630kVA 11-0.433kV Oil Distribution TX Datasheet

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

3/27/2019

Technical Datasheet Transformers 11 KV

STANDARD I.E.C 60076 OIL IMMERSED HERMETICALLY SEALED

Rated Power KVA 630


INSTALLATION
1 I/O
TYPE
2 ONAN

3 FREQUENCY Hz 50

4 B.I.L( BASIC INS. LEVEL) KV 75

5 SEPARATE SOURCE WITHSTAND VOLTAGE KV 28

6 PRIMARY VOLTAGE KV 11

7 SEPARATE SOURCE WITHSTAND VOLTAGE KV 3

8 SECONDARY VOLTAGE ( NO LOAD) V 433

9 TAPPING % +-2,5+-5

10 V. GROUP Dyn11

11 NO LOAD LOSSES W 1200

12 LOAD LOSSES AT 75oC W 9300

13 IMPEDANCE VOLTAGE % 6

14 HV BUSHINGS PORCELAIN 20 NF 250 ACC. TO D.I.N 42531

15 LV BUSHINGS PORCELAIN ACC. TO D.I.N 42530

16 ALTITUDE * m 1000
o
17 AMBIENT TEMPERATURE C 40

18 MATERIAL Cu/Cu

19 WEIGHT Kgr 2200


EFFICIENCY (cos φ= 1)
20
at 100% Load
% 98.36
at 75% Load
% 98.66

21 ACOUSTIC PRESSURE (at 1 m distance) dB(A) 64

22 DIMENSIONS ( LxWxH )( approximate value) mm 1750x1200x1700

NOTES:
DMCR Included
* *Altitude can be given at 2000m on request; IP54 cable boxes to be given on request.
1)The prices are valid for hermetically sealed with 4 bidirectional rollers,rating plate ,drain & sampling valve .
2)Schneider Electric will only be held responsible for certified drawings that are issued after order
3)Painting Final color RAL 7033
4) Routine test report will be submited for all the ordered T/Fs
5) Any equipment or service not clearly mentioned in this list is not included in the price
6) Tolerances on losses and impedance voltage will be subjected under I.E.C 60076 directions
7) T/Fs shall be filled with mineral oil acc. to IEC 60296

Manufacturer's Name: SCHNEIDER ELECTRIC Signature: Stamp & Date: