN 62271-102:2005; PN-EN 62271-102 :2005/A1:2011 - “High Voltage Switchgear and Control
gear – Part 102: High voltage altering current disconnectors and grounding switches”,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN 61140:2005/A1 - Protection against electric shock. Common aspects for installation and equipment.
Switch disconnectors have a certificate of conformity from the accredited body: the Institute of
Electrical Engineering in Warsaw.
www.zpue.com 25
VIEW, DIMENSIONS AND CONSTRUCTION
6 7
1000 450
4 8
10
11
700
3 2
800
5
9
380 1
710 1700
Load break interrupter view – switch disconnector closed Load break interrupter view – switch disconnector opened
26 www.zpue.com
MV overhead connectors
6 / Connectors with limited connection capability 25 A
in frame and modular version
frame version
CONSTRUCTION
Connectors are three-pole appliances with one drive. Each pole is equipped with two supporting insulators –
fixed or movable. Connectors can be equipped with porcelain, composite insulators with cycloaliphatic resin or
silicone in an HTV rubber cover. Handles with main contacts are installed to the insulators. The main contacts are
made from tinning coated, profiled copper flat bars. The construction of the contacts allows their self-guidance,
and provides a large contact surface and clamping force.
Appliances, as standard, are equipped with current terminals, which allow the installation of isolated or naked
aluminum electricity cables with a cross-section of 16-95 mm2 (a special design allows connecting cables with
a cross-section of 120 mm2). This information must be provided while placing an order or request. Additionally,
appliances with earthing switches are equipped with a flexible contact, which takes over the effects of bending on
a movable appliance pole.
Connectors in the modular structure can be expanded with additional elements such as: lightning arresters,
additional support insulators. They can be installed in the horizontal or vertical position.
www.zpue.com 27
CHARACTERISTICS
Connector parameters RN III 24(36)/4; RUN III 24(36)/4; ON III 24(36)/4; OUN III 24(36)/4
Connector type RUN (RN) RUN (RN) OUN (ON) OUN (ON)
28 www.zpue.com
Compliance with standards:
• PN-EN 62271-103:2011 – “High Voltage Switchgear and Control gear – Part 103: Disconnectors with rated
voltages above 1 kV and up to and including 52 kV”,
• PN-EN 62271-1:2009+A1:2011 - “High Voltage Switchgear and Control gear – Part 1: Common
specifications”,
• PN-EN 62271-102:2005; PN-EN 62271-102 :2005/A1:2011 - “High Voltage Switchgear and Control
gear – Part 102: High voltage altering current disconnectors and earthing switches”,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN 61140:2005/A1 - Protection against electric shock. Common aspects for installation and equipment.
Switch disconnectors and disconnectors have a certificate of conformity from the accredited body:
the Institute of Electrical Engineering in Warsaw.
1000 450
6 11
10
810
910
3 2
5
9
7
8
380 1
710 1700
www.zpue.com 29
VIEW, DIMENSIONS AND CONSTRUCTION OF THE FRAME CONNECTORS
11
6
10
740 (960*)
7 2
3
1
9 8
5
The Connector structure refers to well-known power industry solutions, which have been in use for many years
now. A modified contact system allows the transmission and switching capability to be increased. The application
of silicone drive insulators eliminates the risk of damage to this element. The main shaft interlock prevents faulty
switching operations and considerably improves the handling safety of the appliance. Connectors can be equipped
with porcelain, composite insulators with cycloaliphatic resin or silicone in an HTV rubber cover. Contact elements
applied from our production units guarantees the proper electrical and mechanical operation of the appliance.
Appliances are designed to power lines with considerable cable cross-sections up to 240 mm2, overhead
switchgear busbar bridges and stations 110 kV/15 – 24 – 36 kV and for cable trays. Standard hand drives
manufactured by ZPUE S.A. are used to control the connectors.
5 7
2
9 11
30 www.zpue.com
1
1020 (1080*)
8
www.zpue.com 31
CONNECTORS WITH LIMITED CONNECTION CAPABILITY 25 A
IN FRAME AND MODULAR VERSION
- - -
V – operates in a vertical position 24 kV*
H – operates in a horizontal position *
Rated voltage 24 kV
36 kV
Overhead
ON III 24/4 P
Stands for an overhead, three-pole disconnector for the rated voltage 24 kV and rated continuous current 400 A.
32 www.zpue.com
CONNECTORS DESIGN VARIANTS
Frame connectors
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change of the device's
weight and dimensions.
www.zpue.com 33
CONNECTORS DESIGN VARIANTS
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.
34 www.zpue.com
CONNECTORS DESIGN VARIANTS
Modular connectors with the construction for lightning arresters installation (horizontal)
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Modular connectors with the construction for support insulators installation (horizontal)
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result
in a change of the device's weight and dimensions.
www.zpue.com 35
CONNECTORS DESIGN VARIANTS
Modular connectors with the construction for lightning arresters installation (vertical)
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Disconnector Disconnector
ON III 24/4 with the
o W-S(K)(P)-V earthing switch
OUN III 24/4
o W-S(K)(P)-V
Modular connectors with the construction for support insulators installation (vertical)
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result
in a change of the device's weight and dimensions.
