Magnetics For Neutral Current Compensation in

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Magnetics for Neutral Current Compensation in

Three-Phase Four-Wire Distribution System


Bhim Singh, Fellow IEEE, P. Jayaprakash, Student Member, IEEE, and D P Kothari, Senior Member
IEEE

current has been researched and some remedial measures have


Abstract— In this paper, a number of methods for neutral also been patented [18-22].
current compensation using magnetics are proposed and these The typical loads in a three-phase four-wire distribution
are compared with reported techniques. The proposed neutral system may be computer loads, lighting ballasts, small rating
current mitigation techniques include a Scott-transformer, T- adjustable speeds drives (ASD) in air conditioners, fans,
connected transformer, star-hexagon transformer and star- refrigerators and other domestic and commercial appliances
polygon transformer designed for mmf (magneto motive force) etc. It has a significant portion of the third harmonic current
balance. These transformer configurations along with the component. The iron-cored inductive ballasts as well as
conventional transformer configurations such as a star-delta electronic ballasts in fluorescent lighting also contribute to
transformer and a zig-zag transformer are analysed, designed, third harmonic currents [23]. Observations on computer power
simulated and verified by developing prototypes. The systems have indicated harmonic neutral currents from zero to
transformers provide a path to the zero sequence fundamental as 1.73 times the phase current in the United States in a survey
well as harmonics currents. Two single phase transformers are [24]. It also revealed that 22.6% of the sites have neutral
required for the proposed Scott- connection and T-connection currents exceeding the full load phase currents and this
where as three single phase transformers are required in other scenario is becoming worst in the recent years due to the
methods. The neutral current compensation schemes using proliferation of such nonlinear single-phase loads. The major
transformers are modeled and simulated using MATLAB with its reason for such excessive neutral current is the proliferation of
Simpower systems (SPS) toolboxes and compared to demonstrate nonlinear loads as well as unbalanced loads in the three-phase
the effectiveness of the proposed transformers. Laboratory four-wire distribution system.
prototypes of the transformers are developed and their test Residential and commercial supply networks show dominant
results are presented to validate the design of transformers for non-linear loads and they are modeled as harmonic voltage
neutral current compensation. sources [25-29]. The excessive neutral currents in the neutral
Index Terms—Neutral Current Compensation, Scott- conductor result in wiring failure due to improper sizing of
transformer, T-connected Transformer, Zig-zag Transformer, neutral conductor. Moreover, excessive neutral to ground
Star/DeltaTransformer, Star/Hexagon Transformer, voltage may appear and this results in the malfunction of
Star/Polygon Transformer. Power Quality, sensitive equipments. The transformer is also overheated due
to harmonic currents and these result in insulation damage and
I. INTRODUCTION failure [25]. Some corrective measures suggested are given
below.
T HREE-PHASE four-wire distribution systems are facing
the severe problem of excessive neutral current and
harmonic neutral current along with other power quality
1. Derating of transformers [24]
2. Over sizing of neutral conductor [24]
3. Use of four-leg active filters [13]
problems such as high reactive power demand, harmonic 4. Use of zig-zag transformers [30-34]
currents and unbalanced loads. There are many standards 5. Use of star/ delta transformer [35-38]
proposed to control the quality of electric supply in the The derating of the transformer leads to low efficiency
distribution system [1-4]. The power quality problems and operation and increased heat due to losses. However, the
their mitigation techniques are reported in the literature over application of the zig-zag transformer or a star/delta
the years [5-17]. The problems related to harmonic neutral transformer for reduction of the neutral current has an
advantage of passive compensation, ruggedness and less
complex.
Bhim Singh is with Dept. of Electrical Engg., Indian Institute of Technology,
In this investigation, some new transformer configurations
Delhi, Hauz-Khas, New Delhi-110016, India (bhimsinghr@gmail.com)
are proposed for neutral current mitigation for three-phase
P Jayaprakash is with Dept. of Electrical Engg., Govt. College of Engg,
Kannur, Kerala, India-670563 (email: jayaprakashpee@gmail.com).
four-wire distribution system. First one is based on a Scott-
D P Kothari is with Vellur Institute of Technology, Vellur, Tamil Nadu, India connected transformer arrangement and the Scott-connected
(email: dpk0710@yahoo.com). windings of the transformer provide a path to the zero
sequence fundamental as well as harmonics currents. There
978-1-4244-7781-4/10/$26.00 ©2010 IEEE are only two single phase transformers required for the
proposed Scott- connection. Some other new configurations
investigated are based on T- connected transformer, star- experimented for compensation of source neutral current.
hexagon transformer and star-polygon transformer. The
magnetic solutions for neutral current compensation are tested III. DESIGN AND MODELING OF MAGNETICS
by simulation using MATLAB software with its Sim power The neutral current compensation techniques using a zig-zag
systems (SPS) toolboxes and then these are verified by
transformer, a star/delta transformer, T-connected transformer,
