Cause of Alarm A08526 PROFINET No Cyclic
Cause of Alarm A08526 PROFINET No Cyclic
https://support.industry.siemens.com/cs/ww/en/view/109478314
This entry is from the Siemens Industry Online Support. The general terms of use
(http://www.siemens.com/terms_of_use) apply.
Security Siemens provides products and solutions with industrial security functions that
informa- support the secure operation of plants, solutions, machines, equipment and/or
tion networks. They are important components in a holistic industrial security
concept. With this in mind, Siemens’ products and solutions undergo continuous
development. Siemens recommends strongly that you regularly check for
product updates.
For the secure operation of Siemens products and solutions, it is necessary to
take suitable preventive action (e.g. cell protection concept) and integrate each
component into a holistic, state-of-the-art industrial security concept. Third-party
products that may be in use should also be considered. For more information
about industrial security, visit http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-
specific newsletter. For more information, visit
http://support.industry.siemens.com.
Table of contents
Siemens AG 2015 All rights reserved
1 General................................................................................................................ 3
2 Setting the PG/PC interface and loading the configuration .......................... 4
3 Assigning a PROFINET device name .............................................................. 6
3.1 Version 1: Assigning a PROFINET device name 1 under
"Online access" .................................................................................... 6
3.2 Version 2: Assigning a PROFINET device name in the device
view ...................................................................................................... 8
1 General
Question
What is the cause of alarm A08526 "PROFINET: No cyclic connection" with quick
flashing red BF-LED?
Cause
1. The PROFINET device name is not assigned
2. The PROFINET device name is incorrect
3. The assigned PROFINET device name differs from the PROFINET device
name in the offline project
Solution
1. Assign the PROFINET device name, using TIA-portal
2. Follow the naming conventions:
Additional information on assigning addresses and names for PROFINET
devices can be found in the Help section in the TIA Portal, for example: "Index
-> Device name -> Assign PROFINET device name and address".
3. Assign consistent PROFINET device names
Siemens AG 2015 All rights reserved
NOTE When the "Generate PROFINET device name automatically" option is activated,
the device name is automatically derived from the configured name of the drive.
You cannot directly change this name. To indirectly change the PROFINET
device name, you change the name of the drive involved in General properties:
Siemens AG 2015 All rights reserved
Table 3-1
Stepp Task Screen shot
4-1 5. Under "Online access",
for the Ethernet card,
click on "Update
accessible devices".
6. For the SINAMICS 1
G120 device found, click
on "Online &
diagnostics" 2
Siemens AG 2015 All rights reserved
NOTE When the SINAMICS G120 already had a PROFINET device name, and the
PROFINET device name is changed, then the device must be restarted!
If you do not wish to restart the SINAMICS G120, then alternatively, the
PROFINET interface parameters can be reset, and the new, correct PROFINET
device name assigned to the SINAMICS G120.
The PROFINET interface parameters can be reset using the "Online access" ->
"Update accessible devices" -> "Online & diagnostics" -> "Functions" ->
"Resetting the PROFINET interface parameters" menu.
When the SINAMICS G120 did not have a PROFINET device name, and the
PROFINET device name is assigned for the first time, then the device does not
have to be restarted!
NOTE The PROFINET device name becomes effective immediately in the drive, even
when the drive already has had a PROFINET device name. No restart is
required.