36 www.zpue.com
CONNECTORS DESIGN VARIANTS
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Modular connectors with the construction for lightning arresters installation (horizontal)
Modular connectors with the construction for lightning arresters installation (vertical)
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.
www.zpue.com 37
CONNECTORS DESIGN VARIANTS
Appliance type connector drawing and weight Appliance type with the earthing switch connector drawing and weight
Disconnector Disconnector
ON III 36/4 with the
W-S(K)(P)-H earthing switch
OUN III 36/4
W-S(K)(P)-H
Modular connectors for 36 kV with the construction for lightning arresters installation (horizontal)
Disconnector Disconnector
ON III 36/4 with the
o W-S(K)(P)-H earthing switch
OUN III 36/4
o W-S(K)(P)-H
Notice:
The manufacturer reserves the right to make construction modifications at any time, which may result in a change
of the device's weight and dimensions.
38 www.zpue.com
MV overhead connectors
7 / Overhead rail switch disconnector RNK-1
CONSTRUCTION
Switch disconnector RNK-1 is designed for continuous and short-circuit current conduction, as well as to
perform switching operations in a current range which does not exceed the rated continuous current of the switch
disconnector.
A switch disconnector is a single-pole appliance, which is composed of a fixed base, movable base, hydro-
cycloaliphatic resin insulators, current busbars, electric arc extinguishing guide bars.
The main contacts of the switch disconnector are made from profiled electrolytic copper flat bars coated with silver
plating. Construction elements are made from St3SY steel and protected against corrosion by hot dip galvanizing.
All movable elements are made from stainless steel.
A switch disconnector can be equipped with a busbar connection.
In open/closed position, the switch disconnector makes a visible and safe isolation gap.
Detailed information on the switch disconnector is presented on www.zpue.com and in the technical
documentation.
Electrical class of the switch disconnector Minimum 15 switches of the rated current
www.zpue.com 39
MV overhead connectors
8 / Motor drive for remote controlling in Smart
Grid systems
CONSTRUCTION
Motor drive type NSP-7/SO-2 and NSP-8 produced by ZPUE are adapted to manipulating by RN and RPN with
rotary movement, instead of used manual drives which functionality is significantly higher than another solutions
applied in energy production. Motor drive casings are made from powder painted aluminium (there i salso
possibility to order casing from stainless steel), drive type NSP-7/SO-2 (requires another controller mounted in
different cabinet).
Drive type NSP-8 can be equipped in any telemechanic controller produced by Mikronika, Apator-Elkomtech,
charger for battery, battery, earth fault indicator.
All drives produced by ZPUE are compatibile with all dispatechers systems: Wind-ex; Syndis; NetMan-Radius;
SEN-CZAT.
Motor drives T1 and T2 are dedicated only for disconnectors type THO- description in subsection
„Disconnectors: sectionalizers” THO in closed casings for Smart Grid, parameters in table below.
• PN-EN 61439-1:2011 - Low-voltage switchgear and controlgear assemblies - Part 1: General rules;
• PN-EN 60529:2003 - Degrees of protection provided by enclosures (IP code);
• PN-EN 60439-5:2008 - Low-voltage switchgear and controlgear assemblies - Part 1: General rules
concerning sets for energy distribution in public networks
• PN-EN ISO 1461:2011 - Hot Dip Galvanized Coatings on Fabricated iron and steel articles
• PN-EN ISO 12944-2:2001P - Corrosion protection of steel structures by protective paint systems - Part 2:
environments classification
• PN-EN 60529: 2003 - Degrees of protection provided by enclosures (Code IP) and connected standards
• PN-EN 62262:2003 - Degrees Of Protection Provided By Enclosures For Electrical Equipment Against
External Mechanical Impacts (IK Code)
• PN-EN 61140:2005/A1:2008 - Protection against electric shock - Common aspects for installation and
equipment
• PN-EN ISO 12944-2:2001P - Paints and Varnishes - Corrosion protection of steel structures through the use
of painting methods – Part 2: environment classification.
* Note
motor drive T1 in new design available for sale from 1.01.2017.
40 www.zpue.com
Motor drive NSP-7/SO2
View from the SO-2 side View from the drive side
1 240
11 12
10 4 3
8
5
390
14
49
6
13 7
6 9
CLOSE
15
OPEN
OPERATING PRINCIPLE
A mechanical interlock allows permanent locking of the switch disconnector in the “OPEN” or “CLOSE” position.
In order to lock the drive, the manual drive slot interlock (7) should be opened. Next insert the hand drive
mechanical interlock (6) in such a way as to fit the interlock lugs with the cut out of the manual drive slot (8), then
close the casing door (10).
www.zpue.com 41
OPERATING PRINCIPLE
Opening of the manual driver slot interlocks causes simultaneous switching off of the drive power supply
thanks to the limit switch activation.