developing prototypes in the laboratory environment.
Scott-transformer, star-hexagon transformer and star-polygon
transformer are properly designed and modeled to study their
II. NEUTRAL CURRENT MITIGATION TECHNIQUES
effectiveness. The performances of designed transformers are
The magnitude of the neutral current in three-phase four- simulated using the MATLAB software with its Sim power
wire distribution system depends on the harmonic content and systems (SPS) toolboxes. The design and modeling equations
phase unbalance of the load currents. The passive technique are explained below.
for neutral current mitigation involves LC filters, zig-zag
transformers and star / delta transformers [30-38]. But the LC A. Zig-Zag Transformer:
filters are not effective for voltage source type loads [29]. A The connection of the zig-zag transformer and its phasor
phase shifting and zero sequence current filter is patented [18] diagram are shown in Figs. 1(a). Three single phase
and a zig-zag transformer for harmonic neutral current transformers each of rating 1.4kVA, 140/140V are selected.
reduction is also patented in [19].
B. Star-Delta Transformer:
Fig.1 (a) shows a zig-zag transformer connected in parallel
to the load for filtering the zero sequence components of the The connection of the star/delta transformer and its phasor
load. The zig-zag transformer consists of three single phase diagram are shown in Figs. 1(b). The voltage ratio of the
transformers with turns ratio 1:1. It acts as an open circuit for transformer is 1:1. Three numbers of single-phase
positive sequence and negative sequence component of load transformers of each of rating 2.4 kVA, 240V/240V are
currents and the current flowing through the zig-zag selected.
transformer is only the zero sequence components [31]. The C. T-connected Transformer
phasor diagram of the transformer shows that the resultant Fig. 1(c) shows the connection of two single phase
voltages are 120º phase shifted. The zero sequence component transformers for interfacing with a three-phase four-wire
of load currents can be locally circulated using a star/delta system. The T-connected winding of the transformer provides
transformer as shown in Fig. 1(b). The secondary delta a path for the zero sequence fundamental current and
connected winding provides a path for the zero sequence harmonic currents and hence offers a path for the neutral
currents and hence the supply neutral current is reduced to current when connected in shunt at PCC. Under unbalanced
zero. The relative value of a series inductance (Zsn) with loads, the zero sequence load neutral current divides equally
transformer impedance plays a significant role in the into three currents and takes a path through the T-connected
effectiveness of the neutral current compensation [34]. windings of the transformer. The current rating of the
Therefore, the transformers must be installed near the load or windings is decided by the required neutral current
it is required to connect a high value of series inductance. compensation. The voltage across each winding is designed as
In this paper, some new transformer configurations are shown below.
proposed for the neutral current compensation in a three-phase The phasor diagram shown in Fig. 1(c) gives the following
four-wire distribution system. The Scott-Transformer and T-
relations to find the turn’s ratio of windings. Hence, two
connected transformer are used in the power system for
single-phase transformers of rating 2.4 kVA,
different applications [39-41]. The proposed configuration of
240V/120V/120V and 2.1 kVA, 208 V/208 V are selected.
T-connected transformer for neutral current compensation is
shown in Fig. 1(c) and in this two single phase transformers D. Scott-Transformer
are used for neutral current compensation. These single phase The Scott-connected transformer at the PCC provides a path
transformers are connected in T- configuration and it shows
for zero sequence harmonics and fundamental neutral currents.
that the resultant voltages are 120º phase shifted. The
Fig. 1(d) shows the connection of Scott-transformer and its
transformer is simple and the windings are suitably designed
phasor diagram. There are only two single phase transformers
for mmf (magneto motive force) balance. Similarly, a Scott-
transformer is proposed for neutral current compensation and required to get the neutral terminal. In order to obtain the
is shown in Fig. 1 (d) and as compared to earlier T-connected neutral terminal, the voltages across windings of one
transformer, the required numbers of windings are reduced. A transformer, Va1 and Va2 are equal and is equal to Va cos
star-hexagon transformer is reported along with voltage source 30º. Similarly, for the second transformer windings, the
converters as DSTATCOM which also helps in neutral current voltages are Va sin 30º and Va respectively. The current rating
compensation [42]. A star-polygon transformer [43] is depends on the neutral current to be compensated. In proposed
reported for some other application, but it is proposed for scheme, two single phase transformers of 2.1 kVA,
neutral current compensation for the first time in this paper. 207V/207V and 2.4 kVA, 240V/120V are selected for neutral
Similarly, a zig-zag transformer is analysed in detail for zero current compensation.
sequence harmonic compensation in the literature [44]. These
transformer configurations are designed, simulated and then
Fig.1 Schematics of transformer connected system along with phasor diagram of (a) zig-zag transformer (b) star-delta transformer (c) T-connected transformer
(d) Scott-transformer (e) star-hexagon transformer (f) star-polygon transformer.

unbalanced linear/ non-linear loads are observed to study their


E. Star-Hexagon Transformer:
effectiveness. The system data is given in Appendix.
The connection of the star/hexagon transformer and its
phasor diagram are shown in Figs. 1(e). Three numbers of A. Simulated results of zig-zag transformer
single-phase transformers of each of rating 2.6 kVA, 240 Fig. 2 shows the performance of a zig-zag transformer for
V/140V/140V are selected. the neutral current compensation of three-phase four–wire
non-linear balanced/unbalanced loads. The load neutral
F. Star- Polygon Transformer: current (iLn) is observed to be mainly harmonic current and the
The connection of the star/polygon transformer and its current in the supply neutral current (isn) is nearly zero due to
phasor diagram are shown in Figs. 1(f). Three numbers of proper compensation. The kVA rating of the zig-zag
single-phase transformers of each of rating 2.6 kVA, 240V/ transformer is observed to be nearly 4.2 kVA.
203V/75V are selected. B. Simulated results of star/delta transformer
The performance of neutral current compensation of a three-
IV. SIMULATION RESULTS
phase four–wire system using star/delta transformer is shown
The proposed neutral current compensation techniques using in Fig. 3 for non-linear loads. The voltages at PCC (vs), supply
magnetic such as Scott-transformer, T-connected transformer, currents (is), unbalanced load currents (iLa, iLb, iLc), supply
star-hexagon transformer and star-polygon transformer are neutral current (iSn), load neutral current (iln), star/delta
modeled and simulated using MATLAB. These systems are transformer neutral current (iTn), star/delta transformer
modelled along with conventional methods such as zig-zag winding currents (iT) and kVA rating of transformer are
transformer, a star/delta transformer with linear and non-linear demonstrated under varying load conditions. The kVA rating
balanced and unbalanced loads. The performances of neutral of the star/delta transformer is observed to be nearly 7.2 kVA.
current compensation techniques with balanced and
C. Simulated results of T-connected transformer where as the supply neutral current is 0.048 A only as shown
Fig. 4 shows the performance of proposed T-connected in Figs. 8(g), (h) and (i) respectively.
transformer for neutral current compensation of a three-phase The performance of neutral current compensation of a three-
four–wire load. The voltages at PCC (vs), supply currents (is), phase four–wire system using Scott- transformer at linear
unbalanced load currents (iL), supply neutral current (iSn), load loads is shown in Fig. 9. The load currents are shown in Figs.
neutral current (iln), T-connected transformer neutral current 9(a), (b) and (c) respectively and the supply currents are
(iTn), T-connected transformer winding currents (iT) and kVA shown in Figs.9 (d), (e) and (f) respectively. The supply
rating of transformer are demonstrated under varying load neutral current is 0.645 A only where as the load neutral
conditions. The source neutral current is maintained at nearly current is 6.52 A and the transformer neutral current is 5.87 A
zero by providing the compensation of zero sequence as shown in Figs. 9(g), (h) and (i) respectively.
harmonic load neutral currents. The kVA rating of the T- The Scott-transformer winding currents are shown in Figs.
connected transformer is observed to be nearly 4.48 kVA. 9(j), (k) and (l) respectively. It is observed that they are almost
equal and are one-third of the load neutral current. It is
D. Simulated results of Scott-connected transformer observed that the magnitude of the source current is reduced.
The performance of neutral current compensation of three- When the load is nonlinear and balanced, the load neu9l
phase four–wire non-linear loads is carried out using Scott- current is observed to be mainly triplen harmonics current and
transformer and is shown in Fig. 5. The voltages at PCC (vs), this is compensated using the Scott-connected transformer.
supply currents (is), unbalanced load currents (iLa, iLb, iLc),
supply neutral current (iSn), load neutral current (iln), Scott- VI. COMPARISON OF MAGNETIC SCHEMES
transformer neutral current (iTn), Scott- transformer winding A comparison of winding voltages and kVA rating of
currents (iT) and kVA rating of transformer are studied and it different magnetic schemes are shown in Table I. In general,
is observed as same as that of the T-connected transformer. all the transformers are capable of mitigating fundamental as
But the number of winding required is less in Scott- well as harmonic neutral currents. It is observed that the kVA
transformer as compared to a T-connected transformer. rating of zig-zag, T-connected and Scott transformers are
E. Simulated results of star/hexagon transformer lower compared to other schemes. But, the T-connected and
Scott transformers require only two single phase transformers.
The performance of neutral current compensation of a three-
Moreover, Scott-transformer requires less number of windings
phase four–wire system using star/hexagon transformer is
compared to T-connected transformer. It is observed that the
shown in Fig. 6 for non-linear loads. The voltages at PCC (vs),
supply currents (is), unbalanced load currents (iLa, iLb, iLc), application of magnetics mitigates the source neutral current
supply neutral current (iSn), load neutral current (iln), to zero along with the magnitude of source current is reduced
and the THD of source current is also reduced.
transformer neutral current (iTn), transformer currents (iT) and
kVA rating of transformer are demonstrated under varying
load conditions. The kVA rating of the star/hexagon VII. CONCLUSION
transformer is observed to be nearly 7.8 kVA. The neutral current mitigation techniques for a three-phase
four-wire distribution system using magnetics have been
F. Simulated results of star/polygon transformer
demonstrated and some new cost effective method using
The performance of neutral current compensation of a three- transformers have been proposed for neutral current
phase four–wire system using star/polygon transformer is compensation. The proposed neutral current mitigation
shown in Fig.7 for non-linear loads. The voltages at PCC (vs),
supply currents (is), unbalanced load currents (iLa, iLb, iLc),
TABLE I.
supply neutral current (iSn), load neutral current (iln), COMPARISON OF KVA RATING OF TRANSFORMERS USING
star/polygon transformer neutral current (iTn), star/polygon SIMULATION FOR A LOAD KVA OF 21.6 KVA
transformer currents (iT) and kVA rating of transformer are Transformer Winding ITa VA Total
demonstrated under varying load conditions. The kVA rating voltages (A) rating kVA
of the star/delta transformer is observed to be nearly 7.8 kVA. (V) /phase rating
(kVA) (%)
Zig-zag 140/140 10 1.4 4.2
V. EXPERIMENTAL VALIDATION
Transformer (19.4%)
Laboratory prototype of a Scott-transformer is developed Star-delta 240/240 10 2.4 7.2
and is tested at linear and non-linear loads for the neutral transformer (33.3%)
current compensation. Scott- 240/120 10 2.4 4.48
connected 208/208 2.08 (20.7%)
A. Experimental results of Scott-transformer Transformer
The performance of neutral current compensation of a three- T-connected 240/120/120 10 2.4 4.48
phase four–wire system using Scott- transformer is shown in transformer 208/208 2.08 (20.7%)
Fig. 8 at non-linear loads. The load currents are shown in Figs. Star-hexagon 240/140/140 10 2.6 7.80
8(a), (b) and (c) respectively and the supply currents are transformer (36%)
Star-polygon 240/203/75 10 2.6 7.80
shown in Figs. 8(d), (e) and (f) respectively. The load neutral
transformer (36%)
current is 6.78 A and the transformer neutral current is 6.78 A
Fig.2 Performance of Zig-zag transformer for neutral current Fig. 5 Performance of Scott- transformer for neutral current compensation
compensation with nonlinear load with nonlinear

Fig. 3 Performance of star/delta transformer for neutral current Fig. 6. Performance of Star- Polygon transformer for neutral current
compensation with nonlinear load. compensation with nonlinear load.

Fig. 4 Performance of T-connected transformer for neutral current Fig. 7 Performance of Star-Hexagon transformer for neutral current
compensation with nonlinear load. compensation with nonlinear load.

techniques include a Scott-transformer, T-connected transformer and a zig-zag transformer have been analysed,
transformer, star-hexagon transformer and star-polygon designed and simulated. A simple connection of suitably
transformer designed for mmf (magneto motive force) designed windings of Scott- transformer for mmf balance has
balance. These transformer configurations along with the been proposed for neutral current compensation. The
conventional transformer configurations such as a star-delta simulation model of the Scott- transformer has been verified
(a) (b) (c)
(a) (b) (c)

(d) (e) (f)


(d) (e) (f)

(g) (h) (i)


Fig. 8. Neutral current compensation using Scott- transformer for non-linear (g) (h) (i)
load (a) Load current in phase ‘a’ (b)Load current in phase ‘b’ (c) Load
current in phase ‘c’ (d)source current in phase ‘a’ (e) source current in phase
‘b’ (f) source current in phase ‘c’(g) Load neutral current (h) Transformer
neutral current(i) Source neutral current.

by developing a prototype in the laboratory. The Scott-


transformer requires only two single phase transformers and
hence this method is found simple and cost effective
(j) (k) (l)
compared to other methods of neutral current compensation. It
Fig. 9. Neutral current compensation using Scott-transformer for linear load
has been verified that the application of magnetic mitigates the (a) Load current in phase ‘a’ (b) Load current in phase ‘b’ (c) Load current
source neutral current to zero along with the magnitude of in phase ‘c’ (d) Source current in phase ‘a’ (e) Source current in phase ‘b’
source current is reduced and the THD of source current is (f) Source current in phase ‘c’ (g) Source neutral current (h) Transformer
neutral current (i) Load neutral current (j) Transformer current in phase ‘a’
also reduced.
(k), Transformer current in phase ‘b’ (l) Transformer current in phase ‘c’.

