Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 7

Date Designed

WATER DEMAND CALCULATION & WATER BALANCE CHART Checked


Approved
Project : Embassy Zenith @ Bangalore
Type of Building(s) available : Malls Hospitals Hotels Office school Quarters Hostel Residence Airports Bus station/Rly stn Malls
Hospitals
Type of Building Office 4 Hotels
Office
Description Unit Enter value School
Office block population count
2 6283 Quar5%
No of drivers & staffs population count
3 265 265 Hos10%
No: of security & maintennace staffs No's 1 56 Resi
1 Airpo
1 Bus stn/Rly stn
1
1 1 meal/person
Others:
Landscaping Area in Sqm 4000
HVAC cooling tower make up water demand M3/day 88 (@10 Ltr/TR/hr)
DG cooling tower make up water demand M3/day 0 59
swimming pool + reflective pool volume M3 50
Water feature volume M3 0
Filter backwash water (STP) M3/d M3/day 15.0 (value in dbr) Domestic/drinking
Filter backwash water (WTP) M3/d M3/day 10.0 (value in dbr) 2.5 45 LPCD 0 IF(C7=4,"5%"
0

Reference for Domestic Drinking Flushing


Description Unit Population/Area/seats LPCD / Rate 'Diversity ?
LPCD/Rate
LPCD M3/D LPCD M3/D RO? LPCD M3/D

Ofiice block
Fixed population Nos 6283 45 LPCD 1 NBC 2019/SP35 20 125.7 5 31.4 N
2.0 20.0 125.7 6
Floating population Nos 942 15 Ltrs/person NBC 2019 4 3.8 1 0.9 N
2.0 10 9.4 3 6
Others: 6
No: of security & maintennace staffs 56 45 ltr/person NBC 2019 20 1.1 5 0.3 N- 20 1.1 6
No of drivers & staffs 265 15 ltr/person NBC 2019 4 1.1 1 0.3 N
2.0 10 2.7 6
TOTAL (M3/DAY) 131.6 32.9 138.9
OTHER REQUIRMENTS:
Landscaping irrigation Area in sqm= 4000 5 ltr/sqm
1 practical reqmnt 5 20.0 - - - - 6
Water loss thru RO reject RO recovery = 70% 0.0
WTP /STP filter & softener backwash loss 10.0 15.0
### Swimming pool ,reflecting pool,water feauture evoparation loss (cum) 50 2 practical reqmnt 0.1 5.0 - - - - 1 6
+ Misc: - Fire Make up water 2.0 2.0 6
37.0 17.0

WATER BALANCE CHART :


+
Swimming Loss thru
HVAC pool/water Filters Misc: - Fire
Domestic & Drinking Landscaping RO water req
Flushing (m3/day) requirement feature Backwash and Make up
(m3/day) (m3/day) (m3/day)
WATER DEMAND SPLIT-UP (m3/d) requirement RO reject water
( M3/DAY ) (m3/d) (m3/d)
(Rounded-off to zero decimal)

165.0 139.0 20.0 88.0 5.0 10.0 2.0 0.0

000000Sensitivity: LNT Construction Internal Use


#
Additional Inputs :
Description Enter value Flushing /Irrigation /others
Flushing usage from 1 Domestic /Drinking
RO recovery (in percentage) 70% 5 ltr/sqm
Total waste generated % from Domestic 85% 6ltr/sqm
Total waste generated % from flushing 100% 7 ltr/sqm STP treated water
Treated water % generated from STP 95% 8 ltr/sqm Domestic water
Filter backwash water (STP) M3/d 15.0 Domestic/drinking
Filter backwash water (WTP) M3/d 10.0
HVAC requirement sourced from 1 7 ltr/sqm
Landscaping irrigation requirement sourced from 1 1 8 ltr/sqm
Swimming pool /water feuture make-up sourced from 2 YES
NO
92
TOTAL FRESH WATER Misc: - Fire
Make up
182 M3/D water
2 m3/d
###
0 0 0
0 165 0 m3/d 0 m3/d 10.0 m3/d 0 m3/d

Domestic Flushing HVAC / DG Landscaping


RO Feed 0m3/d
requirement Requirment requirement requirement

0 m3/d 165 m3/day 139 m3/day 88 m3/d 20 m3/day


5
70% recovery 85% 141m3/d 139m3/d 100% m3/d

279.25
Swimming
RO water Requirement Filter back wash
(M3/DAY) Total waste generated pool/Water
water (STP&WTP)
feuture
0 m3/day 280 m3/day 5 m3/d 25 m3/day

Reject to waste 0 265.2875


0 m3/day m3/d 139 m3/d 0 m3/d 88 m3/d 15.0 m3/d 20 m3/d
STP

95% 266 m3/d


139 0 88 20
Treated waste water +
Make up water
0
265 m3/day

3.287
Excess
treated water
to municipal
drain
4 m3/d

~ SM

000000Sensitivity: LNT Construction Internal Use


#
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: STANDARDISATION - PHE DOCUMENT NO DATE


Standard 12.12.08
DESIGNED CHECKED SHEET
TITLE: Retail Water Demand calculation STGK/PEARL VSJ/ OS 1 OF 1

References for Specification:

NBC 2005:

Part : 4 Fire and Life safety - Table :20 Occupancy Load - Floating Population

For Mercentile (F)


Street Floor and Sales basement 3 m2/person
Upper Sales Floors 6 m2/person

As the retail floors are normally G+3 or G+2 ; On an average the floating population is taken as 4 m 2/person

Restaurant water requirement: 70 liters/seat (NBC pg:no 19)


Multiplex water requirment: 15 liters/seat (NBC pg:no 19)

Standard Book: Time savers Standards page no: 18.2 Table 1: Space allowance.

Restaurant Seating capacity : 1 seat/1.4 sq.mt ( Time savers Standards)

Food Court Capacity : 1 seat/1.4 sq.mt (Time savers Standards)

Multiplex Seating Capacity : 1 seat /1.5 sq.mt ( Time savers Standards)

Practical Requirement:

GYM water requirement : 10 litres/ 1 sq.mt

Hyper market water requirement : 10 litres/Sq.mt

Night Club water requirement : 3.7 litres/sq.mt

Fixed Population : 3 person/100 m2 or


10% of Floating Population
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: STANDARDISATION - PHE DOCUMENT NO DATE


Standard 12.12.08
DESIGNED CHECKED SHEET
TITLE: Back up for Hotel water demand Calculation PEARL VSJ/ OS 1 OF 1

References for Specification:

NBC 2005:

Part-9 Plumbing & Sanitary Table:1 pg.no:19

For 5 Star & above = 320 LPCD


Restaurant water requirement = 70 liters/seat
Flushing water requirement: out of 150 to 200 liters per head per day. 45 liters
per head per day may be taken for flushing
requirement s and the remaining quantity for other
domestic purpose.

Vendor details:

Laundry water requirement : 25 liters /Kg of Linen


Per meal water requirement for restuarant : 7 liters/meal ( As per SP35 pg.no: 50 )
But 10 liters /meal is adopted based on the some practical aspects like the population to
banquet hall is not constant, no.of sitting varies)

Hotel Operator Details:

As per IHG Standards : Staff population is 1.75 times the no.of rooms.
As per oberoi comments: Staff population is 2.25 times the no.of rooms.

000000Sensitivity: LNT Construction Internal Use


#
000000Sensitivity: LNT Construction Internal Use
#
DATE
12.12.08
SHEET

000000Sensitivity: LNT Construction Internal Use


#
000000Sensitivity: LNT Construction Internal Use
#

You might also like