Pulling out the mechanical interlock (6) from the manual drive slot (8) and closing the manual drive slot
interlock (7) causes the release of the lock.
The switch disconnector can be maneuvered remotely or electrically from the control panel SO-2.
On the control cubicle panel are buttons:
1 22 21
4 26 7 18 10 24
25
9 12
13
8 11
805
29 27
28
15
19
20
14
550 0 2 3
35 17 16
5
1 - main shaft of the drive 15 - main overcurrent protection with the earthing switch disconnector
2 - espagnolette key to open panels Tytan (2A)
3 - manual drive crank 16 - short circuit indicator SZN-1 (option related to the controller type)
4 - drive casing 17 - temperature regulator
5 - door opening interlock 18 - espagnolette lock to open panels
6 - terminal to ground the drive casing 19 - batteries
7 - control panel SO-2 20 - heater
8 - place for installation of the mechanical interlock 21 - gearmotor
padlock 22 - limit switches of the drive shaft position indication
9 - manual drive slot 23 - optical indicator of the shaft position (by the main shaft 1)
10 - local control buttons (Close / Open) 24 - electrical diagram
11 - control operation mode (Remote/ Deactivated/ 25 - rating plate
Local) 26 - drive power supply circuit breaker 24 V DC
12 - manual drive lever interlock 27 - Plant/PLC controller (depending on the manufacturer)
13 - manual drive interlock lever 28 - place for radio installation
14 - assembly board with the apparatus 29 - lock with the padlock option
42 www.zpue.com
OPERATING PRINCIPLE
Drive NSP-8 is mounted in aluminium casing powder pointed with thermic insulation (can be also made from
stainless steel on special request), in additional it has lock type Master Key with possibility of closing by padlock.
Drive construction enable operation of the drive from ground level. Drive is mounted to the pole that connection
between main shaft of NSP drive and crank of disconnector drive is possible. Bands whoch connect dosconnectros
and drive NSP-8 are delivered with drive set. The drive is equipped with motor and single- step gear and electrical
control system. Disconnector manipulation is making by main drive shaft 180° rotation.
For proper operation, NSP-8 drive requires external power supply 230V with own needs transformer, mounted on
pole station. What's more electrical drive is equipped with controlu unit from Mikronka, Elkomtech, Instytut
Gdańsk. In additiona it can be equipped with earth falut indicator for example SZN-1, SZK-030/B or different type
with exact dimensions. The scheme of connection drive NSP-8, controller and part of mounting plate is shown in
drive Manual. Before making connections, by remote control or control from control box panel, please refer to
manual drive service, specifically with possibility of mechanical interlock of drive, which is decribes in details in
manual.
Disconnector manipulation can be make remotely or electrically from control panel SO-2.
On control panel SO-2 we have buttons (10):
CLOSE- provide impulse for closing the disconnector;
DISCONNECT- providing impulse for opening the disconnector;
Choice of disconnector contro lis realized by control choice switch (11):
1. REMOTE- control by radio
0. SWITCHED OFF- control disabled without possibility of remote or local control
2. LOCAL- manipulation by buttons (10) on control panel SO-2
Control cabinets series SO for remote supervision of the connectors in Smart Grid networks.
Cabinets „SO” are dedicated for complex service of remote control switches produced by ZPUE. Cabinet casing
is made from aluminium s powder pointed sheet. In cabinet casing the special drainage and protected by pollution
system is used.
Casing doors have lock type Master Key with possibility of use padlock and interlock which prevents from
accidential closing. Cabinets can be equipped with service socket 230V AC, internal lighting, heater 30W and
extracting ventilator.
In the bottom of the cabinet the metal glands fi 36 and fi 29 are mounted. By these glands the control wires fron
disconnector drive, antennas wire and power from own needs transformer or different supplying sources are
leading on (glands are fitting individually dirong production process).
In cabinets we have mounted poles controllers type Ex-mBEL; SO-52v-21-xxx; USP-120/x and another
available on the market, also communication module which integrating following functions: measuring, protective,
control with motor drives, telemechanic, automated technology, multichanels disturbance recorder as well as for
collecting and processing information about network parameters and occuring events and providing proper
communication wiyh SCADA system.
Detailed functional description of controllers and communication modules you can find in separated documents
which can be shared by ZPUE S.A. on client request.
www.zpue.com 43
Compliance with standards:
• PN-EN 62271-1 - High Voltage Switchgear and Control gear – Part 1: Common specifications,
• PN-EN 61439-1:2011 - Low Voltage Switchgear and Control gear – Part 1: General specifications,
• PN-EN 60529:2003 - Degrees of protection provided by enclosures (IP code),
• PN-EN 60439-5:2008 – Low Voltage Switchgear and Control gear – Part 5: Particular
requirements for assemblies for power distribution in public networks,
• PN-EN ISO 1461:2011 - Hot dip galvanized coatings on fabricated iron and steel articles,
• PN-EN ISO 12944-2:2001P – Paints and Varnishes - Corrosion protection of steel structures
through the use of painting methods – Part 2: environment classification,
• PN-EN 60529: 2003 - Degrees of protection provided by enclosures (IP code) and related
standards,
• PN-EN 62262:2003 - Degrees of protection against mechanical damages provided by the
enclosures of the electrical devices (IK code),
• PN-EN 61140:2005/A1:2008 - Protection against electric shock - Common aspects for
installation and equipment,
• PN-EN ISO 12944-2:2001P - Paints and Varnishes - Corrosion protection of steel structures
through the use of painting methods – Part 2: environment classification.