VIII. APPENDICES Star/Hexagon Transformer: Three single-phase


transformers of 2.4 kVA, 240 V/140 V/ 140 V each.
A. Supply voltage: Three-phase, four-wire, 415 V (L-L), 50 Star/Polygon Transformer: Three single-phase
Hz transformers of 2.4 kVA, 240 V/203 V/ 75 V each.
Loads: (i) Linear: 20 kVA, 0.80 pf lag
C. Data for Laboratory Prototype
(ii) Non-linear: Three single-phase bridge rectifier
with R = 25 Ω and C = 470μF Supply voltage:Three-phase,four-wire,220 V (L-L), 50
Hz
B. Data for Simulation Loads: (i) Linear: 5 kVA, 0.80 pf lag
Zig-zag Transformer: Three single-phase transformers of (ii) Non-linear: Three single-phase bridge rectifier
1.4 kVA, 140 V/140 V each. with R = 25 Ω and C = 470 μF.
Star/Delta Transformer: Three single-phase transformers Scott-connected Transformer: Two single-phase
of 2.4 kVA, 240 V/240 V each. transformers.
T-connected Transformer: Two single-phase transformers Transformer 1: 2.4 kVA, 120 V/60 V
Transformer 1: 2.4 kVA, 240V/120V/120V Transformer 2: 2.1 kVA, 105 V/105 V
Transformer 2: 2.1 kVA, 208V/208V
Scott-connected Transformer: Two single-phase IX. REFERENCES
transformers • Books/Standards/Patents
Transformer 1: 2.4 kVA, 240V/120V [1] IEEE Recommended Practices and Requirements for Harmonics
Transformer 2: 2.1 kVA, 208V/208V Control in Electric Power Systems, IEEE Std. 519, 1992.
[2] IEEE Recommended Practice for Electric Power Distribution for
Industrial Plants, IEEE Std. 141- 1993.
[3] IEEE Guide for Application and Specification for Harmonic Filters, [30] P. P. Khera, “Application of zig-zag transformers for reducing
IEEE Std.1531, 2003. harmonics in the neutral conductor of low voltage distribution
[4] Electromagnetic Compatibility (EMC) – Part 3: Limits- Section 2: system,” in Proc. of Conf. Industry Applications Society Annual
Limits for harmonic current emissions (equipment input current <16 Meeting, vol. 2, Oct. 1990, pp. 1092.
A per phase), IEC1000-3-2 Document, First Edition, 1995. [31] Sewan Choi and Minsoo Jang, “A Reduced-Rating Hybrid Filter to
[5] G. T. Heydt, Electric Power Quality, 2nd edition, Stars in a Circle, Suppress Neutral Current Harmonics in Three-Phase Four-Wire
West Lafayette, 1994. Systems,” IEEE Trans. Ind. Electron., vol. 51, no. 4, pp. 927-930,
[6] Math H. J. Bollen, Understanding Power Quality Problems: Voltage August 2004.
Sags and Interruptions, IEEE Press Series on Power Engineering, [32] Hurng- Liahng Jou, Jinn- Chang Wu, Kuen- Der Wu, Wen- Jung
New York, 2000. Chiang and Yi- Hsun Chen, “Analysis of zig-zag Transformer
[7] J. Arrilaga, N R Wattson and S. Chen, Power System Quality applying in the three-phase Four- Wire Distribution Power System,”
Assessment, John Wiley & Sons, 2000. IEEE Trans. Power Delivery, vol. 20, no. 2, pp. 1168- 1173, April
[8] C. Sankaran, Power Quality. New York: CRC Press, 2001. 2005.
[9] E.Acha, V.G. Agelidis, O. Anaya-Lara and T.J.E. Miller, Power [33] Sewan Choi and Minsoo Jang, “Analysis and Control of a Single-
Electronic Control in Electric Systems, Newness Power engineering Phase- Inverter- zigzag Transformer Hybrid neutral- current
series, 1st Edition, Oxford, 2002. suppressor in Three-phase Four Wire Systems,” IEEE Trans. Ind.
[10] A.Ghosh and G. Ledwich, Power Quality Enhancement using Custom Elec., vol. 54, no. 4, pp. 2201- 2208, August 2007.
Power Devices, Kluwer Academic Publishers, London, 2002. [34] Hurng- Liahng Jou, Kuen- Der Wu, Jinn- Chang Wu and Wen- Jung
[11] Math H. J. Bollen and Irene Gu, Signal Processing of Power Quality Chiang, “A three-phase four- wire power filter comprising a three-
Disturbances, Wiley-IEEE Press, 2006. phase three-wire active filter and a zig-zag transformer,” IEEE Trans.
[12] R. C. Dugan, M. F. McGranaghan and H. W. Beaty, Electric Power Power Electron., vol. 23, no. 1, pp. 252- 259, January 2008.
Systems Quality. 2ed Edition, McGraw Hill, New York, 2006. • Star/Delta Transformers Based Compensation
[13] K.R. Padiyar, FACTS Controllers in Transmission and Distribution, [35] Sikyung Kim, Prasad N. Enjeti and Ira J. Pitel, “A New approach to
New Age International, New Delhi, 2007. improve power factor and reduce harmonics in a three-phase diode
[14] H. Akagi, E H Watanabe and M Aredes, Instantaneous power theory rectifier type utility interface,” IEEE Trans. Ind. Applicat., vol. 30, no.
and applications to power conditioning, John Wiley & Sons, New 6, pp. 1557- 1564, Nov./ Dec 1994.
Jersey, USA, 2007. [36] P. Enjeti, W. Shireen, P. Packebush and I. Pitel, “Analysis and Design
[15] Antonio Moreno-Munoz, Power Quality: Mitigation Technologies in of a New Active Power Filter to Cancel Neutral Current Harmonics in
a Distributed Environment, Springer-Verlag London limited, London Three-phase Four-Wire Electric Distribution Systems,” IEEE Trans.
2007. Ind. Applicat., vol. 30, no. 6, pp. 1565- 1572, Nov./ Dec. 1994.
[16] Ewald F. Fuchs and Mohammad A. S. Mausoum, Power Quality in [37] Steffan Hansen, Peter Nielsen and Frede Blaabjerg, “Harmonic
Power Systems and Electrical Machines, Elsevier Academic Press, Cancellation by mixing Non-linear single-phase and three-phase
London, UK, 2008. loads,” IEEE Trans. Ind. Applicat., vol.36, no.1, pp.152-159, Jan.
[17] Angelo Baggini, “Handbook on power quality,” John Wiley & Sons, /Feb. 2000.
New Jersey, 2008. [38] P. Vedelho and G D Marques, “A neutral current electronic
compensator,” in Proc. of IEEE Proceedings in Industrial Electronics,
[18] Michael Levin, "Combined phase-shifting directional zero phase
sequence current filter and method for using thereof", US Patent, vol.2, pp.831-836, Aug/Sept 1998.
US5416688, 16th May 1995. • T-connected/Star-hexagon/Star-polygon Transformers
[19] Leon H. Beverly, Richad D. Hance, Alexander L.Kristalinski,Age T. [39] Bell A. Cogbill and John A. Hetrick, “Analysis of T-T connections of
Visser, “Method and apparatus for reducing the harmonic currents in two single phase Transformers,” IEEE Trans. on Power Apparatus
alternating current distribution networks, ” US Patent, 5576942, 19th and Systems, vol.-PAS-87, no.2, Feb.1968.
Nov. 1996. [40] B Singh, V. Garg and G.Bhuvaneswari, “A novel T-Connected
[20] Kevin L. Parker, "Active neutral current compensator", US Patent autotransformer-based 18-Pulse AC–DC converter for harmonic
US5574356, 12th Nov. 1996. mitigation in adjustable-speed induction-motor drives,” IEEE Trans.
[21] Ira J. Pitel and Prasad Enjeti, "Active harmonic power filter apparatus on Industrial Electronics, vol.54, no.5, pp. 2500 – 2511, Oct.2007.
and method", US Patent US5568371, 22nd Oct. 1996. [41] Bhim Singh, P. Jayaprakash and D P Kothari “A T-Connected
[22] Einar Larsen, "Filter for removing harmonic current from a neutral Transformer and Three-Leg VSC Based DSTATCOM for Power
conductor", US Patent, US5914540, 22nd June 1999. Quality Improvement,” IEEE Trans. Power Electronics, vol. 23, no. 6,
pp. 2710-2718, Nov 2008.
• Neutral Current Problems
[42] Bhim Singh, Jayaprakash P and D P Kothari “Three leg VSC with a
[23] Ah-Choy Liew, “Excessive Neutral Currents in Three-Phase
Fluorescent Lighting Circuits,” IEEE Trans. Ind. Applicat., vol.25, star-hexagon transformer based DSTATCOM for power quality
improvement in three-phase four-wire distribution system,”
no.4, pp.776-782, July/August 1989.
International Journal of Emerging Electric Power Systems, vol.9,
[24] Thomas M. Gruzs, “A Survey of Neutral Currents in Three-Phase
Computer Systems,” IEEE Trans. Ind. Appicat., vol.26, no.4, pp. 719- no.8, Article 1, Dec. 2008.
[43] B Singh, S. Gairola, A Chandra and K. Al-Haddad, “Power quality
725, July/August 1990.
improvements in isolated twelve pulse AC-DC converters using
[25] Aintablian, H.O.Hill and H.W. Jr, “Harmonic currents generated by
personal computers and their effects on the distribution system neutral delta/double polygon transformer,” IEEE Power Electronics
Specialists Conference, (PESC ‘07) , June.2007, pp. 2848 - 2853
current,” Conf. IEEE Ind. Appl., vol. 2, pp.1483-1495, Oct. 1993.
[26] H. Aintabilan, “The harmonic currents of commercial office buildings [44] F.N. Belchior, J.F.V. Ferreira, J.C. Oliveira, R. Apolonio and A.B.
due to non- linear electronic equipment,” in Proc. of IEEE South Vasconcellos, “Three-phase electromagnetic filter for zero-sequence
harmonics,” IEEE Trans. Magnetics, Vol. 42, pp.2201 –2207,
Conf., June 1996, pp. 610- 615.
[27] E. Gursoy, O. Gul and A.Kaypmaz, “Power quality and neutral Sept.2006.
currents in three-phase power systems,” in Proc.of Int. Conf.
Electrical Power Engg, Aug/Sept. 1999, pp.222.
[28] E. Ngandu and D. Paraiso, “Line and neutral current harmonics
characteristics in three-phase computer power systems,” in Proc. of
IEEE conf. on Electrical and Computer Engg., vol.3, May 2004,
pp.1659-1664.
[29] Jose Antenor Pomilio and Sigmar Maurer Deckmann,
“Characterization and Compensation of Harmonics and Reactive
Power of Residential and Commercial Loads,” IEEE Trans. Power
Delivery, vol. 22, no. 2, pp. 1049- 1055, April 2007.
• Zig-Zag Transformer Based Compensation

You might also like