U#1 TG SIDE DEFECT LIST

Sl No Unit-1 Defects List Dept


1 Water leakage from TDBFP-A mechanical seal cooler nde side TMD
temperaure gauge union
4 TMD
Steam leakage from Ext-4 to APRDS drain Miv Flange before NRV (0 mtr)
5 H2 filling line miv passing(6.9 m) TMD
6 LPH#6 condensate I/L mov not operating from DCS C&I
7 Vacuum pump#A PNDE gland water lkg. TMD
8 Gland steam overflow C/V limit setting required C&I
9 Gland steam overflow C/V passing TMD
10 HPH#1 shell side safety valve flange steam lkg. TMD
11 AUX.header interconnection mov steam lkg (inside insulation) TMD
12 LPH#5 condensate O/L mov upstream flange water lkg. TMD
13 Steam leakage from Ext-4 to APRDS drain Miv Flange before NRV (0 mtr) TMD
16 Main turbine BV-3Y and 4y vibration on higher side C&I
17 MS line left side drain miv dropwise water lkg. TMD
18 TDBFP#A booster pump suction line PRV passing TMD

19 MDBFP booster pump discharge line flow orifice flange having dropwise TMD
water lkg.
20 OCCW#B PNDE side gland lkg. TMD
21 TDBFP#A Ext.MOV 13 mtr. Gland leakage TMD
22 HPH-2 local level gauge top bolt leakage TMD
23 EXT.4 to TDBFP NRV leakage suspected at 13 mtr. TMD
24 Seal oil discharge header pressure gauge faulty C&I
25 Oil purifier vaccum pump pressure not developing. TMD
26 OCCW debris filter not available TMD
27 Dewatering pump B N/A TMD
28 CW ARV leakage from supply line TMD
29 Ext.1 drain valve 4 SOV having air leakage 6.9 mtr. TMD
30 Preheating drain to atmosphere passing at 6.9 mtr. TMD
31 Boiler EER package AC N/A TMD
32 Feed Water Tx-1 having deviation C&I
33 vaccum pump-B nde side gland leakage TMD
34 Stator water Demenilizer inlet before miv glang leakage TMD
35 Extraction 1 before NRV drain Passing TMD
36 Extraction 1 after NRV drain Passing TMD
37 APRDS Header drain Passing TMD
38 HPH 3 tube side drain Passing TMD
39 HPH 1 tube side drain Passing TMD

U#1 Steam and Water leakage In TG

1 Water leakage from TDBFP-A mechanical seal cooler nde side TMD
temperaure gauge union
2 Water leakage from TDBFP-B fire fighting line union joint TMD

4 TMD
Steam leakage from Ext-4 to APRDS drain Miv Flange before NRV (0 mtr)
7 Vacuum pump#A PNDE gland water lkg. TMD
10 HPH#1 shell side safety valve flange steam lkg. TMD
11 AUX.header interconnection mov steam lkg (inside insulation) TMD
12 LPH#5 condensate O/L mov upstream flange water lkg. TMD
13 MS line common drain miv inside insulation steam lkg. TMD
17 MS line left side drain miv dropwise water lkg. TMD

19 MDBFP booster pump discharge line flow orifice flange having dropwise TMD
water lkg.
20 OCCW#B PNDE side gland lkg. TMD
Notification No
1000189300

1000189303

5000037750
5000037751
1000191151
5000037752
5000037753

5000039461
5000039462
5000039463
5000039464
5000039465

1000189300
1000189301

1000189303

1000191151
U#1 BOILER SIDE DEFECT LIST
Sl NO U#1 Defects List Dept
1 PA fan#B fan side HP return line oil leakage BMD
2 Reheater flue gas Damper no 1, 2, 3 inoperative C&I/BMD
3 SH Spray second stage B down stream MOV gland leakage BMD
4 Soot blowing drain MOV of LHS LRSB not operative(MCB tripping) C&I
5 HRH saftey valve no 4 RHS passing BMD
6 Reheater Spray CV both passing BMD
7 D1 classifier inert MOV steam passing BMD
8 Wall blower drain MOV (left & Front,Right & back) inoperative from DCS C&I
9 PA Fan B motor winding temp T4 and T6 showing bad value in DCS C&I
10 PA fan B Bearing vibration is on higher side (X-5 mm/s) C&I
11 FD Fan#A motor winding temp. T3 showing bad value in DCS C&I
12 ID Fan#A bearing vibration-X maintaininghigher side C&I
13 D3 Coal pipe chocking C&I
14 Right Hopper Front Side 4 no. gate in damaged condition. C&I
15 DP2 of gas between ESP A inlet and Outlet (10HNA10CP103) is showing bad value in DCS C&I
16 Mill B motor lube oil cooler is not effective BMD
17 SADC- 6 Not available (AA1, AA3, A4, AB2, CC1, EF1) C&I
18 Right wall vertical tem (RWVT)-22 temp is showing wrong value in DCS C&I
19 Divisional platen SH-48 and 61 temp. value showing bad in DCS. C&I
20 FSH-6,FSH-52,FSH66,FSH-67 temp is showing bad value in DCS. C&I
21 LTRH-42 temp is showing bad value in DCS. C&I
22 Final RH 1 and 4 wall temp is showing bad value in DCS C&I
23 Mill-C RGB discharge hose oil seepage BMD
24 Defective soot Blower :- Wall blower 5 Nos not available, LRSB-L8 and R19 BMD
25 Mill Inerting HDR Inerting MIV gland lkg(13mtr) BMD
26 Seal trough makeup line from LP line(LHS) chocked AHP
27 Left wall vertical tem (LWVT)-1 to 12 value hunting in DCS C&I
28 SH Spray second stage B down stream MOV gland leakage BMD
29 Wall blowers drain MOV(Left&Right) & (Right&Back) is inoperative due to power cable issue EMD
30 SCAPH A i/l flange no#3 lkg ( front down side count ) internal inspection required. BMD
31 SCAPH B hdr main before drain wheel damage BMD
32 Water separetor #1 o/l steam press transmeter line drain up stream miv gland lkg BMD
33 Mill-F RGB return line oil seepage BMD
34 APH B support bearing temp. showing bad value in DCS C&I
35 ID fan-A outlet damper open fault C&I
36 Bottom Ash hopper left side red hot AHP
Unit -1 boiler Er
Defected mcb

Oil gun:- ab2, ab3,bc1,bc3,de1,de3,de4,ef1,ef3,ef4


Pkg AC:- b
mix air gate:- mill B&C
MDV:- c2
Feeder seal air:- d1,e1,f2
Classifier steam inerting:- b2
Mill steam inerting:- f2