Drive control
Capacitive system
voltage
dividers Drive control
system SO-2
(option related
to the THO switch
disconnector)
Communication
with the supervision
Communication
centres for the
Plant/PLC controller
modem Smart Grid networks
with the function of
the short-circuit indication
Ex-mBEL_Bx
or
SO-52v-21-AUT Local switches,
3xU
indication
and control system
Current
transformers 3xI
THO-24 switch
disconnector with
current transformers
and voltage dividers
Power
supply
AKU
44 www.zpue.com
MV overhead connectors
9 / Fuse bases
CONSTRUCTION
Fuse bases are composed of the base main frame, MV bushing insulators and a fuse link.
PBNV-24, PBNV-30 overhead bases are designed for fixing WBGNp-17,5 and 24, OWBG-36 fuse links up to 25
A, as well as for connection with secured circuit in overhead switchgears, in particular in pole transformer
substations up to 400 kVA.
PBNW-24 overhead fuse bases are designed for installation of pipe type fuses HH 24/....A, VVC/HH 24/....A up
to 63 A, and to connect with a secured circuit in overhead switchgears, in particular in pole transformer substations
with a transformer more than 400 kVA.
www.zpue.com 45
Technical parameters of the fuse bases
DESIGNATION
PBNV-24 PBNVo-24/D w I
2 2
3
6
3 6
3 3
1
1
7
5 5
4
4
PBNW-24
3 2
6 1 – Bushing insulator
2 – fuse link HH
1 3 – current terminal
4 – earthing terminal
5 – assembly element of the base
6 – main contacts of the base
5 4
46 www.zpue.com
MV overhead connectors
10 / Concrete poles and construction of the overhead power lines
Prefabricated functional spun concrete or wooden poles are delivered with previously installed constructions,
elements of the overhead connectors' drives, elements for lightning arresters installation, constructions for cable
terminations, required groundings, warning plates, etc.
Connectors should be self assembled on the poles in the construction site in order to avoid damage to the
elements during transfer and transport. Steel constructions are protected against corrosion by hot dip galvanizing
according to the PN-EN ISO 1461 norm. All connecting elements used in the construction assembly, such as bolts
and nuts, are protected against corrosion by hot dip galvanizing. The application of galvanizing for anti-corrosion
protection has been eliminated because of its insufficient durability. Prefabricated concrete poles are made
according to individual projects developed by ZPUE S.A and overhead power line albums adopted by the Polish
Society of Transmission and Distribution of Electricity.
In accordance with Regulation (UE) 305/2011 of the European Parliament and of the Council of 9 March 2011
(Construction Products Regulation – CPR), ZPUE is pleased to inform our customers that the Factory Production
Control System was introduced, fulfilling the requirements of the PN-EN 1090 norm within the range of production
of low, medium and high voltage power constructions, and transformer stations.
ZPUE was also examined and found to be a company which performs welding works in “steel supporting
constructions”.
To confirm the implementation, ZPUE has gained certificates from the notified and accredited body TUV
NORD.
www.zpue.com 47
LIST OF DEVELOPMENTS AND ALBUMS WITH CONCRETE POLES
FOR OVERHEAD POWER LINES
• 15-30 kV Overhead power lines with AFL-6 (35-70) cables on E spun concrete poles. Energoprojekt Poznań 1993
P-22505 volume 1-10 LSN/E
• 15-30 kV Overhead power lines with AFL-6 (35-70) cables on EPV spun concrete poles. Energoprojekt Poznań
1992 P-22529 volume 1-7 LSN/V
• Medium voltage overhead power lines with AFL 35-70 cables on PTPIREE spun concrete poles,
• EL-project, Energolinia Poznań 1996 volume 1-8 LSN/P
• 15-20 kV Medium voltage overhead power lines with 70 (50) naked cables on spun concrete poles. Flat cable
line. PTPIREE, Energolinia Poznań 2000 volume 1-8 LSN 50/E
• Medium voltage overhead power lines with AFL 95-240 cables on spun concrete poles Energolinia Poznań 1998
EN-118 volume 1-2 LSN 240/E
• Medium voltage overhead power lines with PAS 50-120 cables on spun concrete poles. Flat and vertical cable
line. Energolinia Poznań 1998 EN-029 volume 1-6 LSN/PAS
• 15-20 kV Medium voltage overhead power lines with 35 (50), 70 (120) insulated cables on spun concrete poles.
Vertical and flat cable line El-project Poznań 1996 volume 1-16 LSNi
• Medium and low voltage overhead insulated lines on wooden and spun concrete poles – dual-voltage PTPIREE
power lines, Energolinia, Elprojekt Poznań 1996 volume 1-7 LSN/LNN
• Medium voltage overhead power lines with AFL 35-70 naked cables on wooden poles. Triangular cable line.
PTPIREE, Energolinia Poznań 2001 volume 1-3 LSNd
• 15-20 kV Medium voltage overhead power lines with semi-insulated cables with cross-sections 50-120mm2 in
flat configuration on PTPIRE spun concrete poles, Elprojekt, Energolinia Poznań 2003 volume 1-8 LSNi 50- 120
• 15-20 kV Medium voltage overhead power lines with AFL 120(70) cables on spun concrete poles El- project
• Poznań 1994 volume 1-4 LSN 120/E Actualisation PTPIREE, El-project Poznań 1998 volume 1-4 LSN 120/E
• Medium voltage overhead power lines on spun concrete poles. Metering points catalogue (accounting) AFL 35-
70 Energolinia Poznań1997 EN-067 volume 1-2 LSN/PR
• 15-20 kV Medium voltage overhead power lines on spun concrete poles. Metering points album. PTPIREE,
Energolinia Poznań 2008 LSN/PR
• 15-20 kV Medium voltage overhead power lines with 35 (50) and 70 mm2 naked cables on spun concrete poles
with radio controlled switch disconnectors. PTPIREE, Elprojekt, Energolinia Poznań 2000 volume 1-3 LSN-os
• 15-20 kV Medium voltage overhead power lines with naked cables in triangular configuration on PTPIREE spun
concrete poles, Energolinia Poznań 2002 volume 1-4 LSN 35(50)
• Medium voltage double track lines with AFL 120 (70) cables on PTPIREE spun concrete poles,
• El-project Poznań 1995 volume 1-3 LSN 2 x 120/E
• Medium voltage overhead double track lines with semi-insulated 2x70-120mm2 cables in vertical configuration
on PTPIREE spun concrete poles, Elprojekt Poznań 2004 volume 1-3 LSNi 2x70-120
• 15-20 kV Medium voltage overhead power lines with unisolated cables in flat configuration 70 and 50mm2 on
single spun concrete poles type E and EM Energolinia Poznań 2007 EN-340 volume 1-3 LSN 70(50)
• 15-30 kV Medium voltage overhead power lines on E, EPV, ŻN, BSW spun concrete poles. Catalogue of the poles
with THO (AFL 35 70)switch disconnectors Energolinia Poznań 1997 EN-097 volume 1 LSN/R
• 15-30 kV Medium voltage overhead power lines on ŻN, BSW concrete poles, E and EPV spun concrete poles, with
unisolated and insulated cables.
15-30 kV Medium voltage overhead power lines with AFL-6 120, 240mm2 cables in flat and triangular
configuration on spun concrete poles Energolinia Poznań EN-316 2010 volume 1-2 LSN 120, 240
48 www.zpue.com
In addition we kindly invite to use catalogues for overhead lines design.
Poles stations with RN and RPN Poles stations with THO disconn- Poles stations with disconnectors
disconnectors with radio control ectors with radio control and cables (TOM I, TOM II)
Catalogue MV overhead lines Catalogue MV overhead lines Overhead battery for conductor
with wires AFL-6 120, 240 mm with disconnectors and cables rail 3kV current PKP with wires
(TOM I) for line AFL-6 120, 240 mm 2x2xAFL-6 240mm + 1xAFL-6
(TOM II) 70mm on concrete poles.
www.zpue.pl 49
EXEMPLARY SOLUTIONS FOR CONCRETE POLES
WITH RADIO CONTROLLED CONNECTORS
~3,0 m
~1,6 m
~1,2 m
Pole Or LSN 70(50) Pole Oro LSN 70(50) with recloser THO-RC27
with recloser THO-RC27 and disconnector ON III 24/4 P
50 www.zpue.com
Pole Op-12g(2r) LSN 70(50) Pole RPKr LSN 70(50)
with switch disconnector THO i RN with switch disconnector RN-100A
~3,0 m
~1,7 m
~1,7 m
www.zpue.com 51
EXEMPLARY SOLUTIONS FOR CONCRETE POLES
WITH MANUALLY CONTROLLED CONNECTORS
1,4
52 www.zpue.com
Pole Kb(2g0) LSNi 2x70(120) Pole Ko(2g) LSN 70(50)
www.zpue.com 53
MV overhead connectors
11 / Spun concrete poles and prefabricated fundaments
(The pre-stressed high strength type E and EM concrete poles offered by ZPUE are the highest quality
products, compliant with the standard PN-EN 12843:2008. Use of modern technology of concrete density by
centrifugation method allows us to achieve a high level of density and a smooth surface, which guarantees the
stability and bearing capacity of the spun concrete poles. Concrete compressive strength class minimum
C40/50(C50/60) according to PN-EN206-1:2003.)
CHARACTERISTICS
APPLICATION
• Supports for overhead and overhead-cable MV and LV power lines, telecommunication lines, train and tram
lines,
• Various support constructions for general application.
E M 12/15
Legend
L – overall length of the concrete pole
dw – outside diameter of the apex
Dp – outside diameter of the base
54 www.zpue.com
TECHNICAL PARAMETERS OF THE CONCRETE POLE TYPE E
dw
Dimensions
Rupture Strength
Lp. Concrete Strength force Weight [m] [mm]
pole type [kN] [kg] color
[kN] indication
770 mm
L L1 L2 dp dw
170 mm
1 E 6,7/12 12 21,6 850 6,7 6,7 1,5 353 218 Yellow
6 E 8,2/12 12,0 21,6 1150 8,2 6,6 1,6 341 218 Yellow
Green
7 E 8,2/15 15,0 27,0 1150 8,2 6,6 1,6 341 218
8 E 9/2,5 2,5 4,5 775 9,0 7,4 1,6 308 173 White
Openings 26 for crossbar assembly
9 E 9/4,3 4,3 7,7 845 9,0 7,4 1,6 308 173 Blue
10 E 9/6c 6,0 10,8 845 9,0 7,4 1,6 308 173 Black
11 E 9/6 6,0 10,8 1162 9,0 7,7 1,6 353 218 Black
12 E 9/10 10,0 18,0 1200 9,0 7,2 1,8 353 218 Red
13 E 9/12 12,0 21,6 1224 9,0 7,2 1,8 353 218 Yellow
14 E 9/15 15,0 27,0 1180 9,0 7,2 1,8 353 218 Green
15 E 10,5/2,5 2,5 4,5 988 10,5 8,7 1,8 330 173 White
16 E 10,5/4,3c 4,3 7,7 1048 10,5 8,5 2,0 330 173 Blue
17 E 10,5/4,3 4,3 7,7 1308 10,5 8,5 2,0 375 218 Blue
18 E 10,5/6 c 6,0 10,8 1048 10,5 8,5 2,0 330 173 Black
19 E 10,5/6 6,0 10,8 1308 10,5 8,5 2,0 375 218 Black
20 E 10,5/10 10,0 18,0 1476 10,5 8,3 2,2 375 218 Red
21 E 10,5/12 12,0 21,6 1568 10,5 8,3 2,2 375 218 Yellow
22 E 12/2,5 2,5 4,5 1156 12,0 10,0 2,0 353 173 White
23 E 12/4,3c 4,3 7,7 1298 12,0 9,8 2,2 353 173 Blue
Blue
25 E 12/6c 6,0 10,8 1298 12,0 9,8 2,2 353 173 Black
26 E 12/6 6,0 10,8 1605 12,0 9,8 2,2 398 218 Black
Approximately L
27 E 12/10 10,0 18,0 1822 12,0 9,5 2,5 398 218 Red
L
28 E 12/12 12,0 21,6 1930 12,0 9,5 2,5 398 218 Yellow
29 E 12/15c 15,0 27,0 2090 12,0 9,5 2,5 398 218 Green
30 E 13,5/2,5 2,5 4,5 1668 13,5 11,3 2,2 375 173 White
Marking
31 E 13,5/4,3c 4,3 7,7 1168 13,5 11,1 2,4 375 173 Blue
place
32 E 13,5/4,3 4,3 7,7 1887 13,5 11,1 2,4 420 218 Blue
33 E 13,5/6 6,0 10,8 2047 13,5 11,0 2,5 420 218 Black
34 E 13,5/10 10,0 18,0 2230 13,5 10,8 2,7 420 218 Red
35 E 13,5/12 12,0 21,6 2394 13,5 10,8 2,7 420 218 Yellow
36 E 15/2,5 2,5 4,5 1690 15,0 12,5 2,5 398 173 White
500 mm.
37 E 15/4,3c 4,3 7,7 1913 15,0 12,3 2,7 398 173 Blue
38 E 15/4,3 4,3 7,7 2374 15,0 12,3 2,7 443 218 Blue
39 E 15/6 6,0 10,8 2379 15,0 12,2 2,8 443 218 Black
40 E 15/10 10,0 18,0 2657 15,0 12,0 3,0 443 218 Red
41 E 15/12 12,0 21,6 2809 15,0 12,0 3,0 443 218 Yellow
TECHNICAL
PARAMETRY PARAMETERS
TECHNICZNEOFŻERDZI
THE CONCRETE
typu E M POLE TYPE EM
40 ventilation or for
Dimensions
Rupture Rupture Strength
Lp. Concrete force force Weight [m] [mm] color
[kg]
3500 mm.
2 EM 10,5/17,5 17,5 31,5 1907 10,5 8,3 2,2 420 263 Orange
2
3 EM 10,5/20 20,0 36,0 1991 10,5 8,3 2,2 420 263 Brown
Cooperage
Approximately L
4 EM 10,5/25 25,0 45,0 2082 10,5 8,3 2,2 420 263 Purple
5 EM 12/15 15,0 27,0 2225 12,0 9,5 2,5 443 263 Green
Opening
6 EM 12/17,5 17,5 31,5 2383 12,0 9,5 2,5 443 263 Orange
7 EM 12/20 20,0 36,0 2492 12,0 9,5 2,5 443 263 Brown
8 EM 12/25 25,0 45,0 2518 12,0 9,5 2,5 443 263 Purple
9 EM 13,5/15 15,0 27,0 2841 13,5 10,8 2,7 465 263 Green
10 EM 13,5/17,5 17,5 31,5 2893 13,5 10,8 2,7 465 263 Orange
11 EM 13,5/20 20,0 36,0 3042 13,5 10,8 2,7 465 263 Brown
12 EM 13,5/25 25,0 45,0 3086 13,5 10,8 2,7 465 263 Purple
13 EM 15/15 15,0 27,0 3131 15,0 12,0 3,0 488 263 Green
Dp 14 EM 15/17,5 17,5 31,5 3131 15,0 12,0 3,0 488 263 Orange
15 EM 15/20 20,0 36,0 3225 15,0 12,0 3,0 488 263 Brown
16 EM 15/25 25,0 45,0 3225 15,0 12,0 3,0 488 263 Purple
www.zpue.com 55
SPUN CONCRETE POLES WITH EARTHING
The pre-stressed high strength type E and EMU concrete poles offered by ZPUE are the highest quality
products, compliant with the standard PN-EN 12843:2008. Use of modern technology of concrete density by the
centrifugation method allows us to achieve a high level of density and smooth surface, which guarantees stability
and bearing capacity of the spun concrete poles. Concrete compressive strength class minimum C40/50(C50/60)
according to PN-EN206-1:2003.
APPLICATION
• Supports for overhead and overhead-cable MV and LV power lines, telecommunication lines, train and tram
lines,
Various support constructions for general application.
E M U 12/15
Legend
L - overall length of the concrete pole
dw - outside diameter of the apex
Dp - outside diameter of the base
56 www.zpue.com
dw TECHNICAL PARAMETERS OF THE CONCRETE POLE TYPE E AND EU
Dimensions
Lp. Rupture [m] [mm] Strength
Concrete Strength force Weight
pole type [kN] [kg] colour
770 mm
[kN] indication
L L1 L2 dp dw
170 mm
1 EU 6,7/12 12 21,6 850 6,7 6,7 1,5 353 218 Yellow
1300 mm
2 EU 7,5/12 12 21,6 980 7,5 6,7 1,5 330 218 Yellow
3 EU 8,2/4,3 4,3 7,7 987 8,2 6,7 1,5 353 218 Blue
4 EU 8,2/6 6,0 10,8 990 8,2 6,6 1,6 341 218 Black
5 EU 8,2/10 10,0 18,0 1100 8,2 6,6 1,6 341 218 Red
6 EU 8,2/12 12,0 21,6 1150 8,2 6,6 1,6 341 218 Yellow
7 EU 8,2/15 15,0 27,0 1150 8,2 6,6 1,6 341 218 Green
Openings 26 for crossbar assembly
8 EU 9/2,5 2,5 4,5 775 9,0 7,4 1,6 308 173 White
9 EU 9/4,3 4,3 7,7 845 9,0 7,4 1,6 308 173 Blue
10 EU 9/6c 6,0 10,8 845 9,0 7,4 1,6 308 173 Black
Ground terminal
11 EU 9/6 6,0 10,8 1162 9,0 7,7 1,6 353 218 Black
12 EU 9/10 10,0 18,0 1200 9,0 7,2 1,8 353 218 Red
13 EU 9/12 12,0 21,6 1224 9,0 7,2 1,8 353 218 Yellow
(A)
14 EU 9/15 15,0 27,0 1180 9,0 7,2 1,8 353 218 Green
15 EU 10,5/2,5 2,5 4,5 988 10,5 8,7 1,8 330 173 White
16 EU 10,5/4,3c 4,3 7,7 1048 10,5 8,5 2,0 330 173 Blue
17 EU 10,5/4,3 4,3 7,7 1308 10,5 8,5 2,0 375 218 Blue
18 EU 10,5/6 c 6,0 10,8 1048 10,5 8,5 2,0 330 173 Black
19 EU 10,5/6 6,0 10,8 1308 10,5 8,5 2,0 375 218 Black
20 EU 10,5/10 10,0 18,0 1476 10,5 8,3 2,2 375 218 Red
21 EU 10,5/12 12,0 21,6 1568 10,5 8,3 2,2 375 218 Yellow
1
22 EU 12/2,5 2,5 4,5 1156 12,0 10,0 2,0 353 173 White
Approximately L
23 EU 12/4,3c 4,3 7,7 1298 12,0 9,8 2,2 353 173 Blue
24 EU 12/4,3 4,3 7,7 1605 12,0 9,8 2,2 398 218 Blue
L
25 EU 12/6c 6,0 10,8 1298 12,0 9,8 2,2 353 173 Black
26 EU 12/6 6,0 10,8 1605 12,0 9,8 2,2 398 218 Black
Marking
Ground terminal
27 EU 12/10 10,0 18,0 1822 12,0 9,5 2,5 398 218 Red
place
28 EU 12/12 12,0 21,6 1930 12,0 9,5 2,5 398 218 Yellow
29 EU 12/15c 15,0 27,0 2090 12,0 9,5 2,5 398 218 Green
(A)
30 EU 13,5/2,5 2,5 4,5 1668 13,5 11,3 2,2 375 173 White
31 EU 13,5/4,3c 4,3 7,7 1168 13,5 11,1 2,4 375 173 Blue
32 EU 13,5/4,3 4,3 7,7 1887 13,5 11,1 2,4 420 218 Blue
500 mm
33 EU 13,5/6 6,0 10,8 2047 13,5 11,0 2,5 420 218 Black
34 EU 13,5/10 10,0 18,0 2230 13,5 10,8 2,7 420 218 Red
35 EU 13,5/12 12,0 21,6 2394 13,5 10,8 2,7 420 218 Yellow
36 EU 15/2,5 2,5 4,5 1690 15,0 12,5 2,5 398 173 White
37 EU 15/4,3c 4,3 7,7 1913 15,0 12,3 2,7 398 173 Blue
38 EU 15/4,3 4,3 7,7 2374 15,0 12,3 2,7 443 218 Blue
39 EU 15/6 6,0 10,8 2379 15,0 12,2 2,8 443 218 Black
40 ventilation or for
40 EU 15/10 10,0 18,0 2657 15,0 12,0 3,0 443 218 Red
41 EU 15/12 12,0 21,6 2809 15,0 12,0 3,0 443 218 Yellow
3500 mm
3600 mm
Dimensions
Rupture Rupture Strength
Cooperage
2 EMU 10,5/17,5 17,5 31,5 1907 10,5 8,3 2,2 420 263 Orange
3 EMU 10,5/20 20,0 36,0 1991 10,5 8,3 2,2 420 263 Brown
4 EMU 10,5/25 25,0 45,0 2082 10,5 8,3 2,2 420 263 Purple
5 EMU 12/15 15,0 27,0 2225 12,0 9,5 2,5 443 263 Green
Dp 6 EMU 12/17,5 17,5 31,5 2383 12,0 9,5 2,5 443 263 Orange
7 EMU 12/20 20,0 36,0 2492 12,0 9,5 2,5 443 263 Brown
8 EMU 12/25 25,0 45,0 2518 12,0 9,5 2,5 443 263 Purple
M10x25 9 EMU 13,5/15 15,0 27,0 2841 13,5 10,8 2,7 465 263 Green
10 EMU 13,5/17,5 17,5 31,5 2893 13,5 10,8 2,7 465 263 Orange
26
11 EMU 13,5/20 20,0 36,0 3042 13,5 10,8 2,7 465 263 Brown
263 Purple
12 EMU 13,5/25 25,0 45,0 3086 13,5 10,8 2,7 465
13 EMU 15/15 15,0 27,0 3131 15,0 12,0 3,0 488 263 Green
detail (A)
14 EMU 15/17,5 17,5 31,5 3131 15,0 12,0 3,0 488 263 Orange
earthing terminal
15 EMU 15/20 20,0 36,0 3225 15,0 12,0 3,0 488 263 Brown
16 EMU 15/25 25,0 45,0 3225 15,0 12,0 3,0 488 263 Purple
www.zpue.com 57
PREFABRICATED FOOTING ELEMENTS
Precast concrete is designed for concrete poles and transformer stations foundations in MV and LV overhead
networks. Concrete prefabricated footing and fundament elements are made from concrete class C 30/35. Footing
elements should be chosen based on PTPIREE albums and assessment of the ground parameters according to the
regulations defined in PN-81/B-03020 and PN-80/B-03322 norms.
Plate U - 85
Plate U - 130
2 Footing plates UP 11 - 18
Element ES-2
Alloyed plate 0,3 x 0,3
Block B - 60
Block B - 80
3 Footing blocks To the concrete pole Block B - 90
ŻN and BSW Block B - 150
Element
Element Symbol of a weight
name the element [cm] Element sketch
[kg]
58 www.zpue.com
Element
Element Symbol of a weight Element sketch
name the element [cm] [kg]
U - 85 77
FOOTING BLOCKS
U - 130 156
Płyta
denna 510
PD
www.zpue.com 59
Element Symbol of Element sketch
weight the element
[kg]
B - 60 23
B - 80 38
FOOTING BLOCKS
B - 90 72
B - 150 120
FOOTING ELEMENTS
EF 1060
60 www.zpue.com
NOTE
www.zpue.com 61
NOTE
62 www.zpue.com